Turbine Control Parameters

The 505E interfaces with two control valves (HP & LP) to control two parameters

and limit an additional parameter, if desired. These two controlled parameters are

typically speed (or load) and extraction/admission pressure (or flow), however,

the 505E could be utilized to control or limit: turbine inlet pressure or flow,

exhaust (back) pressure or flow, first stage pressure, generator power output,

plant import and/or export levels, compressor inlet or discharge pressure or flow,

unit/plant frequency, process temperature, or any other turbine related process

parameter. Refer to Volume 2 for details on applications.

Communications

The 505E can communicate directly with plant Distributed Control Systems

and/or CRT based operator control panels, through two Modbus® *

communication ports. These ports support RS-232. RS-422. or RS-485

communications using ASCII or RTU MODBUS transmission protocols.

Communications between the 505E and a plant DCS can also be performed

through hardwired connections. Since all 505E PID setpoints can be controlled

through analog input signals, interface resolution and control is not sacrificed.

*—Modbus is a trademark of Schneider Automation Inc.

Additional Features

The 505E also provides the following features: First-Out Trip Indication (5 total

trip inputs), Critical Speed Avoidance (2 speed bands), Auto Start Sequence (hot

& cold starts), Dual Speed/Load Dynamics, Zero Speed Detection, Peak Speed

Indication for Overspeed trip, and Isochronous Loadsharing between units.

Using the 505E

The 505E control has two normal operating modes, the Program Mode and the

Run Mode. The Program Mode is used to select the options needed to configure

the control to your specific turbine application. Once the control has been

configured, the Program Mode is typically never again used, unless turbine

options or operation changes. Once configured, the Run Mode is used to operate

the turbine from start-up through shutdown. In Addition to the Program and Run

modes, there is a Service Mode which can be used to enhance system operation

while the unit is running. Refer to Volume 2 for information on the Service Mode.

505E Inputs and Outputs

Control Inputs

Two speed inputs which are jumper configurable for MPU (magnetic pickup units)

inputs or proximity probes.

Six analog inputs are available.  One is dedicated as the extraction/admission

input.  The remaining five are configurable.  The sixth analog input has isolation

circuitry and should be used for a self-powered signal that is not isolated.

Sixteen contact inputs are available. Four are dedicated for shutdown, reset,

raise speed setpoint, and lower speed setpoint. Another two contact inputs must

be dedicated for generator breaker and utility tie breaker if the control is used in a

generator application. Ten additional contact inputs can be configured. If the unit

is not used in a generator application, then twelve additional contact inputs can

be configured.

Four function keys on the front panel of the control. F1 and F2 are dedicated to

alarm and overspeed test, respectively. F3 and F4 can be used to enable or

disable various functions of the control.

Control Outputs

Two actuator outputs with linearization curves for the HP and the LP valve

outputs.

Six 4–20 mA outputs, for meters or other readouts.

Eight Form-C relay contact outputs, six that are configurable. The two dedicated

relay outputs are for shutdown and alarm indication.

Control Communications

Two Modbus ports, to be used as control interfaces. The protocol can be either

ASCII or RTU and the communications can be RS-232. RS-422. or RS-485.

One computer (PC) port to be used for program configuration storage.

An overview of the 505E functions is shown in Figure 1-1. Use this block diagram

to match the control features to the site-specific application required.

The 505E Digital Governor is designed to control extraction, extraction/

admission, or admission steam turbines. The difference between these turbines

is the capability of the turbine to allow low pressure steam, which is at a lower

pressure than the inlet, to enter and/or exit the turbine. An extraction turbine

allows the lower pressure (extraction) steam to exit the turbine only and will have

a non-return valve in the extraction header/line to prevent steam from entering

the turbine. An admission turbine (also called induction) will allow excess header

steam to enter the turbine through the low pressure inlet. An extraction/admission

turbine will allow low pressure header steam to enter or exit the turbine

depending on system pressures. A turbine with admission capability will have a

stop valve or trip-and-throttle valve in the low pressure line to prevent steam from

entering the turbine when the unit is tripped. The type of turbine used will depend

on the system requirements and must be designed by the turbine manufacturer

to perform the functions required.

The 505E has two independent control channels available, the speed/load and

auxiliary controllers. The outputs of these two controllers are low-signal-selected

(LSS) to provide to speed/load demand signal to the ratio/limiter. In addition to

these channels, the speed/ load controller can be manipulated by another

controller, the cascade controller. The cascade controller is ‘cascaded’ into the

speed controller, whereby the speed controller setpoint is changed directly by the

cascade controller output. The auxiliary controller can act as either a control

channel or as a limiting channel. All three of these PID controllers have the

option of utilizing an analog input signal to remotely position their setpoints.

Additional features of the 505E include frequency control, isochronous

loadsharing, critical speed avoidance, idle/rated control, and an automatic start

sequence. There are two serial communications ports which can be used to

monitor and control the turbine using Modbus protocol.

Extraction Turbines

The 505E control can be configured to operate single automatic extraction

turbines by controlling the interaction of the governor (HP or high pressure) valve

and the extraction (LP or low pressure) valve. (The 505E can also operate the

governor valve and the first extraction valve of multiple extraction turbines).

Single automatic extraction turbines have a high pressure stage and a low

pressure stage, each controlled by a valve. Steam enters the turbine through the

HP valve (see Figure 1-2). At the downstream end of the HP turbine stage and

before the LP valve, steam can be extracted. The LP valve controls the entry of

steam into the LP turbine stage, and the diverting of steam through the extraction

line. As the LP valve is opened, more steam enters the LP stage and less is

extracted.

In most cases, the operator of an extraction turbine needs to maintain both

turbine speed/ load and extraction pressure/flow at constant levels. Changing the

position of either the HP valve or the LP valve affects both turbine speed/load

and extraction. If either the load on the turbine or the extraction demand

changes, both the

Admission Turbines

The 505E control can be configured to operate single automatic admission

turbines by controlling the interaction of the governor (HP or high pressure) valve

and the extraction (LP or low pressure) valve.

Single automatic admission turbines have a high pressure stage and a low

pressure stage, each controlled by a valve.  Steam enters the turbine through the

HP valve (see Figure 1-3) and at the downstream end of the HP turbine stage,

before the LP valve.  The LP valve controls the entry of steam into the LP turbine

stage and through the admission line.  As the LP valve is opened, more steam

enters the LP stage.

In most cases, the operator of an admission turbine needs to maintain both

turbine speed/ load and admission pressure/flow at constant levels.  Changing the

position of either the HP valve or the LP valve affects both turbine speed/load

and admission.  If either the load on the turbine or the admission demand

changes, both the HP valve position and the LP valve position must be changed

to maintain speed/load and admission.

The movement of both valves is automatically calculated by the 505E’s ratioing

logic based on the turbine performance parameters to minimize valve/process

interaction.

Extraction and Admission Turbines

The 505E control can be configured to operate single automatic extraction and

admission turbines by controlling the interaction of the governor (HP or high

pressure) valve and the extraction (LP or low pressure) valve.

Single automatic extraction and admission turbines have a high pressure stage

and a low pressure stage, each controlled by a valve.  Steam enters the turbine

through the HP valve (see Figure 1-2).  At the downstream end of the HP turbine

stage and before the LP valve, steam can either be extracted or admitted

(inducted) into the LP turbine stage.  The LP valve controls the entry of steam into

the LP turbine stage.  As the LP valve is opened, more steam enters the LP stage

and less is extracted.

In most cases, the operator of an extraction turbine needs to maintain both

turbine speed/ load and extraction or admission pressure/flow at constant levels.

Changing the position of either the HP valve or the LP valve affects both turbine

speed/load and extraction or admission.  If either the load on the turbine or the

extraction / admission demand changes, both the HP valve position and the LP

valve position must be changed to maintain speed/ load and extraction/

admission.  The movement of both valves is automatically calculated by the

505E’s ratioing logic based on the turbine performance parameters to minimize

valve/process interaction.

Speed Control

The speed control receives a turbine speed signal from one or two magnetic

pickups or proximity probes.  The speed PID (proportional, integral, derivative)

control amplifier then compares this signal to the speed setpoint to generate an

output signal to the ratio/ limiter (through a low signal select bus).

Extraction/Admission Control

The Extraction/Admission (Extr/Adm) control receives an extraction/admission

(4–20 mA) signal from a pressure or flow transducer. The Extr/Adm PID

controller then compares this signal to the setpoint to generate an output signal

to the Ratio/Limiter.

The Extr/Adm control can also receive a programmable (optional) droop

feedback signal to increase the stability of the extraction control loop.

The Extr/Adm setpoint is adjustable with raise or lower commands through the

keypad on the front of the control, the remote contact inputs, or the

communication links. Also, the setpoint can be directly set by entering the new

setpoint from the keypad or through either Modbus communications link. In

addition, a remote extr/adm setpoint analog input can be programmed to

remotely position the Extr/Adm setpoint.

Remote Extraction/Admission Setpoint

One of the 4–20 mA inputs can be configured to remotely adjust the Extr/Adm

setpoint. The remote setpoint input directly affects the 505E’s Extr/Adm setpoint.

The maximum rate at which the remote input signal can change the setpoint is

programmable and can be changed in the Run mode. When the remote setpoint

is enabled, the Extr/Adm setpoint will move at a much slower rate until the two

settings are matched, at which point the setpoint will be allowed to move at the

maximum rate. The remote setpoint function can be enabled and disabled as

required from the front-panel keypad, the remote contact inputs or either Modbus

communication link.

Ratio/Limiter

The Ratio/Limiter receives input signals from the speed (or aux) and extr/adm

control PIDs. The ‘ratio’ logic uses these signals and, based on the turbine

performance parameters, produces two output signals, one to control the HP

actuator and one to control the LP actuator. The ‘limiter’ logic keeps the actuator

outputs within the boundaries of the turbine steam map.

The ratio logic controls the interaction of both HP and LP valves to maintain

desired turbine speed/load and extraction/admission pressure/flow levels. By

controlling valve interaction, the ratio logic minimizes the effects of one controlled

process on the other controlled process.

When speed/load or extraction/admission demands cause the turbine to reach an

operating limit, the limiter logic limits the HP or LP valves to maintain speed/load

or extraction/ admission demands depending on the priority selected




  • WOODWARD 5448-890 SPM-D10 Series One Breaker Synchronizer
  • FOXBORO 43AP-FA42D/PB-AA 43AP Pneumatic Indicating Controllers
  • Stucke Elektronik SYMAP®G generator protection
  • Stucke Elektronik SYMAP®F feeder protection
  • Stucke Elektronik SYMAP®ECG engine control and generator protection
  • Stucke Elektronik SYMAP®EC Engine Control
  • Stucke Elektronik SYMAP®ARC Arc protection system
  • Stucke Elektronik SYMAP®R Digital protection system
  • Stucke Elektronik SYMAP® Compact Digital protection and control equipment
  • LEYBELOD SV40 BI Single-stage, oil-sealed rotary vane pump
  • LEYBELOD TURBOVAC 361 (C) Suspension turbomolecular pump
  • LAND M2300/1100C-V Industrial Control Module
  • LAMBDA LZS-1500-3 Single Output Industrial Power Supplies
  • LAMBDA LZS-A1500-3-001 POWER SUPPLY
  • LAMBDA HWS1500-24 Power supply
  • Kongsberg K-Chief Control Room Panel (CRP) 603525
  • Kongsberg MSI-12 Input/Output Module 339368
  • Kongsberg dPSC Dual Process Segment Controller Module 8100183
  • HHirschmann Modular OpenRail Fast Ethernet switch 8-24 ports MS20-1600SAAEHH08.0
  • Hirschmann MM20-Z6Z6Z6Z6SAHH ETHERNET / Fast-ETHERNET Media Modules
  • Hirschmann MM2-2FXM3/2TX1 ETHERNET / Fast-ETHERNET Media Modules
  • Hirschmann Industrial ETHERNET Switch MICE MS20/MS30
  • Hirschmann MACH102-24TP-FR Gigabit Ethernet industrial workgroup switch
  • Hirschmann MM2-4TX1 MICE switch medium module
  • Hirschmann MICE switch medium module MM2-2FXS2
  • ABB AFS670 19" Ruggedized Switch AFS670-EREEDDDSSEEEEEEEPZYX05.1.0
  • NI Controller for VXI VXIPC-871B
  • GE VMIVME-1150 Serial Communications Controller
  • GE Hydran M2-X Enhanced Monitoring with Extended Sensor Life
  • GE IC660BBD022 I/O module
  • GE Digital Energy D20 Analog Input Module
  • Foxboro FBM I/O cards PBCO-D8-009
  • GE SR750-P5-G5-S5-HI-A20-R-E Multilin Relay
  • ABB 3BSE019050R1000 PFTL 301E 1,0kN, Load cell
  • Foxboro DNBT P0971WV Dual-node bus module of I/A series
  • EPRO MMS6210 Dual-channel axial displacement measurement module
  • EMERSON PMCspan PMC Expansion Mezzanine
  • EMERSON KJ3242X1-BK1 12P4711X042 S-Series H1 Card
  • EMERSON KJ4006X1-BD1 Interface Terminal Block
  • EMERSON KJ4001X1-CK1 40-Pin Mass Termination Block
  • ABB UCD224A103 Industrial controller module
  • ABB ARCOL 0339 Solid-state motor controller
  • ABB UFC718AE01 HIEE300936R0101 Main Circuit Interface Board
  • Abaco VME-REPEATL-485 VMEBus Repeaters
  • Abaco VME-4900 Digital-to Synchro/Resolver Board
  • Abaco VME-4911 digital converter board
  • Abaco XM-664-80 Transition module with rear I/O access to VIPC664
  • Abaco TPMCC 6U VME triple PMC carrier for use with the V5C SBC
  • Abaco VIPC8243 is an intelligent 6U VME carrier board
  • Abaco DCPMC Conduction-cooled or Rugged PMC Carrier
  • Abaco CP237 is a 6U CompactPCI Card
  • Abaco VME-3413 32-Channel Signal Conditioning Board
  • Abaco VME-3125 VME Analog I/O Input Boards
  • Alstom GE SPU232.2. 029.366.817 Single Processor Unit SPU2322
  • ALSTOM COP232.2 VME A32/D32, 029.232 446 controller unit
  • ICS TRIPLEX T8111C​ Trusted TMR Processor
  • VMIC VMIVME-7740 VME Single Board Compute 750
  • foxboro FBM232 Field Device System Integrator Module P0926GW
  • GE 04220HL21204A IPC Control Module
  • ABB 3BSE000860R1 SB510 Backup Power
  • ABB 0504994880 Controller unit
  • ABB PFSA140 3BSE006503R1 Industrial robot Supply Unit
  • ABB 5SHX1445H0002 3BHL000387P0101 POWER IGCT unit
  • ABB 128877-103 CABLE, SP1200 IR DET.
  • ABB CI853K01 and TP853 RS-232C Interface
  • ABB REM610 MOTOR PROTECTION RELAY REM610C11HCNR
  • ABB IGBT 5SDF0860H0003 5SDF1045H0002 unit
  • ABB TC512V1 3BSE018059R1 RS485 Twisted pair Modem
  • ABB DO880 S800HI 3BSE028602R1 Digital Output
  • ABB GDD360C 3BHE047217R0101 Advanced Automation Solution
  • ABB UCD240A101 3BHE022287R0101 controller unit
  • ABB AC800F Ethernet Module AM811F 3BDH000050R1​
  • ABB AC800F Module AM801F 3BDH000040R1
  • ABB SD802F 3BDH000012R1 POWER UNIT
  • ABB operation panel PM820-2 3BSE010798R1 system module
  • ABB operation panel PM820-1 3BSE010797R1 system module
  • ABB CI857K01 3BSE018144R1 INSUM Ethernet Interface
  • ABB PM861/PM861AK01 and TP830 Processor Unit
  • ABB SA811F 3BDH000013R1 Power Supply 115/230 VAC
  • ABB 751010R0815 1VC1T0374A00R unit
  • 5SGY35L4510 Robot high voltage board Brand ABB
  • ABB HVC-02B 3HNA024966-00103 Robot high voltage board Brand HVC02B
  • ABB SLMG99 UNIT
  • ABB 086406-002 PWA.SIOC. SMART I/O CALIP 086407-502
  • ABB UCD208A101 3BHE020018R0101 UNIT
  • ABB UAD154A 3BHE026866R0101 UNIT
  • ABB GCD207B101 3BHE024642R0101 controller card
  • ABB TB820V2 S800 Modulebus module 3BSE013208R1
  • ABB UDD406A 3BHE041465P201 Control unit
  • ABB PPD113B01-10-150000 3BHE023784R1023 unit CPU module
  • ABB 5SHY35L4512 3BHE014105R0001 5SXE08-0166 IGCT unit
  • ABB Backplane Uni Type3+housing FETD685A1156U01
  • ABB 07DC91C GJR5251400R0202 Digital input and output Unit
  • ABB UNS2881b-P,V1 3BHE009319R0001 UNS2881BPV1 Inspirational system
  • ABB UNS2880B-P,V2 3BHE014967R0002 UNS2880B-PV1 Inspirational system
  • ABB CI810B 3BSE020520R1 AF 100 Fieldbus Comm. Interface
  • ABB FM9925a-E HIEE451116R0001 Interface Module Card
  • Bently 2300/25 0002 Vibration Monitors
  • Bently 2300/20 0002 Vibration Monitors
  • ALSTOM VP327 020-23EU 75X-6025-29 Control mainboard VP32702
  • ABB NE802 3BSE080237R1 Industrial switch
  • ABB 3BSE080207R1 NE810 Industrial switch
  • MOTOROLA MVME2400 VME Processor Modules
  • ABB 3BHE021481R0001 intelligent current distr UNIT
  • MOTOROLA MVME2434 VME Processor Modules
  • METSO PDP606 CONTROLLER unit
  • WOODWARD PG-PL-29 Governor 8577-613
  • GE IS230TNRLH1B Combination module kit Mark VI
  • GE IS230TNAIH2C Combination module kit Mark VI
  • ABB 3ASC25H204 DAPU 100 Control board I/O
  • ABB 3BHE014070R0101 V PPC905AE101 CCB-2 COMPLETE
  • ABB PRC3BSE050198R1 PM866K01 Processor Unit
  • Kongsberg RAIV400 600370 Remote Analogue Input
  • ABB SPSED01 event sequence module
  • ABB HIEE300900R0001 PP C322 BE01 PSR-2 processor + fieldbus
  • ABB 3BHE003604R0102 UFC765AE102 circuit board
  • ABB ACU-01B 3HNA024871-001 Robot controller
  • ABB XVC770BE101 3BHE021083R0101 circuit board
  • ABB UAC383AE01 HIEE300890R0001 Module
  • ABB REF610C11LCNP FEEDER PROTECTION RELAY
  • ABB MT91 Operator Panel MT-91-ARC FP A
  • ABB XUD194 XUD194A 3BHC018137R0001 module base
  • ABB 5SHY4045L0001 3BHB018162 3BHE009681R0101 GVC750BE101
  • ABB G2000A5.7ST graphical operation panel (HMI)
  • ABB 3BHE017628R0002 PPD115A02 SG579989013
  • ABB Motor Protection and Control REM615 Product Guide
  • ABB PFTL101B 3BSE004185R1 2.0KN sensor
  • ABB PFCL201CE 50KN 3BSX802939-108 sensor