The recordings can be uploaded with a DR Collector Tool which converts the data to a COMTRADE format. The DR-Collector Tool is supported in CAP501 and CAP505 relay tools.
Power quality functions
Power quality functions enable measurement of total harmonic distortion (THD) of voltage and current, and total demand distortion (TDD) of current. Individual harmonics are measured up to 13th.
The power quality functions produce statisti cal data about harmonic distortion for long term evaluation. Short time average and max imum values for THD and individual har monics are also supported.
LIB 510 supports graphical presentation of harmonics in the PQ Monitoring Tool.
Control functions
The control functions are used to indicate the status of switching devices, i.e. circuit break ers and disconnectors, and to execute open and close commands for controllable switch ing devices of the switchgear. Furthermore,
control functions provide on/off switching objects for control logic purposes and miscel laneous objects for data monitoring, etc. The control functions configured with the CAP 505 Relay Product Engineering Tools are linked to object status indicators included in the MIMIC configuration picture displayed on the MMI. The object status indicators are used to indicate the status of switching devices via the MIMIC picture and to control them locally. The status of different objects, e.g. open/close/undefined, displayed in the MIMIC view can be freely designed.
Condition monitoring functions
Condition monitoring function blocks such as supervision of the energizing current and voltage input circuit, operation time counter, circuit breaker electric wear, scheduled main tenance, trip circuit supervision and breaker travel time are available for the REF 54_ feeder terminals.
General functions
Additional functions are available for differ ent general purposes to be used in logics such as activation of MMI backlight, switch groups, and resetting of operation indications, latched output signals, registers and distur bance recorder.
Communication functions
The feeder terminal REF 54_ provides two serial communication protocols: SPA and LON.
Standard functions
Standard functions are used for logics such as interlocking, alarming and control sequenc ing. The use of logic functions is not limited and the functions can be interconnected with each other as well as with protection, mea surement, power quality, control, condition monitoring and general functions. In addition, the digital inputs and outputs and LON inputs and outputs can be connected to standard functions by using the Relay Configuration Tool.
Other functions
Low auxiliary voltage indication The REF 54_ feeder terminal is provided with a low auxiliary voltage indication fea ture. The power supply module issues an internal alarm signal when a drop in the power supply voltage is detected (ACFail, active low). The alarm signal is activated if the power supply voltage falls about 10% below the lowest rated DC input voltage of the power supply module. The indication of a low auxiliary voltage is available in the feeder terminal configuration environment and can be configured to acti vate an alarm. Overtemperature indication The REF 54_ feeder terminal includes an internal temperature supervision function. The power supply module issues an internal alarm signal when overtemperature has been detected inside the terminal enclosure. The alarm signal will be activated once the tem perature inside the terminal enclosure increases to +78°C (+75°...+83°C). Over temperature indication is available in the feeder terminal configuration and can be con figured to activate an alarm. Analogue channels The feeder terminal measures the analogue signals needed for protection, measuring, etc. via sensors or galvanically separated match ing transformers. Depending on whether sensors are included or not, REF 54_ feeder terminals have 9 (without sensors) or 10 (with sensors) ana logue channels. The number of channels used depends on the feeder terminal configuration and the kind of matching transformers or sen sor inputs used. In addition to 9 conventional matching trans formers, sensors developed by ABB can be used parallel in REF 54_ feeder terminals. The feeder terminal has 9 sensor inputs. A current sensor (Rogowski coil) or a voltage divider can be connected to each sensor input. Please, see the connection diagram below for details. When ordering, please note the type of analogue inputs. Analogue channels of the feeder terminal are configured with the CAP 505 Relay Product Engineering Tools. A separate scaling factor can be set for each analogue channel. The factors enable differ ences between the ratings of the protected unit and those of the measuring device (CTs, VTs etc.). The setting value 1.00 means that the rated value of the protected unit is exactly the same as that of the measuring device.
ABB REU615E_D
ABB UFC911B108 3BHE037864R0108
ABB IMRIO02
ABB REM610C55HCNN02
ABB TU811
ABB PFVK135
ABB KUC321AE HIEE300698R1
ABB PFSA103D 3BSE002492R0001
Add: Building F05, High-tech Software Park, Xiamen City, Fujian Province
Tel: 0592-5211302
Mobile: 17750019513 (WhatsApp)
Email: yy4291644@gmail.com
ivy@kongjiangauto.com
Website: https://www.abb-sis.com