Description
The 4-Channel Relay Module is a full-height module that provides four relay outputs. Any number of 4-Channel Relay Modules can be placed in any of the slots to the right of the Rack Interface Module. Each output of the 4 Channel Relay Module can be independently programmed to perform needed voting logic. Each relay utilized on the 4-Channel Relay Module includes "Alarm Drive Logic". The Alarm Drive Logic is programmed using AND and OR logic, and can utilize alarming inputs (alerts and dangers) from any monitor channel or any combination of monitor channels in the rack. This Alarm Drive Logic is programmed using the 3500 Rack Configuration Software to meet the specific needs of the application. Note: Triple Modular Redundant (TMR) applications require the use of the 3500/34 TMR Relay Module. Consult Bently Nevada Specification and Ordering Information part number 141534-01 for details. Specifications Inputs Power Consumption: 6 Watts typical. Outputs OK LED: Illuminated when module is functioning properly. TX/RX LED: Transmit and Receive. Flashes to indicate proper communications between this module and other modules within the rack. CH ALARM LED: Illuminated to indicate that the Relay Channel is in an alarm state. Relays Type: Two single-pole, double-throw (SPDT) relays connected in a double-pole, double-throw (DPDT) configuration. Environmental Sealing Epoxy-sealed. Arc Suppressor 250 Vrms, installed as standard. Contact Life 100,000 cycles @ 5 A, 24 Vdc or 120 Vac. Operation Each channel is switch selectable for Normally De-energized or Normally Energized.
-30°C to +65°C (-22°F to +150°F). Storage Temperature: -40°C to +85°C (-40°F to +185°F). Humidity: 95%, non-condensing. CE Mark Directives EMC Directives: EN50081-2: Radiated Emissions EN 55011, Class A Conducted Emissions EN 55011, Class A EN50082-2: Electrostatic Discharge EN 61000-4-2, Criteria B Radiated Susceptibility ENV 50140, Criteria A Conducted Susceptibility ENV 50141, Criteria A Electrical Fast Transient EN 61000-4-4, Criteria B Surge Capability EN 61000-4-5, Criteria B Magnetic Field EN 61000-4-8, Criteria A Power Supply Dip EN 61000-4-11, Criteria B Radio Telephone ENV 50204, Criteria B Low Voltage Directives: Safety Requirements EN 61010-1 Hazardous Area Approvals CSA/NRTL/C: Class I, Division 2, Groups A through D. Contact Ratings Resistive load: Max switched power: dc: 120 W ac: 600 VA Minimum switched current: 100mA @ 5 Vdc Max switched current: 5 A Max switched voltage: dc: 30 Vdc ac: 250 Vac Physical Main Module: Dimensions (Height x Width x Depth): 241 mm x 24.4 mm x 242 mm (9.50 in x 0.96 in x 9.52 in). Weight: 0.7 kg (1.6 lbs.). I/O Module: Dimensions (Height x Width x Depth): 241 mm x 24.4 mm x 99.1 mm (9.50 in x 0.96 in x 3.90 in). Weight: 0.4 kg (1.0 lbs.). Rack Space Requirements Main Module: 1 full-height front slot. I/O Modules: 1 full-height rear slot. Ordering Information 3500 4-Channel Relay Module 3500/32 -AXX-BXX Option
Descriptions
A: Output Module 0 1 4-Channel Relay I/O Module
B: Agency Approval Option 0 0 None 0 1 CSA/NRTL/C FOR REFFERENCE ONLY Spares 125712-01 125720-01 04425545 132319-01 04400037 00580436 129771-01 Spare 4-Channel Relay Module Spare 4-Channel Relay I/O Module Grounding Wrist Strap (single use) Firmware IC IC Removal Tool Connector Header, Internal Termination, 6-position, Green 4-Channel Relay Module Manual
Add: Building F05, High-tech Software Park, Xiamen City, Fujian Province
Tel: 0592-5211302
Mobile: 17750019513 (WhatsApp)
Email: yy4291644@gmail.com
ivy@kongjiangauto.com
Website: https://www.abb-sis.com