VIBRO-METER IOC4T 200-560-000-114 I/O interface card
VIBRO-METER IOC4T 200-560-000-114 I/O interface card
AMC8 analog monitoring card (ABE04x and ABE056)
The AMC8 card has the following panel elements (see Figure2-10):
1-One global DIAG/STATUS indicator for the AMC8/IOC8T card pair
This multi-coloured, multi-function LED is used to indicate:
• The status of the card configuration
• Possible hardware errors
• Whether the Danger Bypass (DB) special function is in use.
2-Status indicators for the 8 measurement channels
Each multi-coloured, multi-function LED is used to indicate:
• Whether the signal input for that channel is valid
• The presence of an incoming signal in the Alert/Danger condition
• Whether the channel inhibit function is in use.
3-RS-232 connector
This 9-pin D-sub connector can be used to configure an AMC8 card in a stand-alone
rack. This is done via an interface cable from a computer running one of the VM600
MPSx software packages (MPS1 or MPS2). See Figure2-7 for details of the interface
cable.
2.5 IOC8T input/output card (ABE04x and ABE056)
The IOC8T panel (rear of rack) contains four contact strips, identified as J1 to J4.
Strips J1 to J3 consist of a socket and a mating connector, which contains either 24 or 20
cage clamp terminals (see Figure2-9). The terminals can accept wires with a cross-section
of between 0.08 and 1.0mm2.
Strip J4 consists of a socket and a mating connector, which contains 12 screw terminals. The
terminals can accept wires with a cross-section of ≤1.5mm2
DIAG/STATUS indicator for the AMC8/IOC8T card pair.
The colours of the LED have the following significance:
* Green(continuous) – Normal operation (configuration valid with no active
alarms and no errors).
* Green blinking – Card is configured but still in the stabilisation phase.
* Yellow(continuous) – There is an active multi-channel processing
Alert level alarm ((A−) or (A+)).
* Yellow blinking – Configuration error and/or signal processing error.
* Red(continuous) – There is an active multi-channel processing
Danger level alarm ((D−) or (D+)).
* Red blinking – Hardware error or card not yet configured.
Status indicator for the AMC8/IOC8T card pair measurement channel1.
The colours of the LED have the following significance:
* Off – Channel not configured or card not configured.
* Green(continuous) – Signal input to the channel is valid and there are
no active alarms.
* Green blinking – Signal input to the channel is not valid.
* Green blinking slowly – Channel inhibit function active.
* Yellow(continuous) – There is an active single-channel processing
Alert level alarm ((A−) or (A+)).
* Red(continuous) – There is an active single-channel processing
Danger level alarm ((D−) or (D+))
| Foxboro | FBM203TA PO916AE |
| Foxboro | P0916DE |
| ABB | 3BHE057901R0101 PCD235C101 |
| Triconex | 3704E |
| Triconex | 3504E |
| Triconex | 3504E |
| EMERSON | 1X00781H01L |
| EMERSON | PR6423 009-041+CON 041/913-030 |
| KONSGBERG | RCU500 |
| KONSGBERG | RMP400 |
| KONSGBERG | RDIOR400 |
| Cutler Hammer | 1775K PMPP1700 |
| MOORE INDUSTRIES | MDS/PRG/10-30DC/-MAO |
| ABB | DHH805-A |
| Wago | I/O-IPC 758-873 |
| CONVERTEAM | MVS3000-4001 |
| GE | MX150 |
| GE | IS215ACLEH1A |
| User name | Member Level | Quantity | Specification | Purchase Date |
|---|
Add: High-tech Software Park, Xiamen City, Fujian Province
Mobile: +86-17750019513(WhatsApp)
Email: yy4291644@gmail.com
Website: https://www.abb-sis.com