General notes
df/dt (rate of change of frequency) monitoring measures the stability of the frequency.
The frequency of a source will vary due to changing loads and other effects. The rate of
these frequency changes due to the load variances is relatively high compared to those of
a large network
Voltage Increase
General notes
Voltage is monitored depending on parameter "Monitoring" (parameter ╚═▷ 8806). This
function allows the monitoring of the voltage quality over a longer time period. It is
realized as a 10 minute moving average. The function is only active, if the frequency is
larger than 60 % of the nominal frequency. If "Voltage measuring" (parameter ╚═▷ 1851)
is configured to a three-phase measurement, the slow voltage increase alarm is
monitoring the individual three-phase voltages according to parameter “AND
characteristics” (parameter ╚═▷ 8849).
QV Monitoring
General notes
In case of undervoltage some grid codes require a special monitoring function to avoid
the import of inductive reactive power at the interchange point. The QV monitoring is a
function of voltage and reactive power. To prevent malfunction, a "Minimum current"
(parameter ╚═▷ 3287) must be configured.
QV monitoring is triggered if the following conditions are fulfilled: (Refer to ╚═▷ Fig. 39 for
details)
QV monitoring is configured to "On" (parameter ╚═▷ 3292)
Measured reactive power is higher than the configured “Reactive power threshold”
(parameter ╚═▷ 3291)
Measured average current is higher than the configured “Minimum current”
(parameter ╚═▷ 3287)
Measured voltages are below the configured “Limit undervoltage” (parameter ╚═▷
3285)
As a result Timer 1 and Timer 2 are starting. If the delay time "Delay step 1" (parameter
╚═▷ 3283) has exceeded, the specified relay for step 1 is energized. If the delay time
"Delay step 2" (parameter ╚═▷ 3284) has exceeded, the specified relay for step 2 is
energized
Overcurrent (Level 1. 2 & 3) ANSI# 50/51
General notes
Current is monitored according to how the parameter "Current measuring"
(parameter ╚═▷ 1850) is configured. This controller provides the user with three definite
time alarm levels for overcurrent faults.
Monitoring of the maximum phase current is performed in three steps. Every step can be
provided with a delay time independent of the other steps
Ground Fault (Level 1 & 2)
Calculated ground fault
The current is monitored depending on how parameter "Current measuring" (parameter
╚═▷ 1850) is configured. The measured three conductor currents IL1. IL2 and IL3 are
vectorially totaled (IS = IL1 + IL2 + IL3) and compared with the configured fault limit (the
calculated actual value is indicated in the configuration software). If the measured value
exceeds the fault threshold limit, the configured relay is energized.
| HITACHI | LYA010A |
| HITACHI | LYD105A |
| HITACHI | LYA210A |
| HITACHI | TD000A |
| HITACHI | LYA220A |
| HITACHI | LYA100A |
| HITACHI | LUD700A |
| HITACHI | LPF240A |
| HITACHI | LYT000A |
| HITACHI | LPU100H |
| HITACHI | LPA245A |
| HITACHI | LPA220A |
| HITACHI | LPD220A |
| HITACHI | LPD350A |