MTL 8507-BI-DP, the ultimate solution for power industry, petrochemical industry and general automation.
PAC8000
8507-BI-DP BIM and 8701-CA-BI Carrier
GFK-2577D
June 2013
PROFIBUS DP Bus Interface Module and Carrier
The 8507-BI-DP Bus Interface Module (BIM) provides the communications link between the PAC8000
series I/O modules and a PROFIBUS-DP host. High-speed acquisition of data from the modules and LAN
operation speeds of up to 12 Mbaud allow the host to respond rapidly to changes in process conditions.
The BIM gathers data from the I/O modules and makes it available to the host upon request. It is a slave to
the PROFIBUS master. As well as cyclic data exchange, which is required for reading input and writing
output data, the BIM supports PROFIBUS Extended Diagnostics for status information.
The BIM(s) must be used with an 8701-CA-BI Redundant BIM Carrier, described on page 4.
Redundant BIMs can be used for critical applications. Each BIM in the redundant pair operates in parallel,
continually checking status to enable the backup BIM to monitor the health of the primary BIM.
8507-BI-DP Bus Interface Module
For details on the installation and operation of the BIM, refer to the PAC8000 I/O - PROFIBUS DP BIM
Instruction Manual, INM8507.
Features
support for up to 24 I/O modules
redundant operation
extended diagnostics for module and channel status
PROFIBUS network speeds of up to 12 Mbaud
non-volatile memory for configuration
configurable via PROFIBUS host
HART Pass-through support to monitor/configure HART devices
Configuration/Reset of IP address
Parameterization
The 8507-BI-DP supports parameterization from the PROFIBUS master. The configuration is created in a
PROFIBUS configurator using details provided in a GSD file. This method is fast and enables a
configuration to be built based upon “logical” modules which represent the physical modules. Modules are
added one at a time to the configuration.
The configuration is passed from the PROFIBUS master to the BIM at the start of communication. If the
system is stopped and re-started, or if the node goes through a cold start cycle, the configuration file is re
transmitted to the BIM.
Standard and Extended Diagnostics
The PROFIBUS BIM supports Standard and Extended Diagnostics. While the Standard Diagnostics provide
standard PROFIBUS status information, the Extended Diagnostics provide detailed information relating to
the status of the BIM, the health of the modules and the status of I/O channels. Depending on the I/O
module type, events such as high and low alarm, open circuit and line fault are detected.
Extended Diagnostic messages are generated on detection of any anomalies in I/O modules. Use of the
diagnostic capability requires suitable support in the host application. For hosts unable to use diagnostic
data in the control algorithm, it is possible to map the diagnostic data into the input dataframe.
8701-CA-BI Redundant BIM Carrier For details on the installation and operation of the BIM Carrier, refer to the PAC8000 I/O - PROFIBUS DP BIM Instruction Manual, INM8507. Features
accommodates two Bus Interface Modules
supports PROFIBUS-DP
provides dual PROFIBUS network connections
can be used with DIN rail or panel mounting