Компания TRICONEX AO3481 представляет собой передовой автоматизированный продукт, предназначенный для революции работы в электроэнергетической, нефтехимической и автоматизированной отраслях в целом. Эта модель обладает ключевыми техническими характеристиками, которые отличают ее от других моделей серии TRICONEX как важный инструмент для оптимизации процессов и повышения эффективности.
TRICONEX AO3481 Analog Output Module is a key component in TRICON system, which is used to drive analog signal output. The following are the details about this module:
Functions and features:
The AO module receives the output signal from the main processor module, and selects a healthy channel to drive eight 4-20 mA output signals through the voting mechanism.
Each channel has an internal voltage reference for self-calibration and monitoring module health.
The module supports over-range protection (+6%) and activates the LOAD indicator (load) when an open circuit or over-range is detected.
The module has redundant power supply design, provides independent fuses and power indicator lights (PWR1 and PWR2), and needs external loop power supply.
Technical specifications:
Output type: 4-20 mA with +6% overrange range.
Output points: 8.
Output current range: 4-20 mA.
Output accuracy: ±0.5% FSR.
Maximum load voltage: +42 VDC
External loop power requirements: +24 VDC to +42 VDC.
Diagnostic indicators: PASS, FAULT, ACTIVE, LOAD, PWR1, PWR2.
Working principle:
AO module receives signals from three main processor modules, and selects a healthy channel for signal output through voting mechanism.
Each channel has a current loop feedback mechanism to ensure the accuracy and independence of the signal, and it can work normally even when the load is missing or the channel is selected.
If the module cannot drive one or more outputs, the LOAD indicator light (load) will be activated.
Diagnosis and troubleshooting:
The module supports continuous on-line diagnosis, and the FAULT of any channel will trigger the fault indicator and chassis alarm light.
The fault indicator only reports channel faults, not module faults. The module can continue to run under the condition that at most two channels fail.
Installation and maintenance:
AO module needs external terminal panel (ETP) and TRICON backplane connection with cable interface.
The module is installed in TRICON chassis by mechanical bonding.
TRICONEX AO3481 analog output module is a high-performance industrial-grade equipment, which is suitable for industrial automation scenes requiring high reliability and redundancy. Its design ensures the accuracy of the signal and the stability of the system, and provides rich diagnostic functions and redundant power supply design to improve the reliability of the system.