Beckhoff BX5100-0000 CANopen Bus Terminal Controller
Beckhoff BX5100-0000 CANopen Bus Terminal Controller
BX5100 | CANopen Bus Terminal Controller
The BX5100 Bus Terminal Controller has a CANopen slave interface.
It has automatic baud rate detection up to 1 Mbaud and an address selection switch for address assignment.
Up to 16 Tx PDOs and 16 Rx PDOs can be exchanged with the control.
One unit consists of the BX5100 Bus Terminal Controller with up to 64 Bus Terminals and a bus end terminal.
the terminal bus extension system, the connection of up to 255 Bus Terminals is possible.
The controller is programmed via the COM1 or via the CANopen interface of the FC510x PC Fieldbus Card.
In terms of their equipment and performance, the BX series Bus Terminal Controllers are positioned between the BC series Bus Terminal Controllers and the CX series Embedded PCs.
The main features distinguishing BC and BX are the larger memory and the expanded interfaces of the BX. Additionally, two serial interfaces are integrated for programming and for the connection of further serial devices.
The device itself comprises an illuminated LC display with two lines of 16 characters each, a joystick switch and a real-time clock.
Further peripheral devices, e.g. displays, can be connected via the integrated Beckhoff Smart System Bus (SSB).
The BX family is particularly suitable for a modular machine concept. Within a network, the Bus Terminal Controller can exchange data with other system parts via the fieldbus interfaces.
The real-time clock enables decentralized applications, for which the day of the week or the time play an important role.
The areas of application of this series are similar to that of the BC series, but due to the larger memory the BX can execute significantly more complex and larger programs and can manage more data locally (e.g. history and trend data recording), which are then successively fetched over the fieldbus.
Controller for distributed signal processing
Like for all other Beckhoff controllers, the TwinCAT automation software is the basis for parameterization and programming.
The BX devices are programmed according to the powerful IEC 61131-3 standard in the programming languages IL, FBD, LD, SFC or ST. Users therefore have the familiar TwinCAT tools available, e.g.
the PLC programming interface, the System Manager and TwinCAT Scope.
Data is exchanged optionally via the serial port (COM1) or via the fieldbus through Beckhoff FC510x PC Fieldbus Cards.
The configuration is also carried out using TwinCAT. The fieldbus interface, the SSB bus and the real-time clock can be configured and parameterized via the System Manager.
The System Manager can read all connected devices and Bus Terminals. After the parameterization, the configuration is saved on the BX via the serial interface and can be accessed again later.
PLC data CANopen | BX5100
Programming TwinCAT (via programming interface or fieldbus)
Program memory 256 kbytes
Data memory 256 kbytes
Remanent data 2 kbytes
Persistent data 1 kbyte
Runtime system 1 PLC task
PLC cycle time approx. 1 ms for 1.000 instructions (without I/O cycle, K-bus)
Programming languages IEC 61131-3 (IL, LD, FBD, SFC, ST)
Online change yes
Up/down load code yes/yes
PLC data
Technical data
Housing data

Technical data BX5100
Number of Bus Terminals 64 (255 with K-bus extension)
Max. number of bytes fieldbus 32 Tx/Rx PDOs
Max. number of bytes process image 2048 byte input and 2048 byte output
Digital peripheral signals 2.040 inputs/outputs
Analog peripheral signals 512 inputs/outputs
Data transfer rates automatic detection up to 1 Mbaud
Bus interface open style connector, 5-pin
Interfaces COM1: 1 x RS232. COM2: 1 x RS232 or RS485
SSB CANopen-based subsidiary bus system for the connection of further peripheral devices
Diagnostics LED 2 x power supply, 2 x K-bus
Display FSTN display with 2 x 16 characters for diagnosis or own texts, illuminated
Switch joystick switch for parameterisation and diagnosis
Clock battery-powered real-time clock for time and date
Power supply 24 V DC (-15%/+20%)
Input current 140 mA + (total K-bus current)/4. 500 mA max.
Starting current 2.5 x continuous current
Current supply K-bus 1450 mA
Power contacts max. 24 V DC/max. 10 A
Electrical isolation 500 V (power contact/supply voltage)
Weight approx. 250 g
Operating temperature -25…+60°C
Storage temperature -40…+85°C
Relative humidity 95%, no condensation
Vibration/shock resistance conforms to EN 60068-2-6/EN 60068-2-27
EMC immunity/emission conforms to EN 61000-6-2/EN 61000-6-4
Protect. rating/installation pos. IP20/variable
Approvals/markings CE, UL
PLC data
Technical data
Housing data BXxxxx
Design form compact terminal housing with signal LEDs
Material polycarbonate
Installation on 35 mm DIN rail, conforming to EN 60715 with lock
Side by side mounting by means of double slot and key connection
Marking labeling of the BZxxxx series
Wiring solid conductor (s), flexible conductor (st) and ferrule (f): spring actuation by screwdriver
Connection cross-section s*: 0.08…2.5 mm²,
st*: 0.08…2.5 mm²,
f*: 0.14…1.5 mm²
Stripping length 8…9 mm
Current load power contacts Imax: 10 A
Dimensions (W x H x D) 81 mm x 100 mm x 90 mm (BX8000: 61 mm x 100 mm x 90 mm)