WATLOW CIM300 Communication Interface Module (EIA-232/485),Discontinued
Watlow Anafaze CIM300 is a legacy Communication Interface Module (CIM) designed for the modular MLS300 series.
It provides the critical bridge between the system's internal PID processing logic and external industrial monitoring networks.
1. Introduction
The CIM300 is an early-generation communication module that enables the Watlow MLS300 system to communicate with external devices via EIA-232 or EIA-485 serial protocols.
It allows a central computer, PLC, or SCADA system to read process data, change setpoints, and monitor alarms for up to 32 independent loops.
While it has been replaced by more modern CIM versions (like the CIM316) and eventually the EZ-ZONE series, it remains a common component in legacy semiconductor and plastics machinery.
2. Technical Parameter Table
| Feature | Specification |
| Series | MLS300 (Anafaze Legacy) |
| Interface Types | EIA-232 (Point-to-Point) and EIA-485 (Multi-drop) |
| Protocols | Modbus RTU, Anafaze ASCII |
| Baud Rate Range | 2400, 4800, 9600, or 19200 bps |
| Isolation | 500VDC Optical Isolation |
| Power Supply | 5VDC (Powered via system backplane/ribbon) |
| Loop Support | Access to all 16 or 32 loops in the stack |
| Network Distance | Up to 4,000 feet (1,200m) for EIA-485 |
| Mounting | Modular "Stack" or DIN-rail |
3. Product Advantages and Features
Universal Bridge: Converts internal system bus data into industry-standard serial protocols for easy HMI integration.
Dual-Interface Support: Provides flexibility to use RS-232 for local PC tuning or RS-485 for long-distance plant network communication.
Noise Protection: Optical isolation prevents ground loop currents from damaging the sensitive central processor in high-power industrial environments.
Transparent Access: Allows full read/write access to PID parameters, alarm limits, and job configurations remotely.
4. Application Cases
Legacy Semiconductor Tools: Interfacing with host computers in wafer tracks and diffusion furnaces.
Multi-Zone Plastics Extrusion: Sending real-time zone temperatures to a central operator station for quality logging.
Retrofit Projects: Used to add SCADA visibility to older thermal systems without replacing the entire control architecture.
Environmental Chamber Monitoring: Syncing multi-module data to a centralized data logger for regulatory reporting.
5. Other Models in the Same Series
MLS300-CIM: The later standard version of this module.
MLS300-PM: The essential Processor Module (Central CPU).
MLS300-AIM: Analog Input Module (the data source).
MLS300-OIT: Remote Operator Interface Terminal.
CIM316: A configuration-specific variant for 16-loop systems.
| ABB | 1MRK00008-KB |
| ABB | ICSE08B5 FPR3346501R1012 |
| ABB | LWN2660-6 |
| ABB | 3ASC25H216A DATX132 |
| ABB | 3ASC25H204 DAPU100 |
| ABB | 3ASC25H214 DATX130 |
| ABB | 3ASC25H208 DATX100 |
| ABB | 3ASC25H219B DATX133 |
| ABB | CI857K01 3BSE018144R1 |
| ABB | XVC767AE102 3BHB007209R0102 |
| ABB | PFEA113-65 3BSE050092R65 |
| ABB | PCD232A 3BHE022293R0101 |
| ABB | PPD113B03-26-100100 3BHE023584R2625 |
| ABB | REF542PLUS 1VCF752000 |
| ABB | REF542PLUS 1VCR007346 |
| ABB | R474A11XE HAFAABAAABE1BCA1XE |
| ABB | CP405 A0 1SAP500405R0001 |
| ABB | PM866-2 3BSE050201R1 |
| ABB | CAI04 |
6. Installation and Maintenance
Installation
Mechanical Connection: The CIM300 must be plugged into the side of the MLS300 stack. Ensure the ribbon cable pins are not bent during insertion.
Jumper Settings: Internal jumpers (or DIP switches, depending on revision) must be set to define whether the unit uses 2-wire or 4-wire RS-485 communication.
Address Assignment: Set a unique Modbus address (1-247) via the MLS300-PM keypad to ensure the CIM300 responds correctly on the network.
Maintenance
Pin Inspection: Over time, the high-density ribbon cables can become brittle or oxidized. Clean connections with a specialized electronic cleaner if "Comm Timeout" errors occur.
Grounding: Ensure the shield of the communication cable is grounded at only one end (typically the master/PC end) to prevent noise from masking data signals.
Diagnostic LEDs: Watch for the "Active" and "Comm" LEDs; if the "Comm" LED never blinks, check for a baud rate or parity mismatch between the CIM300 and the PLC.
7. Unique Product Description
"The Watlow CIM300 is the 'gateway to the grid' for legacy thermal systems.
It transforms a standalone modular controller into a networked asset, enabling surgical-level PID data to be accessed from across the factory floor.