Current Consumption for Power Supply Units
■ Checking Current Consumption and Power Consumption
After selecting a Power Supply Unit based on considerations such as the power supply voltage, calculate the current and power
requirements for each Rack.
Condition 1: Current Requirements
There are three voltage groups for internal power consumption: 5 V, 26 V, and 24 V.
• Current consumption at 5 V (internal logic power supply)
• Current consumption at 26 V (relay driving power supply)
• Current consumption at 24 V (power supply output terminals) (C200HW-PA204S only)
Condition 2: Power Requirements
For each Rack, the upper limits are determined for the current and power that can be provided to the mounted Units. Design the system
so that the total current consumption for all the mounted Units does not exceed the maximum total power or the maximum current
supplied for the voltage groups shown in the following tables.
●CPU Racks and Expansion Racks
The maximum current and total power supplied for CPU Racks and Expansion Racks according to the Power Supply Unit model are
shown below.
Note1:For CPU Racks, include the CPU Backplane and CPU Unit current and power consumption in the calculations.
2: For Expansion Racks, include the Expansion Backplanes current and power consumption in the calculations.
Power Supply Units
Max. current supplied

(A) 5 V
(B) 26 V
(C) 24 V
(D) Max. total
power supplied
C200HW-PA204C
C200HW-PA204
C200HW-PA204S
C200HW-PA204R
C200HW-PA209R
C200HW-PD024
C200HW-PD025
CS1D-PA207R
CS1D-PD024
Conditions 1 and 2 below must be satisfied.
Condition 1: Maximum Current
(1) Total Unit current consumption at 5 V ≤ (A) value
(2) Total Unit current consumption at 26 V ≤ (B) value
(3) Current consumption for service power supply at 24 V ≤ (C) value (Only when using the service power supply from the
C200HW-PA204S.)
Condition 2: Maximum Power
(1) x 5 V + (2) x 26 V + (3) x 24 V ≤ (D) value
■ Example: Calculating Total Current and Power Consumption
Example: When the Following Units are Mounted to a CS-series CPU Rack Using a CS1W-PA204S Power Supply Uni
Using the CX-Programer to Display Current Consumption and Width
CPU Rack and Expansion Rack current consumption and width can be displayed by selecting Current Consumption and Width from the
Options Menu in the CS1 Table Window. If the capacity of the Power Supply Unit is exceeded, it will be displayed in red characters.
Example:
| IC695CPE305-AEAT GE RX3i Central Processing Unit |
| PXIE-4080 NI PXI Digital Multimeter |
| ADV569-P00 Yokogawa Digital Output Module |
| 1SAP800400R0010 Digital Configurable In./Output module 32DC ABB |
| GESVDU-1D-8946 GE pcb 68000 sbc gespac |
| GESSIO-1E GE pcb 68000 sbc gespac |
| GESADA-1 GE pcb 68000 sbc gespac |
| PM858 3BSE093350R1 Processor Unit ABB |
| 128164-02-204-10-02-05 Bently Nevada 3300 XL NSv Proximity Probe |
| 3500/46-03-00 Bently Nevada Hydro Monitor |
| RLX2-IHNF-E Prosoft Fast Industrial Hotspot |
| VE4014 EMERSON M-series Virtual I/O Module 2 |
| A06B-6162-H003 FANUC Servo amplifier module |
| User name | Member Level | Quantity | Specification | Purchase Date |
|---|
Add: High-tech Software Park, Xiamen City, Fujian Province
Mobile: +86-17750019513(WhatsApp)
Email: yy4291644@gmail.com
Website: https://www.abb-sis.com