Jaquet with input card -E04 FTFU 3024 -E04 377Z-05855
with input card -E04 FTFU 3024 -E04 377Z-05855
Limit values 1 - 4 Motherboard FTFU 3024 with optional relay card FTV 3090
Up to 4 limits for speed or frequency functions
Hysteresis Upper and lower set points are freely programmable for each limit
Relay function Monostable function, individually definable as ‘Normal’ energized in when upper set point
exceeded ‘Inverse’ energized in when speed below lower set point
Relay outputs 1. 2 and 3 on
FTFU 3024 motherboard
1 potential free change over contact
AC Umax 250V, Imax 5A, Pmax 1250VA
DC Umax 30V, Imax 5A, Pmax 150W
Initial breakdown voltage : 1000Vrms 1min. from neighbouring output, electronics and earth,
ie from front panel and card frames
Relay outputs 1 - 4 on
FTV 3090 relay card
1 potential free change over contact
AC Umax 250V, Imax 2A, Pmax 125VA
DC Umax 220V, Imax 2A, Pmax 60W
Initial breakdown voltage : 1000Vrms 1min. from neighbouring output, electronics and earth,
ie from front panel and card frames
Accuracy 0.1% of the set point
Temperature error max +/- 50ppm with reference to the set point
Reaction time of speed
monitor
Reaction time of
comporaters
Where the limit is assigned to one of the three speed monitors on the motherboard, the
minimum measuring time is 1 period of the corresponding set point frequency.
The reaction time of the corresponding relay output is Max 1 period of the input frequency +
9ms.
Where the limit is assigned to one of the 4 comparators on the motherboard, the minimum
measuring time may be set as the Fixed Time. Where the period of the input frequency is
shorter than the Fixed Time the relay output reaction time is -
Max twice Fixed Time + max input freq. period + 12ms
Typically = Fixed Time + 1 input period + 12ms
Where the input period is longer than the Fixed Time the reaction time of the relay output is
Max max input period + 12ms
Analog outputs 1. 2 and 3 Auxiliary module FTW 3013
Each of the 3 analog outputs can be used for speed or frequency functions each having
independent ranges. The outputs are potential free and isolated to 500V, 50Hz, 1 Min. from
each other, the main electronics and earth (neighbouring o/p, front panel and card frame).
Standard configuration 0...20mA or 4...20mA,
programmable for rising or falling characteristic Max load 500 Ohm (10V)
Optional version S3 0...5mA or 1...5mA
programmable for rising or falling characteristic Max load 2000 Ohm (10V)
Option U, voltage output 0...10V or 2...10V
programmable for rising or falling characteristic Max load 7 KOhm (1.4mA)
Max output voltage 30 V
Resolution 12 Bit. 1: 4096
Max linearity error 0.1%
Accuracy 0.2% of the range
Temperature drift typically +/- 150ppm/ºK, max +/- 300ppm/ºK
Reaction time (step change) The minimum measuring time may be entered. Where the input period is shorter than the
Fixed Time, the reaction time is -
Max twice Fixed Time + max input period + 7.5ms
Typically Fixed Time + 1 input period + 7.5ms
Where the input period is longer than than the Fixed Time, the reaction times is
Max input period + 7.5ms
Each of the analog outputs can be allocated a software defined low pass filter, whose time
constant T can be configured in the range 0.0 to 9.9 seconds. The sample rate is T/10.
Binary inputs 1 - 6 Motherboard FTFU 3024
For programmable control functions such as - failure memory reset - max memory reset - initiate lamp test - set direction of rotation - initiate test
2 binary inputs (B1 and B2)
having common reference -
-V of the supply
4 potential free binary inputs
(B3...B6) with common
floating reference voltage
+ 5 V level with pull up resistor
V low = active 0...+1V, Isink = max 1mA
V high + 3.5...+33V or open
Isolation 500V, 50Hz, 1 Min. from electronics and earth
+24V level
V low 0...+5V or open
V high = active +10...+33V Isource = max 4mA
Frequency outputs 1 and 2 Motherboard FTFU 3024
Frequency output 1
having common 0V with
supply
Square wave, amplitude +10V, output impedance 100 Ohm
Output current +/-50mA continuous
+/- 100mA for 10% of operating time
Frequency output 2
potential free
Square wave, amplitude +15Vpp, output impedance 100 Ohm
Output current +/-50mA continuous
+/- 100mA for 10% of operating time
Isolation 500V, 50Hz, 1 Min. from electronics and earth
Frequency generator Motherboard FTFU 3024
Frequency range 0.002Hz / 30KHz. Signal only accessible internally = F4
Data I/O Comms module FTK 3072
Having potential free
floating reference
Serial RS 232 interface via front panel D9 connector
Supply PSU in the rack for all modules excluding supply modules
18...33Vdc
Power consumption Typically Max
Motherboard FTFU 3024/E01 4.5W 5.5W
Converter FTW 3013 2.6W 2.8W
Relay card FTV 3090 4.0W 4.2W
Comms module FTK 3072 2.0W 2.5W
| User name | Member Level | Quantity | Specification | Purchase Date |
|---|
Add: High-tech Software Park, Xiamen City, Fujian Province
Mobile: +86-17750019513(WhatsApp)
Email: yy4291644@gmail.com
Website: https://www.abb-sis.com