1.2.2 After Startup
1. Continue your "no-smoking" rule in the operating area. Smoke and fine dust particles
can damage cartridge disks and drives.
2. Maintain humidity levels (ideally) between 40 and 60% (lower humidity may cause
static-discharge problems).
3. Control humidity fluctuations to a rate-of-change less than 6% per hour.
4. Do not defeat temperature and humidity controls by opening doors and windows (for
example, to enhance operator comfort).
5. Keep traffic in the control-room operating areas to a minimum. Restrict access to
authorized personnel, whose duties require control room entry.
6. Review procedures for extinguishing electrical fires and establish fire-fighting
procedures. Refer to a qualified fire-fighting systems contractor for assistance
Plant personnel frequently use hand-held radios ("walkie-talkies"), or citizens-band
radios mounted in maintenance vehicles, for communications. To avoid RFI problems,
review the following:
| ABB | AI625 |
| BENTLY | 3500/42M |
| BENTLY | 3500/40M |
| BENTLY | 3500/33 |
| GE | IS230TSVCH1A |
| GE | IS220PTCCH1A |
| GE | IS220PPRAS1B |
| Meggitt | MPC4 200-510-074-114 |
| Pioneer Magnetics | PM2722-1 24F33-0-4-R-S |
| ABB | DSPC172H 57310001-MP |
| Metrix | 5485C‑007‑046 |
| ABB | REF615Z HCFZAEADABCZDAA11G |
| Hirschmann | OZDProfi12MG12 943727‑321 |
| ABB | REF630 UBFNABABAAAZANEBXC |
| WOOODWARD | 5417-557 |
| GE | H201CI-1 |
| ABB | 3BHL000389P0104 5SHX2645L0004 |
• If radio communications must take place within an operating area or process
controller area, a base-station transceiver with an external antenna should be
used.
• For other applications, radio transmitters with outputs rated as high as 5 watts
must be kept at least 3 meters (10 ft.) from the Enhanced Micro TDC3000
equipment during operation. Transmitters with outputs higher than 5 watts
must be kept as far as possible from your equipment. Keep equipment doors
closed while operating.
Other sources of RFI include generators, arcing relays, or motor contacts, etc.
8. Follow proper cleaning procedures when cleaning the operator area or the control room:
• Do not use water freely. Mop should be only dampened, not wet or dry.
• Use a lint-free, antistatic-type dust cloth to remove dust.
• Do not sweep around areas containing cartridge disks or drives.
• Use a vacuum cleaner on carpets—preferably one connected to an external
system.
• Do not allow liquids to be placed on the Enhanced Micro TDC3000 keyboards
and equipment. Liquid spills will damage electronic components