

DEIF LSU-112DG Load sharing, paralleling & operation
LSU-112DG
Load sharing, paralleling & operation
DEIF's load sharing units offer load sharing in various ways between generators and interfaces to a governor through an electronic potentiometer (EPQ96-2 or EPN110DN).
DEIF’s load sharing units offer load sharing in various ways between generators and interfaces to a governor through an electronic potentiometer (EPQ96-2 or EPN110DN).
Suitable for control of diesel and gas generators, for instance, they can control the power unit in stand-alone mode (performing frequency control) or parallel with other power units (performing frequency and power control).
The units have built-in power and frequency transducers that enable connection of external equipment. Constant power or isochronous mode is also possible. Speed control is conducted by two relays.
Variants
LSU-112DG
Frequency and power control
LSU-113DG
Frequency and power control
With -P>
LSU-114DG
Frequency and power control
With start/stop
LSU-122DG
Reactive
U and Q control

Application
The LSU-112DG is a control unit for control of the prime
mover in a power unit.
The LSU-112DG can control the power unit - - -
in stand-alone mode, performing frequency control
parallel with grid, performing power control
parallel with other power units, performing frequen
cy and power control
The unit is designed for connection to a mechanical
speed governor, however in conjunction with the DEIF
electronic potentiometer type EPN-110DN or EPQ-96 it
can control electronic speed governors as well.
The LSU-112DG has a built-in frequency transducer. If
a very stable frequency is wanted, an external frequen
cy transducer common for all the LSU-112DGs in the
power plant can be connected. If a number of power
units are to be synchronised to the busbar at the same
time, the frequency may likewise be controlled external
ly.
Function
The LSU-112DG is measuring the voltage and the
current from which the frequency and the power pro
duced by the power unit are measured. The built-in
power transducer is based on an I x cos phi principle.
The following couplings are available: - -
1W(4) – single phase
1W3 – 1-element 3-phase, 3-wire, balanced load
If unbalanced load can be expected, an external power
transducer with an output of 4 to 20 mA can be con
nected to the LSU-112DG. In this case the built-in I x
cos phi transducer is automatically interrupted.
The power and frequency measured by each LSU
112DG are fed to two paralleling lines for comparison
with the frequency (FS) and power (PS) of the other
connected LSU-112DG.
If L1 or L2 is disconnected from the LSU-112DG at the
same time as a power unit in a power plant is discon
nected from the power line (busbar), built-in relays in
the LSU-112DG ensure that the power output and the
frequency output of the associated unit are disconnect
ed from the paralleling lines. Likewise the power and
frequency outputs are disconnected if the auxiliary
voltage to the LSU-112DG is disconnected.
The LSU-112DG is equipped with an unload input.
When activated this input will control the power unit to
zero power, and at the same time the power output of
the LSU-112DG is disconnected from the paralleling
line.
The calibration of the LSU-112DG is done so it matches
its power unit. This means that load sharing between
power units with different size will be performed accord
ing to the actual size of the individual power unit in the
plant. For example a 100 kW PU and a 150 kW PU
running in parallel will share a total load of 125 kW into
50 kW and 75k W. If the 150 kW PU is derated to 100
kW by means of the DERATING potentiometer on the
front of the LSU-112DG, the load in the above example
will then be shared equally between the two power
units.
Regulator output
The unit is provided with two contact outputs for speed
control:
Power and frequency control:
The regulating speed of the servomotors for the prime
mover is controlled by the built-in P controller of the
LSU-112DG according to its setting for:
TN (min. ON time):
The min. duration of the control pulse when inside the
proportional band Xp.
XP (proportional band):
The zone within which the pulse/pause ratio changes
proportionally to the frequency/power deviation from the
required value.
TP (period time):
The time between the beginnings of two subsequent
relay pulses.
Deadband:
The zone within which no control pulses are emitted.
Self-monitoring
The LSU-112DG is equipped with a self-monitoring
function. The function supervises the built-in micro
controller and hereby verifies if the programme is run
ning correctly. The green LED marked “POWER” is
connected to this function. Constant green light indi
cates that the supply voltage is accepted and the unit is
running correctly. Flashing green light 2-3 Hz indicates
that the supply voltage is accepted but the unit is run
ning incorrectly. In this situation the status output termi
nals 17 and 18 are activated (open).
| User name | Member Level | Quantity | Specification | Purchase Date |
|---|
Add: High-tech Software Park, Xiamen City, Fujian Province
Mobile: +86-17750019513(WhatsApp)
Email: yy4291644@gmail.com
Website: https://www.abb-sis.com