SHINKAWA MODEL VM-53 DUAL COMMUNICATION UNIT
MODEL VM-53 DUAL COMMUNICATION UNIT
New model code
Original model code
Husing fix
screw size Battery Tropical
spec. Serial interface Battery Tropical
spec.
0 #4-40UNC 1 RS-232
1 M2.6×0.45 2 RS-485
COMMUNICATION
DATA
Measurement value,set gap voltage, OK state,
ALERT state,
DANGER state, DANGER bypass state,
CH bypass state
PROTOCOLS Modbus® : Based on AEG Modicon PI-MBUS-300
Reference Manual.Uses Remote Terminal
Unit(RTU) transmission mode.
Modbus is a registered trademark of Modicon, Inc.
I/O CONNECTOR D-Sub 9P 4pc. (CN1 to CN4)
Housing fix screw : #4-40UNC or M2.6×0.45
Specified when ordering.
Unless specified otherwise, preset to #4-40UNC.
Recommended connector(Socket side)
Connector Housing
XM2D-0901 XM2S-0913(#4-40UNC)
XM2S-0911(M2.6×0.45 ) [OMRON]
GM(E)-9F GM-9LD55GU(#4-40UNC)
GM-9LD55G(M2.6×0.45 ) [HONDA]
ID SETTING Set range 1 to 10
Specified when ordering.
Unless specified otherwise IN1: 1
IN2: 2
(can be changed with connected computer.)
TERMINAL
SETTING
ON or OFF
Specified when ordering.
Unless specified otherwise IN1: ON
IN2: ON
(can be changed by internal switch.)
SERIAL
INTERFACE
RS-232 or RS-485
Specified when ordering.
Unless specified otherwise, preset to RS-232.
(can be changed by internal switch.)
Phase Marker
OK status
TB(Valid) or FIX(invalid)
Preset to FIX(invalid)
(can be changed by internal swich.)
TEMPERATURE
RANGE
Operating temperature
: 0 to 65°C(32 to 149°F)(without battery)
0 to 50°C(32 to 122°F)(with battery)
Storage temperature
: -30 to +85°C(-22 to +185°F)(without battery)
-20 to +55°C(-4 to +131°F)(with battery)
Relative humidity
: 20 to 95%RH(noncondensing)
BAUD RATE 1200,2400,4800,9600,19200 bps (RS-232)
1200,2400,4800,9600,19200,38400 bps (RS-485)
Preset to 9600 bps.
(can be changed with connected computer.)
DATA LENGTH 7 bit or 8 bit
Preset to 8 bit.
(can be changed with connected computer.)
PARITY ODD(odd number),EVEN(even number),
NONE(none)
Preset to NONE.
(can be changed with connected computer.)
MASS Monitor : max.0.4kg
Others
STOP BIT 1 bit or 2 bit
Preset to 1 bit
(can be changed with connected computer.)
FLOW
CONTROL
None
Note)
1. Model VM-53 Dual Communication Unit can be installed in any slot for the Relay Module at VM-5H3 or VM-5W1
Instrument Rack.
The Monitor Unit should not be installed in the front side of the VM-53.
2. Model VM-5P3 Phase Marker Unit must be selected when Phase Marker is required.
Model VM-53 and Model VM-5P1,2 Communication/Phase Marker Unit should not be installed in the same rack.
3. Buffer output signal from Model VM-5P3 should be connected to IN and COM terminal of Model VM-53 when the
Phase Marker OK state is required as a communication data item.
4. The operating temperature range is limited to 0 to 50°C(32 to 122°F) with the battery.
The time information may be lost when the power is turned off without the battery.
5. Only one VM-53 Unit can be installed in a Rack.
6. It is not able to communicate with VM-5 monitor unit which is not an applicable model for VM-53.
Software version number of an applicable model for VM-53 is “A” and after as follows.
(Software version number is indicated on the internal circuit board.)
Vibration, Thrust, Expansion, Differential expansion monitor : 2194-001-F004A and after
Rotor monitor : 2194-001-F005A and after
Eccentricity monitor : 2194-001-F006A and after
Dual temperature monitor : 2A98-001-F001A and after
Rod drop monitor : 2B99-002-F001A and after
Bottom hold monitor : 2B99-002-F001A and after
7. VZ-65 (Configuration file for VM-53) is needed to set the communication specifications and customize the
communication data address.
8. The daisy chain connections are five racks or less.