SHINKAWA MODEL VM-5B DUAL ACCELERATION MONITOR
vMODEL VM-5B DUAL ACCELERATION MONITOR
onitor range Input signal Low cut-off frequency
*2 High cut-off
frequency
*2 Rectification Recorder output
1 0 to 20m/s2 pk G 0 to 2g pk 1 CA Series 1 10Hz or less 1 100Hz 0 Average value 0 4 to 20mADC
2 0 to 50m/s2 pk H 0 to 5g pk 2 20Hz 2 200Hz 1 pk-pk 1 1 to 5VDC
3 0 to 100m/s2 pk J 0 to 10g pk 3 50Hz 3 500Hz 2 rms
(additional spec./RMS) 2
Output card
/IS or /RE
option
4 0 to 200m/s2 pk K 0 to 20g pk 4 100Hz 4 1kHz
5 0 to 20mm/s pk L 0 to 1in/s pk 5 200Hz 5 2kHz
6 0 to 50mm/s pk M 0 to 2in/s pk 6 500Hz 6 5kHz
7 0 to 100mm/s pk N 0 to 2g rms
*1 7 1kHz 7 10kHz
8 0 to 20m/s2 rms
*1 P 0 to 5g rms
*1 8 9.5Hz Seismic filter
*3 8 20kHz
A 0 to 50m/s2 rms
*1 Q 0 to 10g rms
*1 A 14Hz Seismic filter
*3
B 0 to 100m/s2 rms
*1 R 0 to 20g rms
*1 B 15Hz Seismic filter
*3
C 0 to 200m/s2 rms
*1 S 0 to 1in/s rms
*1 C 40Hz(36dB/oct)
Pipe filter
*3
D 0 to 20mm/s rms
*1 T 0 to 2in/s rms
*1
E 0 to 50mm/s rms
*1 D 60Hz(36dB/oct)
Pipe filter
*3
| ABB | AINT-14C |
| bently | 3500/92-02-01-01 |
| bently | 3500/32-01-01 |
| bently | 3500/33-01-01 |
| bently | 3500/25-01-01-00 |
| bently | 3500/40M-01-01 |
| bently | 3500/22M-01-02-01 |
| Meggitt | CA202 – 144-202-000-203 |
| Meggitt | TQ402 – 111-402-000-012 |
| bently | 3500/92-02-01-01 |
| bently | 3500/32-01-01 |
| bently | 3500/33-01-01 |
| bently | 3500/25-01-01-00 |
| bently | 3500/40M-01-01 |
| bently | 3500/22M-01-02-01 |
| bently | 26530-12-10-02-018-038-22-04-00 |
| bently | 3500/15-05-05-01 106M1079-01 +106M1081-01 |
| ProSoft | MVI46-MNET |
| AMAT | 0190-19092 |
| GE | IS230JPDGH1B |
| ABB | 70EA04b – E HESG492059 |
| Rolls-Royce | H1111.0203 RR :75670 H6036/1.0 GHz |
F 0 to 100mm/s rms
*1
Alarm reset
(DANGER)
Alarm reset
(ALERT)
Alarm reset
(OK)
Relay mode
(DANGER)
Relay mode
(ALERT)
Relay mode
(OK)
Alarm delay
time(DANGER)
Alarm delay
time(ALERT) Alarm output type First
out*4
0 AUTO-RESET 0 AUTO-RESET 0 AUTO-RESET 0 NORMALLY
DE-ENERGIZED 0 NORMALLY
DE-ENERGIZED 0 NORMALLY
DE-ENERGIZED
0 3 sec. 0 3 sec. 1 CH1:2 points(DANGER1,ALERT1)
CH2:2 points(DANGER2,ALERT2)
0 OFF
1 SELF-HOLD 1 SELF-HOLD 1 SELF-HOLD 1 1 sec. 1 1 sec. 1 ON
1 NORMALLY
ENERGIZED 1 NORMALLY
ENERGIZED 1 NORMALLY
ENERGIZED
2 6 sec. 2 6 sec.
2
CH1:4 points(DANGER1,DANGER2,
ALERT1,ALERT2)
CH2:None
3 None. 3 None.
rms. rectification Isolate output Recorder option
output
Input power supply
requirements*5
Tropical
spec.
Sensitivity
correction
When rectification code 2 is
selected, specify this option code.
0 4 to 20mADC 2 0 to -10VDC 0 85 to 264VAC 1 TIIS(IEC)
1 1 to 5VDC 3 0 to 10VDC 1 24VDC 7 NEPSI
2 0 to -10VDC 4 0 to -5VDC 2 110VDC
3 0 to 10VDC 5 0 to 5VDC
4 0 to -5VDC
5 0 to 5VDC
ALARM SET VALUE DANGER1 :
ALERT1 :
DANGER2 :
ALERT2 :
Unless specified otherwise, preset to :
DANGER : 100% of monitor range
ALERT : 90% of monitor range
ALARM INDICATOR DANGER : (red LED)
ALERT : (yellow LED)
ABNOR.ALARM
INDICATOR
OK : (green LED)
BYPASS INDICATOR BYPASS : (red LED)
TRANSUDUCER INPUT CA Series
Number of input points : 2 points
SEQUENCE SET
VALUE
(to increase alarm set
value during operation of
the sequence circuit)
: ×1.0 to 10.0 (×0.1 step)
Preset to ×1.0 unless specified otherwise.
CAUTION : Set the alarm set value so that its designated
multiple is within 110% of the measurement range
during operation of the sequence circuit.
If set to more than 110%, alarm may not be output.
INPUT IMPEDANCE Approx.50k
EXTERNAL CONTACT
INPUT
(FROM REAR PANEL)
Contact type:Dry contact
Contact for external reset
Contact for sequence
BAR GRAPH METER Recorder output conversion accuracy ±2.5% of F.S.
DIGITAL METER Recorder output conversion accuracy ±1.0% of F.S.
SUPPRESSION
FUNCTION SET VALUE
: 0.0 to 10.0 % of monitor range (0.1 % step)
Preset to 2.0 % unless specified otherwise.
CAUTION : When the measurement value is not more than
suppression function set value, indication and
recorder output value shall be as 0 %.
RECORDER OUTPUT
CONVERSION
ACCURACY
±0.5% of F.S. at calibration frequency at 25°C
±2.0% of F.S. at calibration frequency at 0 to 65°C
(the calibration frequency is determined by the cut-off
frequency range.)
RECORDER OUTPUT
(FROM REAR PANEL)
Voltage or current output proportional to monitor range
1 to 5VDC (output impedance : 250)
4 to 20mADC (max.load resistance : 500)
0 to -10VDC*,0 to 10VDC*,0 to -5VDC*,0 to 5VDC*
(output impedance : 100) (*option)
Number of output points : 2 points
Standard Specifications
ALARM SET POINT 4 points(DANGER1,ALERT1,DANGER2,ALERT2)
ALARM SET RANGE 0 to 110% of monitor range
ALARM SET
ACCURACY
±1.0% of F.S. or less
MONITOR OUTPUT
(FROM FRONT, REAR
PANEL)
Input signal is output via a buffer amplifier.
Signal level : 0.8 to 22VDC
Output impedance : 100 (load resistance : 50k or more)
ALARM SET
REPEATABILITY
±0.1% of F.S. or less
ALARM OUTPUT 5 points (DANGER1,ALERT1,DANGER2,ALERT2,OK) or
6 points (DANGER1,ALERT1,DANGER2,ALERT2,OK1,OK2)
TEMPERATIRE RANGE Operating temperature : 0 to 65°C(32 to 149°F)
Storage temperature : -30 to +85°C(-22 to 185°F)
Relative himidity : 20 to 95%RH(noncondensing) MEASURED VALUE LCD digital meter with 5 digits (7 segments, with back light)
LCD bar graph meter (40 segments, with back light)
* Measurement value and alarm set value are indicated on
the digital meter and bar graph meter simultaneously.
MATERIAL AND FINI
| User name | Member Level | Quantity | Specification | Purchase Date |
|---|
Add: High-tech Software Park, Xiamen City, Fujian Province
Mobile: +86-17750019513(WhatsApp)
Email: yy4291644@gmail.com
Website: https://www.abb-sis.com