SHINKAWA MODEL VM-5E DUAL CASE
MODEL VM-5E DUAL CASE
EXPANSION MONITOR
Monitor range Input signal Frequency
response Polarity
*1 Operation method Recorder output Alarm reset
(DANGER)
Alarm reset
(ALERT)
Alarm reset
(OK)
1 0 to 25mm 1 VM-21 or VM-11P-20S2 0 DC to 0.5Hz 1 Direct 1 Differential 0 4 to 20mADC 0 AUTO RESET 0 AUTO RESET 0 AUTO RESET
2 0 to 50mm 2 VM-21 or VM-11P-21S2 2 Reverse 2 Direct 1 1 to 5VDC 1 SELF-HOLD 1 SELF-HOLD 1 SELF-HOLD
3 0 to 100mm 3 VM-21 or VM-11P-22S2 2
Output card
/IS or /RE
option
4 0 to 1inch 4 VM-21 or VM-11P-23S2
5 0 to 2inch 5 VM-21 or VM-11P-24S2
6 0 to 4inch
Relay mode
(DANGER)
Relay mode
(ALERT)
Relay mode
(OK)
Alarm delay time
(DANGER)
Alarm delay time
(ALERT) Alarm output type First output*2
0 NORMARY
DE-ENERGIZED 0 NORMARY
DE-ENERGIZED 0 NORMARY
DE-ENERGIZED
0 3 sec. 0 3 sec. In case of differential operation 0 OFF
1 1 sec. 1 1 sec. 1 CH1 : 2 points (DANGER1,ALERT1)
H,L are OR output
1 ON
1 NORMALLY
ENERGIZED 1 NORMALLY
ENERGIZED 1 NORMALLY
ENERGIZED
2 6 sec. 2 6 sec.
3 None 3 None 2 CH1 : 4 points (H-DANGER,H-ALERT,
L-ALERT,L-DANGER)
In case of direct operation
3
CH1 : 2 points (DANGER1,ALERT1)
H,L are OR output
CH2 : 2 points (DANGER2,ALERT2)
H,L are OR output
4
CH1 : 4 points (H-DANGER,H-ALERT,
L-ALERT,L-DANGER)
CH2 : None
| ABB | DSAO120 5FSE707630-71 |
| Rolls-Royce | 98H010A00001 |
| moog | G771K202 |
| GE | IS420UCSBH4A Rev.I |
| GE | IS420UCSBH1A Rev.H |
| ABB | EL3020 3.345558.2 0241398794/0300 Magnos 206 O2 98-100% |
| ABB | EL3020 3.346806.2 0241398794/1500 Caldos 27 Ar 0-100% |
| ABB | AX410/50001 |
| Foxboro | FBM217 |
| Foxboro | FBM201 P0914SQ |
| Foxboro | FBM237 P0914XS |
| Foxboro | FBM203 RH914SV |
| Foxboro | FBM201TA P0916AA |
| Foxboro | FBM237TA P0916CC |
| Foxboro | FBM203TA PO916AE |
| Foxboro | P0916DE |
| ABB | 3BHE057901R0101 PCD235C101 |
| Triconex | 3704E |
| Triconex | 3504E |
| Triconex | 3504E |
ALARM SET VALUE * H-DANGER1 :
* H-ALERT1 :
* L-ALERT1 :
* L-DANGER1 :
H-DANGER2 :
H-ALERT2 :
L-ALERT2 :
L-DANGER2 :
Only * are set in case of differential operation
Unless specified otherwise, preset to :
H-DANGER : 100% of monitor range
H-ALERT : 90% of monitor range
L-ALERT : 10% of monitor range
L-DANGER : 0% of monitor range
MEASURED VALUE LCD digital meter with 5 digits
(7 segments, with back light)
LCD bar graph meter (40 segments, with back light)
* Measurement value and alarm set value are indicated on
the digital meter and bar graph meter simultaneously.
ALARM INDICATOR DANGER : (red LED)
ALERT : (yellow LED)
ABNOR. ALARM
INDICATOR
OK : (green LED)
BYPASS INDICATOR BYPASS : (red LED)
TRANSDUCER INPUT VM-11P,VM-21P
Number of input points : 2 points
INPUT IMPEDANCE Approx. 250Ω
EXTERNAL CONTACT
INPUT
(FROM REAR PANEL)
Contact type : Dry contact
Contact for external reset
Standard Specifications
ALARM SET POINT 8 points (H-DANGER1,H-ALERT1,L-ALERT1,L-DANGER1,
H-DANGER2,H-ALERT2,L-ALERT2,L-DANGER2)
In case of differential operation,
4 points (H-DANGER,H-ALERT,L-DANGER,L-ALERT)
BAR GRAPH METER Recorder output conversion acuracy ± 2.5% of F.S.
ZERO SHIFT 0 to 100% of monitor range
DIGITAL METER Recorder output conversion acuracy ± 1.0% of F.S.
RECORDER OUTPUT
CONVERSION
ACCURACY
± 0.5% of F.S. at 25°C
± 2.0% of F.S. at 0 to 65°C
ALARM SET RANGE -10 to +110% of monitor range
ALARM SET
ACCURACY
± 1.0% of F.S. or less
RECORDER OUTPUT
(FROM REAR PANEL)
Voltage or current output proportional to monitor range
1 to 5VDC (output impedance : 250Ω)
4 to 20mADC (max. load resistance : 500Ω)
0 to -10VDC*,0 to 10VDC*,0 to -5VDC*,0 to 5VDC*
(output impedance : 100Ω) (*option)
Number of output points : 2 points
When operation method is differential : 1 point
ALARM SET
REPEATABILITY
± 0.1% of F.S. or less
ALARM OUTPUT 5 points (DANGER1,ALERT1,DANGER2,ALERT2,OK) or
6 points (DANGER1,ALERT1,DANGER2,ALERT2,OK1,OK2)
In case of differential operation.
3 points (DANGER,ALERT,OK) or
4 points (DANGER,ALERT,OK1,OK2) (H,L are OR output)
(6 points when 4-point alarm is selected for CH1) MONITOR OUTPUT
(FROM FRONT,REAR
PANEL)
Input signal is output via a buffer amplifier.
Signal level : 1 to 5VDC
Output impedance : 100Ω (load resistance 50k or more) OTHERS
TEMPERATURE
RANGE
Operating temperature : 0 to 65°C (32 to 149°F)
Storage temperature : -30 to +85°C (-22 to +185°F)
Relative humidity : 20 to 95% (noncondensing)
MATERIAL AND
FINISH
Face plate : Aluminum Munsell N-4.0 (equiv.)
MASS Monitor : max.0.7kg
(including single unit instrument rack : max.2.5kg)
| User name | Member Level | Quantity | Specification | Purchase Date |
|---|
Add: High-tech Software Park, Xiamen City, Fujian Province
Mobile: +86-17750019513(WhatsApp)
Email: yy4291644@gmail.com
Website: https://www.abb-sis.com