foxboro Contact/dc Input Interface Module FBM07 The Contact/dc Input Interface Module (an expandable main module) and its counterpart Contact/dc Expansion Input Interface Module individually function as a 16-channel contact sensor or 16-channel dc voltage monitor. Each module performs the signal conversion required to interface these digital (i.e., on/off state) electrical input signals from the field sensors to the redundant Fieldbus. The expandable main module independently connects to the Fieldbus and is capable of supporting a single expansion module. The expansion module connects to the Fieldbus via any expandable main module and is functionally dependent on the supporting main module. When used alone or in conjunction with an expansion module that interfaces field input signals only, the main module executes either the Digital I/O, Sequence of Events Monitor, Pulse Count Inputs or Ladder Logic program. The configurable option for each program is Input Filter Time. • When used in conjunction with an expansion module that interfaces field input and output signals, the main module executes either the Digital I/O or Ladder Logic program. The configurable options for each program are Input Filter Time, Fail Safe Configuration, Fail Safe Fallback and Sustained or Momentary Outputs. If the Momentary Output configuration is selected, then Pulse Output Interval is also configurable Configurable options for inputs are exercised on a per module basis; those for outputs are exercised on a per channel basis. The functional, environmental and physical specifications are applicable to both modules. Common Characteristics INPUT 16 independent channels ISOLATION Input to Earth (Ground) The module will withstand, without damage, a potential of 1250 V ac applied for one minute between any channel and earth (ground). CAUTION This does not imply that these channels are intended for permanent connection to voltages of these levels. Exceeding the limits for input voltages, as stated elsewhere in this specification, will violate electrical safety codes and may expose users to electric shock. Input Pair to Input Pair The module will withstand, without damage, a potential of 1250 V ac applied for one minute between pairs of channels. Channels are paired and share a common return; isolation is between pairs of channels. NOTE This does not imply that these channels are intended for permanent connection to voltages of these levels. Exceeding the limits for input voltages, as stated elsewhere in this specification, will violate electrical safety codes and may expose users to electric shock. Channel Inputs Inputs are isolated in pairs (e.g., channels 1 and 2 are isolated from channels 3 and 4). When inputs are used with hazardous voltages (greater than 60 V dc), both channels of a pair must be used with hazardous voltages. Hazardous and non-hazardous voltages must not be mixed within a channel pair.
The main module is capable of executing any one of the application programs identified in the following schedule: FILTER TIME Configurable (4, 8, 16, or 32 ms) POWER REQUIREMENTS Input Voltage Range (Redundant) 26 to 42 V dc Consumption Main Module Only 7 W (maximum) Main Module Plus Expansion Module 12 W (maximum) HEAT DISSIPATION Main Module Only 12 W (maximum) Main Module Plus Expansion Module 22 W (maximum) INDICATORS (MOUNTED ON TERMINATION ASSEMBLY) Operational Status 2 light-emitting diodes (LED’s) (1 red and 1 green) Input Channel Status 16 LED’s (1 per channel) FIELD TERMINATION CONNECTIONS(a) Discrete Wire Blocks 32 screw-clamp terminals (2 blocks using 16 terminals per block) Plug Connector Block 34-pin connector. Mates with: – Burndy MSD 34 PM 118 (plug with bar-type cable clamp) – Burndy MSD 34 PM 124 (plug with clam shell hood) – Burndy MSD 34 PM 824 (plug with suitcase hood) – or equivalent Direct Connection Block 32 screw-clamp terminals COMMUNICATION Via the redundant Fieldbus (main module only) Please contact us (kongjiang automation technology), consultation purchase! FOXBORO B0134SV AMPLIFIER FOXBORO B0134ZR CONTROLLER PCLC1 FOXBORO B0134ZX CONTROLLER PCL 2 FOXBORO B0136CG FRONT PANEL FOXBORO B0137NQ BEZEL FOR INSTRUMENT FOXBORO B0137NR BEZEL FOR INSTRUMENT GRAY FOXBORO B0138RA TERMINAL BLOCK W/ADJUSTMENTS 821AL 823 827 FOXBORO B0139RB GASKET FOXBORO B0142CB PWA PANEL INTERFACE FOXBORO B0142CC PWA DT BUFFER FOXBORO B0142CE PWA R/W MEMORY FOXBORO B0142CH CONTROL PANEL FOXBORO B0142DQ PWA I/O POWER CONVERTER FOXBORO B0142DR PC BOARD UCM POWER CONVERTER FOXBORO B0152MC MANIFOLD FOR INSTRUMENT 3VALVE BYPASS CARBON STEEL FOXBORO B0152ME MANIFOLD FOR INSTRUMENT 3VALVE BYPASS 316SST FOXBORO B0158LY ELECTRODE ASSEMBLY NON-FLOW REFERENCE FOXBORO B0158MC ELECTRODE ASSEMBLY - TEMPERATURE COMPENSATOR FOXBORO B0159CA TRANSFORMER FOXBORO B0183AC PCB ASSEMBLY FOXBORO B0184YV PWA FOR JUNCTION BOX / 24VDC FOXBORO B0194RF MODULE KIT FOXBORO B0300BT INDICATOR FOXBORO BK3474 MANUAL FOXBORO BK3493 MANUAL FOXBORO BO197BB REGULATOR FOXBORO BS450XX METER FOXBORO BS806DD BEZEL FOXBORO BS806DQ KEYPAD FOXBORO BS806DU OVERLAY FOXBORO C0125KZ PLUG FOXBORO C0128CB NOZZLE ASSEMBLY