RUN Autoadjust is running.
CALC_ERR Error during plausibility check.
COMPLETE Autoadjust completed successfully.
BREAK Autoadjust has been stopped by the operator. This can be done locally by pressing ENTER.
OUTOFRNG Sensor range of the positioner has been exceeded; Autoadjust was stopped.
NO_SCALE End positions have not yet been determined; therefore, partial Autoadjust cannot be run.
RNG_ERR Less than 10% of the sensor range is used.
TIMEOUT Timeout. The control parameters could not be determined within 200 seconds. Autoadjust was stopped.
SPR_ERR The actual spring action does not match the configured direction.