KONG -Y
NameDescriptionContent
Location:

GE SR760-CASE 750/760Feeder Management Relay® Instruction Manual

From: | Author:kongjiang | Time :2025-04-28 | 1892 Browse: | 🔊 Click to read aloud ❚❚ | Share:

DESCRIPTION 

 The 750 and 760 relays contain many features designed to accommodate a wide range of applications. This chapter is pro vided to guide you, the first time user, through a real-world application. The following step-by-step installation example, pro vides you with a quick and convenient way of becoming familiar with the relay. To start, simply power on the unit, and follow the instructions in this tutorial. The example assumes the following system characteristics. It also assumes that relay set points are unaltered from their factory default values.

• Power System Data System: 3Φ, 4 wire Frequency: 60 Hz Line Voltage: 13.8 kV Maximum Current: 600 A

• Control System Requirements All protection elements used are to trip the breaker. Breaker position monitoring via 52b contact only. Only current metering is required. Contact Inputs: Remote open and close contacts from RTU. Remote/local selection from panel hand switch. Reset from RTU. Alarm after 100 second delay from substation monitor Contact Outputs: Trip and close to breaker control circuit (trip and close relays). Relay failure alarm to RTU (self-test warning relay, no programming required). Alarm contact to RTU (setup in User Function for “Substation Monitor”) No data communications to other equipment.

• Instrument Transformer Data Bus VTs: 3 × Wye connected, ratio = 14.4 kV:120 V Phase CTs: 3 × Wye connected, ratio = 600:5 A

• Phase Protection Settings Time Overcurrent 1: Curve Shape = Moderately Inverse; Pickup = 840 A; Multiplier = 20.2 Instantaneous Overcurrent 1: Pickup = 840 A; Phases Required = Any Two; Delay = 0 seconds Instantaneous Overcurrent 2: Pickup = 10100 A; Phases Required = Any Two; Delay = 0 seconds

• Neutral Protection Settings Time Overcurrent 1: curve shape = Moderately Inverse; pickup = 120 A; multiplier = 10 Instantaneous Overcurrent 1: Pickup = 120 A; Delay = 0 seconds Instantaneous Overcurrent 2: Pickup = 2000 A; Delay = 0 seconds You should now be familiar with maneuvering through and editing setpoint messages. As such, we will now limit our discus sion to just the values that must be programmed, in order to meet the requirements of the example application. Any set points not explicitly mentioned should be left at the factory default value。


A) S2 SYSTEM SETPOINTS The S2 setpoints page contains setpoints for entering the characteristics of the equipment on the feeder electrical system. In our example, these characteristics are specified under POWER SYSTEM DATA and INSTRUMENT TRANSFORMER DATA. From this information and the resulting calculations, program S2 setpoints as indicated.

B) For current transformers, make the following change in the S2 SYSTEM SETUP PHASE CT PRIMARY: "600 A" For voltage transformers, make the following changes in the S2 SYSTEM SETUP CURRENT SENSING setpoints page: BUS VT SENSING setpoints page: VT CONNECTION TYPE: "Wye" NOMINAL VT SECONDARY VOLTAGE: "66.4 V" (13.8kV ø-ø ≡ 7.97kV ø-N; 7.97kV / 120 = 66.4 V) VT RATIO: "120:1" (14.4 kV VTpri / 120V VTsec) Make the following change in the S2 SYSTEM SETUP POWER SYSTEM setpoints page to reflect the power system: NOMINAL FREQ: “60 Hz

c) 3 LOGIC INPUTS SETPOINTS The S3 setpoints page is for entering the characteristics of the logic inputs. In our example, these characteristics are spec ified under the Control System Requirements heading. Program S3 setpoints as indicated. For breaker position monitoring, enter the following values in the S3 LOGIC INPUTS INPUT 2 NAME: "Brkr Position (52b)" INPUT 2 ASSERTED LOGIC: "Contact Close" then enter the following value in the S3 LOGIC INPUTS LOGIC INPUTS SETUP setpoints page: BRKR FUNCTIONS setpoint page: 52B CONTACT: "Input 2" For the Remote Open/Close and Reset RTU contacts, enter the following values in the S3 LOGIC INPUTS SETUP setpoints page: INPUT 3 NAME: "Local Mode" INPUT 3 ASSERTED LOGIC: "Contact Close" INPUT 4 NAME: "Remote Open" INPUT 4 ASSERTED LOGIC: "Contact Close" INPUT 5 NAME: "Remote Close" INPUT 5 ASSERTED LOGIC: "Contact Close" INPUT 6 NAME: "Reset" INPUT 6 ASSERTED LOGIC: "Contact Close" then enter the following values in the S3 LOGIC INPUTS LOCAL MODE: "Input 3" RESET: "Input 6" REMOTE OPEN: "Input 4" REMOTE CLOSE: "Input 5" CONTROL FUNCTIONS setpoint page: To setup an Alarm-after-Delay Input. make the following changes to the S3 LOGIC INPUTS 750/760 Feeder Management Relay LOGIC INPUTS USER INPUT A setpoints page

USER INPUT A NAME: "

Substation Monitor" USER INPUT A SOURCE: 

"Input 1" USER INPUT A FUNCTION: 

"Alarm" USER INPUT A RELAYS (3-7): "3----" USER INPUT A DELAY: 

"100.00 s"

d) S5 PROTECTION SETPOINTS The S5 Protection setpoints page contains setpoints for entering protection element characteristics. In our example, these characteristics are specified under PHASE CURRENT and NEUTRAL CURRENT. From this data and the resulting calculations, program the S5 setpoints as indicated.

  • ADLINK 3U Enclosures & Systems AD-3100
  • Power Supplies cPS-H300S/AC ADLINK
  • CPCI Serial Peripheral cPCI-A3H10 ADLINK
  • ADLINK CPCI Serial Peripheral cPCI-A3XMC
  • CPCI Serial Peripheral cPCI-A3H20 ADLINK
  • CPCI Serial Peripheral cPCI-A3MXM ADLINK
  • ADLINK CPCI Serial Peripheral cPCI-A3COM
  • ADLINK CPCI Serial Peripheral cPCI-A3USB
  • ADLINK CPCI Serial Peripheral cPCI-A3ETH
  • CPCI Serial Peripheral cPCI-A3CAN ADLINK
  • 3U CompactPCI Serial Blades cPCI-A3525 Series
  • 3U CompactPCI Serial Blades cPCI-A3535 Series ADLINK
  • CompactPCI Backplanes cBP-6402 ADLINK
  • ADLINK CompactPCI Backplanes cBP-6402R
  • ADLINK CompactPCI Backplanes cBP-6105R
  • CompactPCI Backplanes cBP-6405R ADLINK
  • CompactPCI Backplanes cBP-6108F ADLINK
  • CompactPCI Backplanes cBP-6108R ADLINK
  • CompactPCI Backplanes cBP-6014R ADLINK
  • ADLINK 6U Enclosures & Systems cPCIS-6130R
  • ADLINK 6U Enclosures & Systems cPCIS-6230R/ 6240R Series
  • ADLINK 6U Enclosures & Systems cPCIS-6235R
  • ADLINK 6U Enclosures & Systems cPCIS-6400X Series
  • ADLINK 6U Enclosures & Systems cPCIS-6400U Series
  • ADLINK 6U Enclosures & Systems cPCIS-6418U
  • ADLINK 6U Enclosures & Systems cPCIS-3300BLS
  • ADLINK 6U Enclosures & Systems cPCIS-3320/AC
  • ADLINK Power Supplies cPS-H640/AC
  • ADLINK Power Supplies cPS-H640/48
  • ADLINK 6U Rear Transition Modules cPCI-R6100 Series
  • ADLINK 6U Rear Transition Modules cPCI-R6002 Series
  • ADLINK 6U Rear Transition Modules cPCI-R6600 Series
  • ADLINK 6U CompactPCI 2.0 Blades cPCI-6660
  • ADLINK 6U CompactPCI 2.0 Blades cPCI-6636(KL) Series
  • ADLINK 6U CompactPCI 2.0 Blades cPCI-6640 Series
  • ADLINK 6U CompactPCI 2.0 Blades cPCI-6540 Series
  • ADLINK CompactPCI Backplanes cBP-3064
  • ADLINK CompactPCI Backplanes cBP-3213PR
  • ADLINK 3U Enclosures & Systems cPCIS-2500 Series
  • ADLINK 3U Enclosures & Systems cPCIS-2630 Series
  • ADLINK 3U Enclosures & Systems cPCIS-2632 Series
  • ADLINK 3U Enclosures & Systems cPCIS-2642 Series
  • ADLINK U Enclosures & Systems cPCIS-2633 Series
  • ADLINK U Enclosures & Systems cPCIS-ET1100 Series
  • ADLINK Power Supplies cPS-H325/AC
  • ADLINK Power Supplies cPS-H325/48
  • ADLINK Power Supplies cPS-H325/110
  • ADLINK Power Supplies cPS-H325/24
  • ADLINK PCI-7841/cPCI-7841 Dual-port Isolated CAN Interface Cards
  • ADLINK Peripherals & Accessories cPCI-3548
  • ADLINK Peripherals & Accessories cPCI-8301
  • ADLINK Peripherals & Accessories cPCI-3W10
  • ADLINK Analog Output cPCI-6208/6216 Series
  • ADLINK Multi-Function DAQ cPCI-9116
  • ADLINK 3U CompactPCI Blades CT-3620
  • ADLINK 3U CompactPCI Blades cPCI-3620
  • ADLINK 3U CompactPCI Blades cPCI-3620
  • ADLINK 3U CompactPCI Blades cPCI-3630
  • ADLINK 3U CompactPCI Blades cPCI-3640 Series
  • 3U CompactPCI Blades cPCI-3520 Series
  • ADLINK IMB-M42H ATX Motherboards
  • Adlink PCIe-GIE74 /PCIe-GIE74V Frame Grabbers / Video Capture Cards
  • ADLINK USB-1605 Removable screw terminal blocks or high-density D-Sub
  • Adlink ETX-NR667-L7400/LXE ETX Module
  • ADLINK NuPRO-842LV/P industrial control motherboard
  • ADLINK cPCI-8994 Serial Communication
  • ADLINK / PCI-7432 Digital I/O
  • ADLINK IEC-915GV Compact industrial-grade fanless embedded system
  • ADLINK ADLINK, PLX / PCI-7296 Digital I/O
  • ADLINK HPCI-14S12U 0040 Backplane Selection Guide
  • ADLINK MXE-5500 /MXE-5501/M16G (G) Fanless Embedded Computer
  • Adlink Multi-Function DAQ PCI-9112
  • ADLINK NuPRO-852LV Control Board
  • ADLINK CompactPCI cPCI-7432R Digital I/O Module
  • ADLINK NUPRO-E320LV PICMG Single Board Computers
  • ADLINK PICMG Single Board Computers NuPRO-E72
  • ADLINK PICMG Single Board Computers NuPRO-865
  • Vibro-Meter Rack VM600SYSMK2-ABE04x 6U 19-inch rack Mk2 system
  • Vibro-Meter Relay expansion RLC16 Mk2 SIL2 (single card) 600-044L
  • Vibro-Meter Relay expansion RLC16 Mk2 SIL2 600-04
  • Vibro-Meter Relay expansion RLC16 Mk2 600-045L
  • Vibro-Meter Relay expansion RLC16 Mk2 600-045
  • Vibro-Meter I/O interface card  IOCN Mk2    600-051
  • Vibro-Meter CPU controller   CPUM Mk2  600-050
  • Vibro-Meter I/O interface card    IOC10 Mk2 (rear card)    600-046
  • Vibro-Meter Temperature / Analog Acquisition  AMC10 Mk2  600-042
  • Vibro-Meter I/O interface card IOC4 Mk2 600-043
  • Vibro-Meter Protective measuring card MPC4 Mk2 SIL2 601-041-A10
  • Vibro-Meter Protective measuring card MPC4 Mk2 601-041-A0
  • Vibro-Meter PSU-VM600 VM600 Rack Power Module
  • Vibro-Meter ABE056 - 1U ultra-thin single-rack
  • Vibro-Meter ABE046 - 6U 19-inch rack
  • Vibro-Meter ABE045 - 6U 19-inch rack
  • Vibro-Meter ABE044 - 6U 19-inch rack (with expansion slots)
  • Vibro-Meter ABE042 6U 19-inch rack (4 slots)
  • Vibro-Meter I/O interface card XIO16T
  • Vibro-Meter XMC16 16-channel combustion monitoring card
  • Vibro-Meter XMV16 - 16-channel vibration condition monitoring card
  • Vibro-Meter RLC16 Relay Card
  • Vibro-Meter IRC4 Intelligent Relay Card
  • Vibro-Meter IOCR2 input/output rear interface card
  • Vibro-Meter CPUR2 Central Processing and Controller Card
  • Vibro-Meter I/O interface card  -  IOCR
  • VIBRO-METER CPU controller CPUR
  • VIBRO-METER IOCN 200-585-000-322 I/O interface card
  • VIBRO-METER IOCN 200-585-000-321 I/O Interface Card
  • VIBRO-METER 200-595-074-323 VM600 system CPU management card, non-redundant
  • VIBRO-METER CPUM 200-595-074-322 CPU Controller
  • VIBRO-METER CPU controller CPUM 200-595-070-321
  • Vibro-Meter IOC8T VM600 Mk1 I/O Interface Card
  • Vibro-Meter AMC8 Analog Monitoring Card
  • VIBRO-METER IOC4G2 I/O interface card
  • VIBRO-METER MPC4G2 Protective measuring card
  • VIBRO-METER IOC4T 200-560-101-017 VM600 Mk1 Isolated I/O Interface Card, equipped with MPC4
  • VIBRO-METER IOC4T 200-560-101-015 VM600 Mk1 interface card
  • VIBRO-METER IOC4T 200-560-000-114 I/O interface card
  • VIBRO-METER IOC4T 200-560-000-113 I/O interface card
  • VIBRO-METER IOC4T 200-560-000-111 Sensor wiring
  • VIBRO-METER MPC4 200-510-072-212 Protection Measurement Card
  • VIBRO-METER MPC4 200-510-071-114 Protective Measurement Card
  • VIBRO-METER 200-510-071-111 4-channel vibration protection + 2-speed channels
  • VIBRO-METER 200-510-070-111 4-channel vibration protection + 2-speed channels
  • ADLINK PICMG Single Board Computers NuPRO-E315
  • ADLINK High Speed Link (HSL) PCI-7853
  • ADLINK Digital I/O PCIe-7432
  • ADLINK Mini-ITX Embedded Boards AmITX-AL-I
  • ADLINK 6U CompactPCI 2.0 Blades cPCI-6860A
  • ADLINK NuPRO-900A PICMG Single Board Computers