KONG -Y
NameDescriptionContent
Location:

ABB PCS6000 PRODUCT FAMLIY

From: | Author:kongjiang | Time :2025-07-24 | 259 Browse: | Share:

Introduction, terms, trademarks and related documents

Equipment covered by this manual

This manual covers a standard converter and provides generic information on the converter. The manual does not claim to cover all variations and details of the converter, nor to consider all eventualities that may arise during installation, commissioning, operation and maintenance of the converter. If the converter is adapted to specific customer needs or applications, and handling, installation and operation of the converter are affected by these modifications, information on these modifications is provided in the appropriate documentation (eg, layout drawings, wiring diagrams, technical data, engineering notes). If information is required beyond the instructions in this manual, refer the matter to ABB.

Overview

This manual covers the standard PCS6000 equipment and provides generic information. The manual does not claim to cover all variations and details of the equipment, nor to consider all eventualities that may arise during installation, commissioning, operation and maintenance of the equipment. If the equipment is adapted to specific customer needs or applications, and if handling, installation, and operation of the equipment are affected by these modifications, specific information is provided in the appropriate documentation (eg, layout drawings, wiring diagrams, technical data, and engineering notes) in the appendices. Each person responsible for the transportation, installation, operation, commissioning, preventive maintenance or troubleshooting must have read and fully understood the corresponding chapters in this PCS6000 user's manual and in particular chapter 2, Important safety information, page 19. These responsible persons must ensure that all involved personnel follows the relevant instructions from this manual.

Important safety information

Safety standards

The following industry standards are observed:

– ANSIZ535.6

– ISO3864-2

– ISO7010

– EN50110

Safety messages

The following safety messages are provided to help prevent personal injury and damage to the equipment. The indicated hazard level is based on the ANSI Z535.6 standard. This is the safety alert symbol. It is used to alert you to potential physical injury hazards. Obey all safety messages that follow this symbol to avoid possible injury or death.

Product safety labels

Safety labels are affixed to the converter components to alert personnel of potential hazards when working on the equipment. For more information, see the label placement document for the converter. The instructions on the safety labels must always be followed and the labels must be kept in a perfectly legible condition.

Figure 2–1 Product warning label examples (label placement depends on the converter)

Additional safety labels, including the following, might also be provided:

General safety instructions

1) Minimize hazards 2) Before energizing the converter: 

 • Remove all foreign objects from the converter 

 • Fasten all internal and external covers securely 

 • Close, lock, and/or bolt all doors 

 • Move the release dial of the door safety switches into the locked position 3) Before working on the converter: 

 • Turn off, lock out, and tag out the main and auxiliary power supplies to the converter 

 • De-energize the converter 

 • Ensure that the safety ground connections are in place 

 • Ensure that the appropriate personal protective equipment (PPE) is available and used when required 

 • Inform the involved personnel about the potential safety hazards 4) While working on the converter: 

 • Wear hearing protection when a converter is running. 

 • Do not step on the roof. 

 • Do not install foreign objects on the roof. 5) Before working on a water cooling unit (WCU): In addition to the safety instructions for working on a converter, always read the WCU safety data sheet for relevant safety information, eg, the type of ion exchange resin and glycol. 6) Before working simultaneously on the converter and on other converter system equipment: 

 • Observe the relevant safety codes and standards 

 • Turn off all energy sources for the equipment 

 • Ensure that all lockout and tagout devices are in place 

 • Install barriers around and use appropriate covers on the equipment that is still energized 

 • Inform the involved personnel about the potential safety hazards 7) In case of fire in the converter room: 

 • Observe the established rules and regulations for fire safety 

 • Only allow firefighters with the appropriate PPE to enter the converter room

The 7 steps that save lives

ABB’s 7 steps that save lives concept is a series of actions that must take place prior to commencing work on or near electrical installations. PRODUCT PCS6000 1) Prepare for the work: do an on-site risk assessment or job hazard analysis that considers the limits of approach for shock and arc-flash. 

 • Be in possession of a clear work order to execute the work. 

 • When required, the access or work permit is to be obtained by a person who is authorized for the specific electrical system. 

 • Engage the person responsible for electrical equipment or system to review single-line diagrams, schematics, switching plans, etc. 

 • Ensure the competence of workers. 

 • Check for proper tools for the job. 

 • Determine and select the proper arc-rated Personal Protective Equipment (PPE). 

 • Decide of the appropriate work methods and initiate the Permit To Work (PTW) process. 2) Clearly identify the work location and equipment. 

 • Use your senses (sight, hearing and smell) to identify problem areas. 

 • Define the work area via barriers and barricading and label equipment. 

 • Avoid distractions such as talking or texting on the phone. 3) Disconnect all sources of supply and secure against reconnection by applying Lockout/Tagout. 

 • If ABB is responsible for switching and it cannot be done remotely, then the person performing the switching must be properly trained and wearing the proper PPE identified in step 1. 

 • The Person in Charge of Work (PICW) must ensure that switching is performed in the proper manner by witnessing it from a safe distance if present on site or by engaging the person responsible for switching to identify all isolation points. 

 • Apply Lockout/Tagout (LOTO) to the energy isolation device and if multiple energy isolation devices are involved, then Group LOTO must be implemented with the PICW serving as the Group LOTO Leader.

4) Verify the absence of operating voltage: always test before you touch! Only use properly rated and inspected voltage detection devices and wear proper PPE identified in step 1: 

 • Test voltage detection device 

 • Test for voltage 

 • Test voltage detection device It is highly important that the voltage detection device is tested on a known voltage source such as a Proving Unit or by performing an internal self-test, according to the manufacturer’s instructions, before and after testing for the absence of operating voltage. 5) Carry out earthing and short-circuiting. 

 • Close and lock the earthing switch if the electrical equipment is designed for this purpose or apply portable equipment for earthing and short circuiting. If this is carried out by the customer, then the PICW must ensure that this equipment is properly earthed as a part of the integration/verification and during step 7 when the PICW walks the PTW. 6) Protect against adjacent live parts and take special precautions when close to bare conductors. 

 • Determine minimum approach distances, apply screening or shrouding, and when applicable, padlock both cable and busbar shutters. 

 • If working within the restricted approach boundary or vicinity zone where inadvertent movement could cause contact with live parts, special precautions must be employed, such as the use of the properly rated insulated gloves and tools. 7) Complete the permit to work and “Walk the Permit”. 

 • Check isolation points 

 • Verify that all circuits are isolated and secured 

 • Ensure all parties are integrated with the Lockout/Tagout 

 • Check the earths are properly applied 

 • Answer specific questions from the working group 

 • Ensure the work can proceed without danger 

 • Complete and verify the “Permit to Work”

Possible residual risks

Residual risks must be considered by the converter system integrator and/or plant owner when assessing the hazards of the equipment to personnel. The following risks can pose a hazard to converter system personnel: PRODUCT PCS6000 1) Electric power equipment generates electro-magnetic fields which can cause a hazard to people with metal implants and / or a pacemaker. 2) Converter system components can move unintentionally when being commissioned, operated, or serviced due to: 

 • Operation of the equipment outside the scope of the specifications 

 • Incorrectly assembled or installed equipment 

 • Wrongly connected cables 

 • External influence on, or damage of the equipment 

 • Wrong parameter settings 

 • Software errors 

 • Faulty hardware 3) Hazardous touch voltages can be present on converter system components, which can be caused by: 

 • Operation of the equipment outside the scope of the specifications 

 • External influence on, or damage of the equipment 

 • Induced voltages by external equipment 

 • Condensation on equipment components, or pollution 

 • Faulty hardware 4) High temperatures, noise, particles, or gases can be emitted from converter system components caused by: 

 • Operation of the equipment outside the scope of the specifications 

 • External influence on or damage of the equipment 

 • Wrong parameter settings 

 • Software errors 

 • Faulty hardware 

 • Hazardous substances can be emitted from converter system components, eg, due to Incorrect disposal of components

PCS6000 User manual 3BHS600000 E40 G en 24/114

5) Control cabinet door: danger of slight injuries, eg, foot crushing as the door of the control cabinet is not fixed to the cabinet when the locks are open.– Support the door with your hand when opening the locks.

– Weight per door: approximately < 20 kg. 6) Generator disconnector: risk of excessive arcing due to undetected arc.

– Risk of injuries from particles, contamination, electric shock, hearing damage, burns, explosion due to hardware failure, operation beyond specified limits, unauthorized access– No access to converter room or platform is allowed when the turbine is idling with open generator disconnectors or a 2CL converter is running in constricted operation 

– Turbine idling speed shall be limited to a maximum of 30% of rated speed

– 2CL converter must not be operated in constricted mode, except in case of converter defect that requires disconnecting the defective converter train

– Operation time in constricted mode and idling with open disconnector must be reduced as far as possible

Important note- main circuit breaker

The main circuit breaker (MCB) is a major protection device of the converter. If a serious fault occurs in the converter, the MCB must disconnect the main power supply to the converter immediately. The main power supply must be disconnected without delay on an open or trip command from the converter to prevent hazard to the personnel and further damage to the equipment. The MCB is located on the primary side of the converter transformer.

Safety and protection requirements

The system integrator must ensure that the following minimum safety and protection requirements for the converter are met.

– ISO13849-1

– IEC60204-1

Safety and protection requirements for the MCB

The following safety requirements are also in the MCB specifications for the converter:

– MCB open and/or trip command:  must be wired directly from the converter to the MCB. If you want to wire the command through a PLC or DCS system, the system must be certified to meet SIL 3 requirements and to fulfill the maximum MCB opening timing requirements. The converter must also be able to open the MCB at any time. It is not permitted to interrupt the open and/or trip command, eg, with a local-remote switch in the MCB.– Closing control of the MCB:  when the MCB is in service position, the converter must have exclusive control over closing the MCB, ie, local closing of the MCB is not permitted.

– MCB maximum opening time:  cannot exceed the maximum time that is defined in the product or project-specific MCB specifications. Typical maximum values for the converter are defined as follows:– Maximum protection trip time:  75 ms The maximum protection trip time is the maximum allowed breaking time (open and arcing) of the breaking device after the open command has been initiated to prevent further damage to the converter.

– Maximum safety trip time:  500 ms The maximum safety trip time is the maximum allowed time to ensure safe disconnection of the main power supply to prevent any hazard to personnel.

Maintenance recommendation

The MCB trip circuits should be checked annually.

ABB PCS6000 PRODUCT FAMLIY 

ABB GRID BREAKER UNIT GBU72 3BHE055094R0002 / 3BHE031197R0001 / ABB 3BHB030310R0001

ABB 3BHE055094R0002 GBU72   

ABB 4045L0006 

ABB 3BHB006338R0002 

ABB SDCS-COM-81 3ADT220134R0001 

ABB 3AXD50000949168

ABB 3AUA0000145150  

ABB SPDSI13  

  • GE 04220HL21204A IPC Control Module
  • ABB 3BSE000860R1 SB510 Backup Power
  • ABB 0504994880 Controller unit
  • ABB PFSA140 3BSE006503R1 Industrial robot Supply Unit
  • ABB 5SHX1445H0002 3BHL000387P0101 POWER IGCT unit
  • ABB 128877-103 CABLE, SP1200 IR DET.
  • ABB CI853K01 and TP853 RS-232C Interface
  • ABB REM610 MOTOR PROTECTION RELAY REM610C11HCNR
  • ABB IGBT 5SDF0860H0003 5SDF1045H0002 unit
  • ABB TC512V1 3BSE018059R1 RS485 Twisted pair Modem
  • ABB DO880 S800HI 3BSE028602R1 Digital Output
  • ABB GDD360C 3BHE047217R0101 Advanced Automation Solution
  • ABB UCD240A101 3BHE022287R0101 controller unit
  • ABB AC800F Ethernet Module AM811F 3BDH000050R1​
  • ABB AC800F Module AM801F 3BDH000040R1
  • ABB SD802F 3BDH000012R1 POWER UNIT
  • ABB operation panel PM820-2 3BSE010798R1 system module
  • ABB operation panel PM820-1 3BSE010797R1 system module
  • ABB CI857K01 3BSE018144R1 INSUM Ethernet Interface
  • ABB PM861/PM861AK01 and TP830 Processor Unit
  • ABB SA811F 3BDH000013R1 Power Supply 115/230 VAC
  • ABB 751010R0815 1VC1T0374A00R unit
  • 5SGY35L4510 Robot high voltage board Brand ABB
  • ABB HVC-02B 3HNA024966-00103 Robot high voltage board Brand HVC02B
  • ABB SLMG99 UNIT
  • ABB 086406-002 PWA.SIOC. SMART I/O CALIP 086407-502
  • ABB UCD208A101 3BHE020018R0101 UNIT
  • ABB UAD154A 3BHE026866R0101 UNIT
  • ABB GCD207B101 3BHE024642R0101 controller card
  • ABB TB820V2 S800 Modulebus module 3BSE013208R1
  • ABB UDD406A 3BHE041465P201 Control unit
  • ABB PPD113B01-10-150000 3BHE023784R1023 unit CPU module
  • ABB 5SHY35L4512 3BHE014105R0001 5SXE08-0166 IGCT unit
  • ABB Backplane Uni Type3+housing FETD685A1156U01
  • ABB 07DC91C GJR5251400R0202 Digital input and output Unit
  • ABB UNS2881b-P,V1 3BHE009319R0001 UNS2881BPV1 Inspirational system
  • ABB UNS2880B-P,V2 3BHE014967R0002 UNS2880B-PV1 Inspirational system
  • ABB CI810B 3BSE020520R1 AF 100 Fieldbus Comm. Interface
  • ABB FM9925a-E HIEE451116R0001 Interface Module Card
  • Bently 2300/25 0002 Vibration Monitors
  • Bently 2300/20 0002 Vibration Monitors
  • ALSTOM VP327 020-23EU 75X-6025-29 Control mainboard VP32702
  • ABB NE802 3BSE080237R1 Industrial switch
  • ABB 3BSE080207R1 NE810 Industrial switch
  • MOTOROLA MVME2400 VME Processor Modules
  • ABB 3BHE021481R0001 intelligent current distr UNIT
  • MOTOROLA MVME2434 VME Processor Modules
  • METSO PDP606 CONTROLLER unit
  • WOODWARD PG-PL-29 Governor 8577-613
  • GE IS230TNRLH1B Combination module kit Mark VI
  • GE IS230TNAIH2C Combination module kit Mark VI
  • ABB 3ASC25H204 DAPU 100 Control board I/O
  • ABB 3BHE014070R0101 V PPC905AE101 CCB-2 COMPLETE
  • ABB PRC3BSE050198R1 PM866K01 Processor Unit
  • Kongsberg RAIV400 600370 Remote Analogue Input
  • ABB SPSED01 event sequence module
  • ABB HIEE300900R0001 PP C322 BE01 PSR-2 processor + fieldbus
  • ABB 3BHE003604R0102 UFC765AE102 circuit board
  • ABB ACU-01B 3HNA024871-001 Robot controller
  • ABB XVC770BE101 3BHE021083R0101 circuit board
  • ABB UAC383AE01 HIEE300890R0001 Module
  • ABB REF610C11LCNP FEEDER PROTECTION RELAY
  • ABB MT91 Operator Panel MT-91-ARC FP A
  • ABB XUD194 XUD194A 3BHC018137R0001 module base
  • ABB 5SHY4045L0001 3BHB018162 3BHE009681R0101 GVC750BE101
  • ABB G2000A5.7ST graphical operation panel (HMI)
  • ABB 3BHE017628R0002 PPD115A02 SG579989013
  • ABB Motor Protection and Control REM615 Product Guide
  • ABB PFTL101B 3BSE004185R1 2.0KN sensor
  • ABB PFCL201CE 50KN 3BSX802939-108 sensor
  • ABB 3BHE023784R2530 PPD113B01-25-111000 AC 800PEC
  • ABB 3BHE046836R0101 GF D563 A101 LCI Conv. Interface (LIN)
  • ABB PPD512A10-454000 3BHE040375R103E PPD512 丨AC800PEC
  • ABB PPD117A3011 3BHE030410R3011 excitation controller
  • ABB AC800M PM891 3BSE053240R1 Processor module
  • ABB PP882 3BSE069275R1 HMI operating touch screen
  • ABB HIEE205014R0001 UNC 4673A,V1 Analog Measuring Card
  • ABB 128057-204 ASPC ASSY, W/-004
  • ABB 3BHB006716R0277 SYN 5302a-Z,V277: Auto dual channel Syn
  • ABB PFSK 163 V3 3BSE016323R3 Module
  • ABB 3BUS208796-001 HKQCS PARTS ON LINE
  • ABB 2VAA008425R1 RMU610 Base for redundant cRBX01
  • ABB 3BSE018876R1 PFSK 151 DSP-Signal processing
  • Westinghouse 1C31129G03 1C31129G01, 1B30035H01 Ovation analog output module
  • Pacific scientific PC833-001-N-BA communication module
  • HONEYWELL 30733159-002 supplied by Honeywell
  • BENTLY 3500/94M 184826-01 VGA Display Monitor
  • BENTLY 1900/65A 172323-01General Purpose Equipment
  • Bently Nevada 9200-01-01-10-00 Speed Sensor
  • Bently Nevada 330104-00-05-10-02-00 Proximity detector
  • Bently Nevada 330901-05-32-05-02-00 3300 XL NSv proximity sensor
  • Bently Nevada ASSY78462-01U I/O module recording terminal
  • 330901-00-90-05-02-00 Bently Nevada3300 NSv Proximity Probes
  • 330180-X1-CN Bently Nevada Proximity sensor
  • Bently Nevada 3500/92 136188-01 RS232 communication gateway module
  • General Electric Multilin345-E-P1-G1-L-E-E-N-Sn-D-N Transformer Protection
  • ALSTOM MV507A2D1A frequency driver Alspa MV500
  • Carrier CEPL130201-02 6400 General Purpose HVAC Comfort Controller
  • Carrier Transicold dual-view temperature display 76-50202-01/ 76-60876-01
  • Carrier CEPL131258-01-R HVAC system touch screen
  • Carrier Ces0110074-01 circuit control board
  • Carrier handheld controller CEPL130435-01 HK50AA033
  • Carrier-A12-00703-04 3922M1042473 stepper valve module
  • CARRIER 00PSG000469000A CEPL 130602-02-R CEBD 430602-07-RA
  • Hirschmann MM20-M4M4T1T1SBH Industrial Ethernet module
  • IC752SPL011 GE control panel
  • GE ALSTOM IR139-1丨063022350丨80801419丨B0037299control card
  • ALSTOM UT150-1 control module
  • ALSTOM AL132丨AL132A Control Card
  • ABB 2CTB802342R0000 surge protector
  • ABB PM118-7BPM1118 MAGNET (NEO) .50LG
  • Tektronix TDP0500 high pressure differential probe
  • Carrier CEPL130403-02-R Microprocessor Board CEBD430403-11-RC 32GB500382EE
  • BENTLY 106M1079-01-Y Power Module Original
  • ABB system module DLM02 original DO610,DO620
  • 1394-SJT22-A servo driver Allen-Bradley servo equipment
  • MOTOROLA SGLF4136FA PLC control system
  • B&R ECPE84-1B Modulus Input Module Quality Service
  • Foxboro FBM213 communication module supply
  • S-093H 3BHB030478R0309 ABB high voltage frequency conversion rack
  • ABB S-123H 3BHB030479R0512 rack
  • ABB 3BHL000406P0103 VFW 30/265Processor unit
  • ALSTOM V4561983-0100 EPIC II ESP controller
  • MOOG G761-3004B5 H38JOGM5VPH Servovalve
  • 3500 BentlyNevada 3500/05-02-01-00-00-00 System rack
  • 3500/05-01-02-00-00-01 Bently Nevada 3500/05 System Rack
  • 3500/05-01-01-00-00-00 BentlyNevada System Rack
  • BentlyNevada 3500/05-02-01-01 System Rack