1
1.1 Improvements
Changes CPU Firmware V2.3.3
The following improvements have been included in Firmware
V2.3.3.
File Handling
IEC 60870-5-104
Using CAA_File Library's Function Blocks under high CPU load
conditions caused stucking of the application program. Fixed.
The Answer to General Interrogations contained values with time
stamp instead of values without time stamp. Fixed.
2
2.1 Improvements
Changes CPU Firmware V2.3.2
The following improvements have been included in Firmware
V2.3.2.
Web Server
Ethernet
PROFINET
CANopen
CS31
Serial Communication
Serial Communication
File Handling
CPU PM5xx has crashed if visualizations with many polling varia
bles have been used. Fixed.
The Function Block ETH_MOD_MAST has not set its outputs DONE,
ERR and ERNO if a timeout has occured. Fixed.
After a PM5xx Standard CPU has been stopped and restarted, the
PROFINET Communication Module CM579-PNIO sends old
values to PROFINET IO Modules, e. g. CI501-PNIO. As a result,
the digital outputs have been activated for approximately 2 sec
onds. Fixed.
After a PM5xx Standard CPU has been stopped and restarted, the
CANopen Communication Module CM578-CN sends old values to
CANopen Slave Modules, e. g. CI581-CN. As a result, the digital
outputs have been activated for approximately 2 seconds. Fixed.
The parameter Ignore Module has not worked for IO expansion
modules attached to CI592-CS31 and DC551-CS31 module. It
worked only for the last IO module attached to the module cluster.
Fixed.
A runtime error occured while using the Function Block
COM_MOD_MAST via Communication Module CM574-RS when the
response time of the slave is longer than the timeout set for the
Function Block. Fixed.
A runtime error occured while using the Function Block
COM_MOD_MAST via Communication Module CM574-RS when the
response time of the slave is longer than the timeout set for the
Function Block. Fixed.
Function SysFileGetTime which is contained in library
SysLibFile always return FALSE at output SysFileGetTime.
Fixed.
TU810V1
0002-07-2-00001-01
TU847
769137 C 13CO2-10% 0746919 E
2RCA006836A0001E
TU810V1
DSTA131 2668180-48/2
CP800
2RCA025057A0001R
Add: Building F05, High-tech Software Park, Xiamen City, Fujian Province
Tel: 0592-5211302
Mobile: 17750019513 (WhatsApp)
Email: yy4291644@gmail.com
ivy@kongjiangauto.com
Website: https://www.abb-sis.com