

Protection, and general-purpose logic timers. Setting Groups and Virtual Control Switches make up the
control functions. The following paragraphs describe each protection and control function.
Overcurrent Protection
Phase and one neutral instantaneous overcurrent elements (50TP and 50TN) with settable time delays
provide inadvertent energization protection when properly supervised by voltage and/or frequency
elements (381. 159. 127).
One phase time-overcurrent element can be voltage restrained (51/27R) or voltage controlled (51/27C) to
provide system backup overcurrent protection (51P).
Two neutral inverse time-overcurrent elements provide ground overcurrent protection and/or generator
step-up (GSU) transformer ground backup protection (51TN and 151TN).
Each neutral 50/51 element can be assigned to monitor either the three-phase residual (IN
) or the optional
independent ground input (IG
).
One inverse time, negative sequence overcurrent element provides generator unbalance overload
protection (46).
Time-overcurrent functions employ a dynamic integrating timing algorithm covering a range from pickup to
40 times pickup with selectable instantaneous or integrated reset characteristics.
Time-overcurrent curves conform to the IEEE C37.112 document and include seven curves similar to
Westinghouse/ABB CO curves, five curves similar to GE IAC curves, four IEC curves, a fixed time curve,
and a user programmable curve. Each time current characteristic can be set for integrating or
instantaneous reset.
Digital signal processing filters out unwanted harmonic components while providing fast overcurrent
response with limited transient overreach and over-travel.
Voltage Protection
One volts per hertz protective element provides overexcitation protection for a generator and/or GSU
transformer (24).
Two phase overvoltage and two phase undervoltage element provides over/undervoltage protection (27P,
127P, 59P, and 159P). Phase overvoltage protection can be set for one of three, two of three, or three of
three logic. When a four-wire voltage transformer connection is used, overvoltage protection can be set
for either phase-to-phase voltage or phase-to-neutral voltage.
Two auxiliary overvoltage and two auxiliary undervoltage elements provide over/undervoltage protection
(27X, 127X, 59X, and 159X). Auxiliary voltage protection elements can be set to individually monitor the
auxiliary voltage fundamental, third harmonic, or phase 3V0 voltages. Complete stator ground fault
protection is provided when the auxiliary voltage input is connected to the generator grounding resistor
voltage, the 27X element is set for third harmonic undervoltage, and the 59X is set for the auxiliary
voltage fundamental.
With the auxiliary voltage input connected to the bus, one sync-check function provides synchronism
protection when putting the generator online (25). Sync-check protection checks for phase angle
difference, magnitude difference, frequency difference (slip) and, optionally, if the generator frequency is
greater than the bus frequency.
One negative-sequence overvoltage element provides protection for phase unbalance or a reverse
system phase (47).
Voltage transformer circuit monitoring adds security by detecting problems in the voltage transformer
sensing circuits and preventing misoperations of the 27P, 127P, 47. 59P, 159P, and the 51/27 functions
(60FL).
Directional Power Protection
Two directional power elements provide loss of prime mover protection and/or sequential trip, shutdown
operation (32. 132). Each directional power element can be set individually for forward or reverse power.
The power measurement algorithm is adapted as appropriate for any possible three-phase or single
phase voltage transformer connection. Directional Power is calibrated on a three-phase basis regardless
of the voltage transformer connection used.
Frequency Protection
Four over/underfrequency protection function blocks are provided: 81. 181. 281. and 381. Each function
block can be set for overfrequency or underfrequency operation.
Loss of Excitation
Loss of excitation protection consists of two elements (40Q, 140Q) that use offset sloped var flow
algorithm.
Breaker Failure Protection
One breaker failure protection block (BF) provides programmable breaker failure protection.
General Purpose Logic Timers
Four general-purpose logic timers (62. 162. 262. and 362) with six modes of operation are provided.
Setting Groups
Two setting groups allow adaptive relaying to be implemented to optimize BE1-GPS100 settings for
various operating conditions. Setting group selection can be made via relay logic, 43 auxiliary switches,
and hard-wired inputs.
Virtual Control Switches
BE1-GPS100 virtual control switches include one virtual breaker control switch and four virtual switches.
Trip and close control of a selected breaker can be controlled by the virtual breaker control switch (101).
The virtual breaker control switch is accessed locally from the front panel human machine interface (HMI)
or remotely from the communication ports.
Additional control is provided by the four virtual switches: 43. 143. 243. and 343. These virtual switches
are accessed locally from the front panel HMI or remotely from the communication ports. Virtual switches
Add: High-tech Software Park, Xiamen City, Fujian Province
Mobile: +86-17750019513(WhatsApp)
Email: yy4291644@gmail.com
Website: https://www.abb-sis.com