EMERSON Remote Automation Solutions D301761X012
ControlWave Micro Analog Input / Output Modules The Analog Input (AI), Analog Output (AO), and Analog Input/Output (AI/O) modules provide the ControlWave Micro with the ability to monitor and control various analog field signals. The following AI, AO, and AI/O modules are available.
6 Analog Inputs and 2 Analog Outputs module
6 Analog Inputs module
8 Isolated Analog Inputs module
4 Isolated Analog Outputs module All I/O modules have surge protection that meets C37.90- 1978 and IEC 801-5 specifications. 6 Analog Inputs and 2 Analog Outputs Module
The 6 Analog Inputs and 2 Analog Outputs module provides six analog inputs and two analog outputs. Analog inputs are externally sourced, single-ended, and individually jumper configurable for either 4 to 20 mA or 1 to 5 Vdc operation. Analog outputs are externally sourced (11 to 30 Vdc) and individually jumper configurable for 4 to 20 mA or 1 to 5 Vdc. Surge suppression between each signal and ground is achieved with 30 Vdc transorbs.
The 6 Analog Inputs and 2 Analog Outputs module is available with local or remote terminations. 8 Isolated High Common Mode (HCM) Analog Inputs Module
The 8 Isolated High Common Mode (HCM) Analog Inputs module provides eight differential analog inputs. Analog inputs are individually jumper configurable as internally sourced 4 to 20 mA non-isolated operation or externally sourced 4 to 20 mA, 1 to 5 Vdc, or 0 to 10 Vdc isolated operation. The analog input circuitry is electrically isolated from the bus interface circuitry of the ControlWave Micro.
The 8 Isolated HCM Analog Inputs module is available with local or remote terminations. 6 Analog Inputs Module The 6 Analog Inputs module provides six analog input channels. Analog inputs are externally sourced, singleended, and individually jumper configurable for either 4 to 20 mA or 1 to 5 Vdc operation. Surge suppression between each signal and ground is achieved with 30 Vdc transorbs.
The 6 Analog Inputs module is available with local or remote terminations. 4 Isolated Analog Outputs Module The 4 Isolated Analog Outputs module provides four analog outputs that can be individually jumper configured for 4 to 20 mA or 1 to 5 Vdc isolated operation. Analog outputs are electrically isolated from the CPU power system. Calibration data for each channel is stored in an onboard EEPROM for both current and voltage mode configurations.
The 4 Isolated Analog Outputs module is available with local or remote terminations. Local or Remote Terminations All analog I/O modules are available factory configured for either local terminations that consist of two 10-point terminal block assemblies or remote terminations that consist of two 14-pin mass termination headers. Terminations are pluggable and accept a maximum wire size of 14 AWG (American Wire Gauge). Remote terminations provide a convenient alternative to the standard direct connect termination. Remote terminations allow a concentration of electrical connections from one or more controllers to be located in a single area, such as the rear of a 19-inch cabinet. For more information on remote terminations, refer to Product Date Sheet CWMICRO.