The FOUNDATION™ Fieldbus Linking Device LD 810HSE Ex is registered as class 42c of the HSE profile, there- fore providing the following functions:
– It supports up to 4 separate FF-H1 links. In each of these links, the Linking Device operates as Link Master as well as SM Time Publisher.
– Identification of devices connected to the H1 links
– Configuration of connected H1 devices through System Management and Network Management via HSE
– Access to the function blocks of connected H1 devices via HSE
– Republishing of process data between H1 links
– Republishing of process data from H1 to HSE and vice versa
– Distribution of alarms and events sent by H1 devices
Functions
The LD 810HSE Ex is a gateway between an FF High Speed Ethernet (FF-HSE) subnet and FF-H1 links. It sup- ports device redundancy. The Linking Device meets protection class IP20 and is DIN rack mountable. It is pow ered by 24 V DC and supports Ethernet 10 Mbit/s or 100 Mbit/s.
Gateway
• Identification of devices connected to the H1 links
• Configuration of connected H1 devices through System Management and Network Management via HSE
• Access to the function blocks of connected H1 devices via HSE
• Republishing of process data between H1 links
• Republishing of process data from H1 to HSE and vice versa
• Distribution of alarms and events sent by H1 devices
• It supports up to 4 separate FF-H1 links
HSE
• System Management Agent
• Network Management Agent
• FMS Server providing object access to H1 de- vices
• Publishing/subscribing of process data from/to H1 devices
• Simple Network Time Protocol (SNTP) Server according to HSE specification (SM time syn- chronization)
• Simple Network Management Protocol (SNMP) is not supported
• Maintenance functions via web server
• Firmware update of Linking Device and H1 power supply modules via http or https
Maximum Limits on HSE
Configured HSE sessions 64
Configured HSE VCRs 400
Automatic HSE sessions 32
Automatic HSE VCRs 128
H1-H1 republishing 64
H1 Links
• System Management Manager • Network Management Manager • FMS Client for object access • Publisher and Subscriber of process data • Support of alarms and events • Link Master • SM Time Publisher: The LD will distribute the system time, i. e. the base for alarm time stamps. • Accesses to an H1 port MIB from H1 network is supported but write access from the H1 net- work is restricted.
H1 Live List
• The H1 live list contains all H1 devices that are active on the H1 link. • For each H1 device, the Linking Device records the node address, the PD tag, and the device ID.
Built-in Web Server
General information about the Linking Device can be queried via the web pages of the built-in web server. This requires a standard web browser sup- porting JavaScript on a PC that is connected to the Linking Device via Ethernet.
Installation in Hazardous Locations
The LD 810HSE Ex is suitable for use and installa- tion in areas with potentially explosive atmosphere in accordance to both the Division model (North America) and the Zone model (Europe and IEC coun tries) of hazardous locations.
Hazardous Location - North American Approval (cULus)
If indicated on the device label, the LD810 HSE Ex is suitable for use in Class 1, Division 2, Groups A, B, C, and D hazardous or non-hazardous locations.
The Linking Device does not meet the requirements of impact protection or IP54 (according to IEC 60529). Thus, it must be installed in a protective enclosure that meets the requirements for re sistance against impact and IP as stated in section 26.4 of IEC/EN 60079-0. This enclosure must be fully mounted and intact. If the enclosure is damaged, the operation is not permitted.
Hazardous Location - European and International Approval (ATEX, IECEx)
The equipment was assessed based on the follow- ing standards and editions: a) IEC 60079-0:2011 Ed. 6, modified Cor. 2012 + Cor. 2013 / EN 60079-0:2012 + A11:2013 b) IEC 60079-11:2011 Ed. 6 + Corr. 2012 / EN 60079-11: 2012 c) IEC 60079-15:2010 Ed. 4 / EN 60079-15: 2010 If indicated on the device label or by technical documentation, the LD 810HSE Ex is suitable for use in gas- Ex atmospheres of Zone 2 in the explo- sion groups IIA, IIB and IIC in temperature class T4, if accommodated in a tested enclosure.
• IECEx marking for explosion protection: Ex nA [ic] IIC T4 Gc
• ATEX marking for explosion protection: II3G nA [ic] IIC T4 Gc The Ex protection method [ic] corresponds only to the FF-H1 fieldbus interfaces.
The LD 810HSE Ex complies with the applicable standards and regulations and meets the require- ments of Directive 2014/34/EU. The requirements for mounting the device as part of the system in potentially explosive atmospheres (e. g. IEC/EN 60079-14) must be strictly adhered to.
Integration into the ABB Ability™ IT System Structure
Within a typical 800xA system structure as shown in the Figure below, a FOUNDATION™ Fieldbus subsystem is linked to the control system via the HSE subnet. The Linking Devices serve as gateways between the field devices on the H1 links and the HSE subnet.