(ISM) Radio-frequency Equipment -
Electromagnetic Disturbance Characteristics - Limits and Methods of Measurement
Meets Class A Limits
IEC 61000-4-2 ESD Immunity
Contact 4 kV, air 8 kV
IEC 61000-4-3 Radiated Field Immunity
10 V/m at 80 to 1000 MHz
IEC 61000-4-4 Electrical Fast
Transient/Burst Immunity
2 kV on I/O, dc power and communication
lines
IEC 61000-4-5 Surge Immunity
2kV on ac and dc power lines; 1kV on I/O
and communications lines
IEC 61000-4-6 Immunity to Conducted
Disturbances Induced by Radio frequency
Fields
10 V (rms) at 150 kHz to 80 MHz on I/O,
dc power and communication lines
IEC 61000-4-8 Power Frequency Magnetic
Field Immunity
30 A/m at 50 and 60 Hz
PRODUCT SAFETY
Underwriters Laboratories (UL) for U.S. and
Canada
UL/UL-C listed as suitable for use in
UL/UL-C listed Class I, Groups A-D;
Division 2; temperature code T4 enclosure
based systems. These modules are also UL
and UL-C listed as associated apparatus for
supplying non-incendive communication
circuits for Class I, Groups A-D hazardous
locations when connected to specified
I/A Series® processor modules as described
in the I/A Series DIN Rail Mounted
Subsystem User’s Guide (B0400FA).
Communications circuits also meet the
requirements for Class 2 as defined in
Article 725 of the National Electrical Code
(NFPA No.70) and Section 16 of the
Canadian Electrical Code (CSA C22.1).
Conditions for use are as specified in the
I/A Series DIN Rail Mounted Subsystem
User’s Guide (B0400FA).
European Low Voltage Directive 73/23/EEC
and Explosive Atmospheres (ATEX) directive
94/9/EC
CENELEC (DEMKO) certified as
EEx nA [nL] IIC T4 for use in CENELEC
certified Zone 2 enclosure certified as
associated apparatus for supplying non
incendive field circuits for Zone 2. Group IIC,
potentially explosive atmospheres when
connected to specified I/A Series processor
modules as described in the I/A Series DIN
Rail Mounted Subsystem User’s Guide
(B0400FA). Also, see Table 1 on page 8
ENVIRONMENTAL SPECIFICATIONS(1)
Operating
TEMPERATURE
FBM201e-20 to +70°C (-4 to +158°F)
Termination Assembly-20 to +70°C (-4 to +158°F)
RELATIVE HUMIDITY
5 to 95% (noncondensing)
ALTITUDE-300 to +3.000 m (-1.000 to +10.000 ft)
Storage
TEMPERATURE-40 to +70°C (-40 to +158°F)
Mounting
FBM201e
The module mounts on a modular baseplate. The
baseplate can be mounted on a DIN rail
(horizontally or vertically), or horizontally on a
19-inch rack using a mounting kit. Refer to DIN
Rail Mounted Modular Baseplates (PSS 21H
2W6 B4) for details.
TERMINATION ASSEMBLY
The TA mounts on a DIN rail and accommodates
multiple DIN rail styles including 32 mm (1.26 in)
and 35 mm 1.38 in).
Mass
FBM201e
284 g (10 oz) approximate
TERMINATION ASSEMBLY
Compression
181 g (0.40 lb) approximate
Ring Lug
249 g (0.55 lb) approximate
RELATIVE HUMIDITY
5 to 95% (noncondensing).
ALTITUDE-300 to +12.000 m (-1.000 to +40.000 ft)
Contamination
Suitable for use in Class G3 (Harsh) environments as
defined in ISA Standard S71.04. based on exposure
testing according to EIA Standard 364-65. Class III.
Vibration
7.5 m/S2 (0.75 g) from 5 to 500 Hz
PHYSICAL SPECIFICATIONS
Dimensions – FBM201e
HEIGHT
102 mm (4 in)
114 mm (4.5 in) with mounting lugs
WIDTH
45 mm (1.75 in)
DEPTH
104 mm (4.11 in)
Dimensions – Termination Assembly
See page 10
Part Number
FBM201e
P0924TA
TERMINATION ASSEMBLIES
See “FUNCTIONAL SPECIFICATIONS –
TERMINATION ASSEMBLIES” on page 8
PHYSICAL SPECIFICATIONS (CONTINUED)
Termination Cables
CABLE LENGTHS
Up to 30 m (98 ft)
CABLE MATERIALS
Hypalon®/XLP
TERMINATION CABLE TYPE
Type 1 – See Table 2 on page 9
BASEPLATE TO MAIN TA CABLE CONNECTION
FBM Baseplate End
37-pin D-subminiature
Termination Assembly End
25-pin D-subminiature
Construction – Termination Assembly
MATERIAL
Polyamide (PA), compression
PA, ring lug
TERMINATION ASSEMBLIES AND CABLES
Field input signals connect to the FBM subsystem via
DIN rail mounted Termination Assemblies, which are
electrically passive (see Figure 1). TAs for the
FBM201e module are available in the following forms:
Compression screw type using Polyamide (PA)
material
Ring lug type using Polyamide (PA) material
See “FUNCTIONAL SPECIFICATIONS –
TERMINATION ASSEMBLIES” on page 8 for a list of
TAs used with the FBM201e module.
Field Termination Connections
COMPRESSION-TYPE ACCEPTED WIRING
SIZES
Solid/Stranded/AWG
0.2 to 4 mm2/0.2 to 2.5 mm2/24 to 12 AWG
Stranded with Ferrules
0.2 to 2.5 mm2 with or without plastic collar
RING-LUG TYPE ACCEPTED WIRING SIZES
#6 size connectors (0.375 in (9.5 mm))
0.5 to 4 mm2/22 AWG to 12 AWG
A removable termination cable connects the DIN rail
mounted TA to the FBM via a field connector on the
baseplate in which the FBM is installed. Termination
cables are available in Hypalon® XLP.
Termination cables are available in a variety of
lengths, up to 30 meters (98 feet), allowing the
Termination Assembly to be mounted in either the
enclosure or in an adjacent enclosure. See Table 2
for a list of termination cables used with the TAs for
the FBM201e module