KONG -Y
NameDescriptionContent
Location:

HONEYWELL 05704-A-0121 ISS.03 QUAD RELAY INTERFACE CARD - 5704 Instructions

From: | Author:kongjiang | Time :2024-11-07 | 968 Browse: | 🔊 Click to read aloud ❚❚ ▶ | Share:

HONEYWELL 05704-A-0121 ISS.03 QUAD RELAY INTERFACE CARD - 5704 Instructions

The 5701 and 5704 control systems provide a complete solution for the operational and engineering requirements of a multi-channel fire and gas detection system. Each control card within the rack system provides sensor drive, signal acquisition, gas concentration display and comprehensive alarm facilities for one or more fire or gas sensors. The MODBUS Interface facility extends the capability of the control system by providing an external computer system with monitoring and control functions for every gas sensor or fire detector connected to the rack. The operation and alarm integrity of the System 57 is not affected by the MODBUS Interface. The digital data link uses a bi-directional 8-bit asynchronous serial connection that is configurable for baud rate, parity and stop bits. Two different modules are available, one supports both RS485 and RS422 electrical interface standards and the other supports the RS232 electrical interface standard. Depending upon the module type, system configuration and the capability of the host computer, various communication options are available as follows: Interface Transmission Dual Highway Multi-drop Mode Option Option RS485 Half Duplex Yes Yes (31 Nodes) RS422 Half Duplex No Yes (10 Nodes) RS232 Half Duplex No No The dual highway option provides a secondary or backup data link for increased communication integrity. Multi-drop configurations allow a single communication line to be shared by a number of devices reducing the number of communication ports required at the host computer. RS232 provides the lowest cost solution for connecting a single System 57 rack to a host computer. RS485 provides the best solution for multi-drop connection of more than one System 57 rack to a host computer and also gives the option of a secondary highway. RS422 is useful to provide multi-drop connection where the host computer software does not have the facility for transceiver direction control (transmit/receive/high impedance) that is required with RS485 connections.

In all cases the System 57 operates as a MODBUS Remote Terminal Unit (RTU), acting as a slave device node and transmitting data onto the communication line only in response to a request from a master device. The host computer system, typically a PLC, DCS or SCADA graphics package, acts as the master device controlling the communication system operation. The subset of MODBUS functions supported by the System 57 RTU are 02, 03, 04, 06 and 16. The MODBUS broadcast commands are not supported and will be ignored, however, global commands are available to reset all cards in the rack simultaneously. For a detailed description of the available commands and data formats refer to the System 57 MODBUS Function Reference given in Section 7. 2.2 MODBUS INTERFACE MODULE - RS485/422 2.2.1 General The RS485/422 Interface Module has two differential 5V transceivers designated channel 1 and channel 2. Each transceiver channel can be resistively terminated by setting LK1 and LK2 respectively (see Figure 1 and Section 3.4.3). The interface signals are isolated from the System 57 power supply 0V and Ground to protect the host computer against damage due to earth loops. 2.2.2 RS485 Operation An outline RS485 connection diagram is shown in Figure 4. When configured for the RS485 mode, transceiver Channel 1 is used in dual highway systems for the primary highway or the only highway in single highway systems. Transceiver Channel 2 is used only in dual highway systems where it functions as the secondary highway. Depending upon the type of installation, operation is possible over distances up to 1.2km (3900ft). In the multi-drop mode up to 32 nodes, including the host, can be connected. The terminal connections are: CH1-A, CH1-B Differential Transceiver Channel 1 (Primary). CH2-A, CH2-B Differential Transceiver Channel 2 (Secondary). DGND Isolated Data Ground. In a dual highway system the MODBUS uses, at any one time, only one of the two available highways, either the primary or the secondary. The interface automatically switches between highways when a communication failure is detected.

The highway switching process is controlled as follows:

a. The inactive highway is continuously monitored for data

communication.

b. If data communication is detected on the inactive highway, the

inactive highway is assumed to be fully serviceable.

c. If valid data communication ceases on the active highway and the

inactive highway is perceived to be serviceable, the MODBUS

interface switches between channels.

When configured for RS422 mode, transceiver Channel 1 is used for transmission from the System 57 RTU to the host computer and transceiver Channel 2 is used as a receiver for transmissions from the host computer to the System 57 RTU. Depending upon the type of installation, operation is possible over distances up to 1.2km (3900ft). Although the EIA RS422 standard specifies only point to point applications, the addressable operation of System 57 permits a modified 'broadcast' mode topology that allows multi-drop connection of up to 10 nodes. Each System 57 node is held in a high impedance state until it receives an appropriately addressed request, when it enables its transmitter for the duration of the response. The terminal connections are: TX-A, TX-B Differential Transceiver Output from RTU. RX-A', RX-B' Differential Receiver Input to RTU. DGND Isolated Data Ground

The RS232 Interface Module has transmit and receive data lines and two handshaking lines. The interface conforms to the RS232 standard giving ±12V output drive. Depending upon the type of installation, operation is possible over distances up to 15m (49ft). To protect the host computer against damage due to earth loops, the interface signals are isolated from the System 57 power supply 0V and Ground. The terminal connections are designated as follows: RXD Receive Data input to RTU. TXD Transmit Data output from RTU. DSR Data Set Ready input to RTU. DTR Data Terminal Ready output from RTU. SGND Isolated Signal Ground.

There are two versions of the Engineering Card. The MODBUS Interface Kit can only be fitted to the Mk 2 Engineering Card. With the Engineering Card removed from the rack, the type of Engineering Card can be visually identified as follows: a. Mk I hardware by the presence of only one 28 pin DIL IC socket on the card pcb. b. Mark II hardware by the presence of two 28 pin DIL IC sockets and a rectangular cutout near the centre of the card pcb. (See Figure 7). A summary of the MODBUS Interface installation procedure is shown below: a. Unpack and check the contents of the kit. b. Remove the Engineering Card from the rack. c. Install the Software Expansion EPROM Integrated Circuit. d. Install the RAM Expansion Integrated Circuit. e. Install the MODBUS Interface Module. f. Wire the DC Input Card terminal blocks to the host computer. g. Configure and Commission After installation is complete perform the commissioning procedures outlined in Section 5. The following sections provide a detailed explanation of the installation operations.

On receipt carefully unpack the equipment observing any instructions printed on or contained in the packaging. Check the contents for transit damage and ensure that the following items are present:

For the MODBUS Interface Module Kit: RS485/422: a. MODBUS Interface Module RS485/422 (05701-A-0282). b. Engineering Card Expansion Option EPROM integrated circuit (05701-A-0385). c. RAM expansion integrated circuit type HN6264ALP. d. User Manual (05701-A-5006). For the MODBUS Interface Module Kit RS232: a. MODBUS Interface Module RS232 (05701-A-0287). b. Engineering Card Expansion Option EPROM integrated circuit (05701-A-0385). c. RAM expansion integrated circuit type HN6264ALP. d. User Manual (05701-A-5006). 3.3 INSTALLING THE MODBUS INTERFACE KIT Except for Step (6) which applies to the RS485/422 Module only, the following installation procedure applies to both versions of the MODBUS Interface Kit: (1) Isolate the SYSTEM 57 Rack from all power sources. (2) Unscrew the two front panel screws that retain the Engineering Card and using the extraction tool supplied with the system pull the Engineering Card from the rack.

(3) Insert the Software Upgrade EPROM integrated circuit (05701-A0385) into the socket IC2 on the Engineering Card, ensuring that pin 1 of the IC is aligned correctly with pin 1 of the socket and that all pins are properly inserted into the socket. Note: If an IC is already fitted to socket IC2, this should be removed and discarded.

(4) Insert the RAM expansion integrated circuit (HN6264ALP) into the socket IC12 on the Engineering Card, ensuring that pin 1 of the IC is aligned correctly with pin 1 of the socket and that all pins are properly inserted into the socket. (5) Using small pliers or an electrical screwdriver gently remove the Engineering Card shorting link LK1 and replace to short pins 1 and 2. See Figure 7. (6) This step applies to the RS485/422 module only. For correct operation, especially at high baud rates, RS485 and RS422 highways should be resistively terminated. In RS422 host systems, a terminator resistance is only required at the receiver device located in the host and at the receiver device located in the System 57 node at the far end of the cable. In RS485 host systems, a terminator resistance is required at the transceiver device located in the host and at the transceiver device located in the System 57 node at the far end of the cable. For dual highway RS485 systems, both highways should be terminated as described above. By default the RS485/422 module transceivers are unterminated. If a resistive termination is required, use small pliers or an electrical screwdriver to gently remove the shorting links, LK2 (Channel 1) or LK1 (Channel 2), on the RS485/422 Module from pins 1 and 2 and replace to short pins 2 and 3. (See Figure 1 and Section 3.4.3). (7) Insert the MODBUS Interface Module into the socket headers J1 and J2 on the Engineering Card, ensuring that pin 1 of the module pin headers is correctly aligned with pin 1 of the Engineering Card socket headers. (8) Re-insert the Engineering Card into the rack, tighten the two front panel screws and go to the Section 3.4.



  • AEROTECH SM Series High-Performance Stepper Motors
  • AEROTECH BLMSC Series Linear Motors
  • AEROTECH Custom Linear Motors
  • AEROTECH BMS Series Brushless, Slotless Rotary Motors
  • AEROTECH BM Series Brushless Rotary Motors
  • AEROTECH BLMX Series Linear Motors
  • AEROTECH BLMH Series Linear Motors
  • AEROTECH BLM Series Linear Motors
  • AEROTECH BLMC Series Linear Motors
  • AEROTECH BLMUC-143    Linear motor forcer with thermistor
  • AEROTECH BLMUC-111    Linear motor forcer with thermistor
  • AEROTECH BLMUC-95  Linear motor forcer with thermistor
  • AEROTECH BLMUC-79 Linear motor forcer with thermistor
  • AEROTECH BLMUC Series Linear Motors
  • AEROTECH Automation1 FLEX Distributed Amplifier Multi-Axis Servo Control System
  • AEROTECH Automation1 FLEX Distributed Amplifier Multi-Axis Servo Control System
  • AEROTECH Automation1 HXA4 6-Axis Hexapod Servo Drive
  • AEROTECH Automation1 iHXA4 6-Axis Hexapod Servo Drive with Motion Controller
  • AEROTECH Modular System Control Console
  • AEROTECH TV Series Transformers
  • AEROTECH TM Series Transformers
  • AEROTECH UFM Noise Filter Module
  • AEROTECH MFM Motor Filter Module
  • AEROTECH MPG Handwheel Pendant
  • AEROTECH Automation1 Multi-Axis Joystick
  • AEROTECH ETM Enhanced Throughput Module
  • AEROTECH Automation1 XL4s High-Speed, Single-Phase Linear Servo Drive
  • AEROTECH Automation1 XL2e Enhanced, Compact Linear Servo Drive
  • AEROTECH Automation1 XL5e Enhanced, Linear Servo Drive
  • AEROTECH Automation1 iXL5e Enhanced Linear Servo Drive with Motion Controller
  • AEROTECH Automation1 GI4 Laser Scan Head Controller
  • AEROTECH Automation1 SI4 Stepper Interface
  • AEROTECH Automation1 XI4 Servo Interface
  • AEROTECH AEROTECH Automation1 iXI4 Servo Interface with Motion Controller
  • AEROTECH Automation1 XC6e Enhanced, High-Power PWM Servo Drive
  • AEROTECH Automation1 iXC6e Enhanced, High-Power PWM Servo Drive with Motion Controller
  • AEROTECH Automation1 XC2 Compact PWM Servo Drive
  • AEROTECH Automation1 XC4 PWM Servo Drive
  • AEROTECH Automation1 GL4 Galvo Laser Scan Head Linear Drive
  • AEROTECH Automation1 XC2e Enhanced, Compact Servo Drive with PWM+
  • AEROTECH Automation1 XC4e Enhanced, PWM Servo Drive
  • AEROTECH Automation1 XR3 Multi-Axis Servo Drive Rack
  • AEROTECH Automation1 iXR3 Multi-Axis Servo Drive Rack with Motion Controller
  • AEROTECH Automation1 iXC2 Compact PWM Servo Drive with Motion Controller
  • AEROTECH Automation1 iXC2e Enhanced, Compact PWM+ Servo Drive with Motion Controller
  • AEROTECH Automation1 iXC4 PWM Servo Drive with Motion Controller
  • AEROTECH Automation1 iXC4e Enhanced, PWM Servo Drive with Motion Controller
  • AEROTECH Automation1 iPC Industrial PC with Motion Controller
  • AEROTECH EPICS & TANGO Drivers for Distributed Control Systems
  • AEROTECH .NET, C, Python & LabVIEW APIs Custom Application Develotpmen
  • AEROTECH Automation1 Industrial Ethernet Support
  • AEROTECH Automation1 iSMC Intelligent, Software-Based Motion Controller
  • AEROTECH Automation1 iXA4 1- 2- or 4-Axis PWM Servo Drive with Motion Controller
  • AEROTECH Automation1 XA4 1- 2- or 4-Axis PWM Servo Drive
  • CTI 2500-ADP2-DISC Discrete Wiring Adapter for Series 500
  • CTI 2500-ADP1 Analog Wiring Adapter for Series 500
  • CTI 2500C-RADP-RS485 Remote Base Controller Adapter for Series 500
  • CTI 2500C-RADP-RBC Profibus RBC Adapter for Series 500
  • CTI 2500C-PADP-120V 120VAC 50W Power Supply for Series 500
  • CTI 2500-RADP RBC Adapter for Series 500
  • CTI 2500-R4500 520/530/DBC Adapter for Series 500 - MATURE
  • CTI 2500-PADP Power Supply Adapter for Series 500
  • CTI 2500-IADP I/O Adapter for Series 500
  • CTI 2500-VP15A-N4-W7 15" Flat-Panel PC with Windows® 7 Embedded
  • CTI 2500S-27-1750 Slice I/O, Ethernet, RS232/485. 900MHz, 2DIO / 4UAI / 2AI
  • CTI 2500S-26-1750 Slice I/O, Ethernet, RS232/485. 900MHz, 8DIO / 2UAI
  • CTI 2500S-23-1750 Slice I/O, Ethernet, RS232/485. 900MHz, 4DI / 4DO / 2UAI / 2AO
  • CTI 2500S-27-1550 Slice I/O, RS232/485. 2DIO / 4UAI / 2AI
  • CTI 2500S-26-1550 Slice I/O, RS232/485. 8DIO / 2UAI
  • CTI 2500S-23-1550 Slice I/O, RS232/485. 4DI / 4DO / 2UAI / 2AO
  • CTI 2500S-27-1050 Slice I/O, Ethernet, 2DIO / 4UAI / 2AI
  • CTI 2500S-26-1050 Slice I/O, Ethernet, 8DIO / 2UAI
  • CTI 2500S-23-1050 Slice I/O, Ethernet, 4DI / 4DO / 2UAI / 2AO
  • CTI 2500C-32F-CJC 32-Pin Field Wiring Connector with Cold Junction Compensation
  • CTI 2500C-32F 32-Pin Field Wiring Connector
  • CTI 2500C-8-TC Eight Thermocouple Inputs
  • CTI 2500C-8-RTD Eight RTD Inputs
  • CTI 2500C-8-RL-FC 8 Form-C Relay Outputs
  • CTI 2500C-8-IDO-24V 8 Isolated 24VDC Outputs
  • CTI 2500C-8-IDO-120V 8 Isolated 120VAC Outputs
  • CTI 2500C-16-DO-24V Sixteen 24VDC Digital Outputs
  • CTI 2500C-16-DO-120V Sixteen 120VAC Digital Outputs
  • CTI 500C-16-IDI-24V Sixteen Isolated 24V AC/DC Digital Inputs
  • CTI 2500C-16-IDI-120V Sixteen Isolated 120V AC/DC Digital Inputs
  • CTI 2500C-16-DIDO-SIM Sixteen Digital Input and Output SImulator
  • CTI 2500C-16-DI-24V Sixteen 24V AC/DC Digital Inputs
  • CTI 2500C-16-DI-120V Sixteen 120V AC/DC Digital Inputs
  • CTI 2500C-RBC-RS485 RS485 Remote Base Controller
  • CTI 2500C-RBC-PRF Profibus Remote Base Controller
  • CTI 2500C-PS-24V-35 35-Watt DC Power Supply
  • CTI 2500C-PS-120V-35 35-Watt AC Power Supply
  • CTI 2500C-R8 Eight-Slot Base
  • CTI 2500C-R4 Four-Slot Base
  • CTI 2500C-R16 Sixteen-Slot Base
  • CTI 2500C-2572-B Fast Ethernet TCP/IP Adapter
  • CTI 2500C-J750 Compact Janus PAC with 3MB Project Memory
  • CTI 2500C-C300 CPU with 512K User Memory
  • CTI 2500C-C200 CPU with 256K User Memory
  • CTI 2500C-C100 CPU with 128K User Memory
  • CTI 2500C-8-AO 8 Analog Outputs
  • CTI 2500C-8-AI 8 Analog Inputs
  • CTI 2559-FCAL Precision Calibration Connector
  • CTI 2559-FPC 2559-FPC 40-pin screw terminal connector
  • CTI 2500-RFC PLC to RF Modem Cable
  • CTI 2500-40F 40-Position Standard Screw-Terminal Connector
  • CTI 2505 Vibration Sensor Interface Module
  • CTI 2554-A 4-Channel Isolated High Speed Counter Module
  • CTI 2553-A 2-Channel Mag Meter Input Module
  • CTI 2502 2-Channel High Speed Counter Input Module
  • CTI 2559-TC 8-Channel Thermocouple Input Module
  • CTI 2556-A 16-Channel Isolated Thermocouple Input Module
  • CTI 2556 16-Channel Isolated Thermocouple Input Module
  • CTI 2551-A 8-Channel Isolated Thermocouple Input Module
  • CTI 2559-RTD 8-Channel RTD Input Module
  • CTI 2557-A 16-Channel RTD Input Module
  • CTI 2557 16-Channel RTD Input Module
  • CTI 2552-A 8-Channel Isolated RTD Input Module
  • CTI 2534 8-Point Form-C Relay Output Module
  • CTI 2532 16-Point Form-A Relay Output Module
  • CTI  2531 32-Point Form-A Relay Output Module
  • CTI  2530 8-Point Form-C Relay Output Module
  • CTI  2562 8-Channel Analog Output Module
  • CTI  2560-A 8-Channel Isolated Analog Output Module
  • CTI  2501 8in/4out Analog Module
  • CTI  2558 8-Channel Analog Input Module
  • CTI  2555-A 16-Channel Analog Input Module
  • CTI  2550-A 8-Channel Isolated Analog Input Module
  • CTI  2599 8/16/32-Point AC Output Module