1. Product overview
Honeywell S4560M S4560M1036 is a high-performance automatic controller specially designed for industrial boiler system by Honeywell Company, which belongs to the core control component of S4560M series. This equipment is mainly used for boiler combustion control, safety interlock and process automation to ensure the efficient, safe and stable operation of boiler system.
1.1 Main functions
Combustion control: accurately adjust the fuel-air ratio and optimize the combustion efficiency.
Safety protection: monitor the flame state and provide Flame Safeguard.
Interlocking control: manage key equipment such as fans, fuel valves and igniters.
Fault diagnosis: detect system abnormality in real time and trigger alarm.
2. Hardware architecture and key components
2.1 Core hardware composition
2.2 technical characteristics
Modular design: easy to maintain and expand functions
Anti-interference ability: it conforms to the industrial EMC standard (EN 61000-6-2/4).
Wide temperature operation:--20°C ~ +60°C (suitable for boiler room environment)
Redundancy design: double flame detection channels are optional to improve reliability.
3. Technical parameters
3.1 Electrical characteristics
Parameter specification
Power supply voltage is 24v AC/DC 10% or 110-240V AC (optional).
Power consumption ≤ 15w (typical)
Relay capacity 5A @ 250V AC (resistive load)
Analog input 2 channels 4-20mA/0-10V (configurable)
Digital input 8-way dry contact/wet contact (24V DC)
3.2 Environmental adaptability
Parameter specification
Protection grade IP20 (installation of control cabinet)
Humidity range 5% ~ 95% RH (non-condensing)
Vibration resistance 1g @ 10-150 Hz (in accordance with IEC 60068-2-6)
4. Typical application scenarios
4.1 Industrial Boiler System
Steam boiler: control fuel supply and steam pressure adjustment.
Hot water boiler: temperature PID control, circulating pump management
Hot oil boiler: oil temperature monitoring and safety interlock
4.2 Combustion Management System (BMS)
Ignition timing control: pre-purging-ignition-start of main burner.
Flame monitoring: detect the combustion state in real time, and automatically cut off the fuel when flameout.
Fault protection: interlock shutdown due to low gas pressure and insufficient wind pressure.
5. Installation and debugging guide
5.1 Installation Specification
Mechanical installation:
It is fixed by DIN guide rail (according to EN 60715 standard).
Avoid areas with high temperature, high humidity or severe vibration.
Electrical wiring:
Connect the sensor signal with shielded cable.
Power cables (such as fuel valve control) are routed separately from control lines.
Grounding requirements:
Independent grounding wire (sectional area ≥ 2.5 mm)
Grounding resistance < 4 ω
5.2 parameter setting
Combustion control parameters: ignition time and flame signal threshold.
Safety delay: pre-purging time (usually ≥30 seconds)
Alarm thresholds: low gas pressure limit and high exhaust temperature limit.
6. Maintenance and troubleshooting
6.1 Daily maintenance
Periodic inspection: clean the flame detector window.
Contact maintenance: check the oxidation of relay contacts.
Firmware upgrade: update through Honeywell service tools.