QB1T & QB2T proportion INSTALLATION & MAINTENANCE INSTRUCTIONS

From: | Author:kongjiang | Time :2025-06-16 | 745 Browse: | Share:

DESCRIPTION / IDENTIFICATION

The QB series valve uses Proportion- Air closed loop technology for Pressure control. It gives an output pressure proportional to an electrical command signal input.

The QB1 is a complete closed loop servo system consisting of valves, manifold, housing and electronic controls. Pressure is controlled by the use of two solenoid valves. One valve functions as inlet control, the other as exhaust. The pressure output is measured by a pressure transducer internal to the QB1 and provides a feedback signal to the electronic controls. This feedback signal is compared with the command signal input.  A difference between the two signals causes one of the solenoid valves to open, allowing flow in or out of the system. Accurate pressure is maintained by controlling these two valves.

The QB2 is similar to the QB1 but uses a double loop control scheme.  In addition to the internal pressure transducer, the QB2 receives an electrical signal from an external sensing device. This primary feedback signal is compared against the command signal input. This comparison is then summed with the internal pressure transducer signal. The gain of the circuit is such that priority is given to the external feedback signal. A difference between the command signal and the feedback signal causes one of the solenoid valves to be activated.

A monitor output is provided for the system measurement. All QB valves come standard with an analog voltage monitor output.

QB1 monitor output is an amplified signal from the internal pressure transducer.  QB2 monitor output is a buffered signal from the primary external transducer connected to the QB2.

For QB valves with model number TFEE or TFIE the monitor output is voltage. The monitor output is analog current, if the valve model number is TFEC or TFIC.  See ordering information for further details.

INSTALLATION

1. Apply a small amount of anaerobic sealant (provided) to the male   threads of the in-line filter supplied with valve.   CAUTION: USE ONLY THE THREAD SEALANT PROVIDED.   OTHER SEALANTS SUCH AS PTFE TAPE AND PIPE DOPE CAN MIGRATE INTO THE FLUID SYSTEM CAUSING FAILURES. 

 2. Install the in-line filter into the port labeled IN on QB valve. 

 3. Connect supply line to the in-line filter port.  Connect device being controlled to port labeled OUT on QB valve. 

 4. Mount valve accordingly. 

 5. The valve can be mounted in any position without affecting performance.  Mounting bracket QBT-01 (ordered separately) can be used to attach valve to a panel or wall surface. 

 6. Proceed with electrical connections.

RE-CALIBRATION PROCEDURE

All QB control valves come calibrated from the factory by trained personnel using precision calibration equipment.  The QB valve is a closed loop control valve using a precision electronic pressure sensor.   Typical drift is less than 1% over the life of the product.  If your QB valve appears to be out of calibration by more than 1%, it is not likely to be QB.   Check the system for plumbing leakage, wiring and electronic signal levels.   Verify the accuracy of your measuring equipment before re calibrating.   Consult factory if you have any questions or require assistance.  If the QB valve needs re-calibration, use the procedure described below:

QB1 VALVES

  1. Identify the inputs and outputs of the valve using the model number of the valve, calibration card included with the valve, and the information provided in this sheet.

  2. 2. Connect a precision measuring gage or pressure transducer to the OUT port of the QB. NOTE:  THERE MUST BE A CLOSED VOLUME OF AT LEAST 1 CU. IN. (17 CC) BETWEEN THE VALVE OUTLET AND THE MEASURING DEVICE FOR THE VALVE TO BE STABLE.

  3.  Connect the correct supply source to the IN port of the QB, making sure the pressure does not exceed the rating for the valve (See Table 1).

  4.  Locate the plastic calibration access cap on top of the QB valve and completely remove it.  Located underneath are two adjustment trim pots, Zero “Z” and Span “S”.  See figure 1 for pots location.

  5.  NOTE:  Only use this step if your device is totally out of calibration.  If it is slightly out of calibration, omit this step and move on to paragraph

  6.   Using a small screwdriver, turn both trim pots 15 turns clockwise.   Then turn both trim pots 7 turns counterclockwise.  This will put the QB roughly at mid-scale. 6. Make correct electrical connections as noted.  Make sure there is a proper meter in place to measure the command input to the QB.

  7.  Set the electrical command input to MAXIMUM value.

  8.  Adjust the SPAN pot until MAXIMUM desired pressure is reached (clockwise increases pressure).

  9.  Set the electrical command input to MINIMUM value.

  10.  Adjust the ZERO pot until MINIMUM desired pressure is reached (clockwise increases pressure).

  11. Repeat ZERO and SPAN adjustments, which interact slightly, until QB1 valve is calibrated back to proper range.  Step 6 - 9.

  12. Replace calibration access cap.

  • Woodward easYgen-3200-1/P1 8440-2049
  • Woodward easYPROTEC-1410-7 8441-1161 8441-1160
  • Woodward MFR300-71M/K45 8444-1111 8444-1112
  • Woodward MFR300-75M 8444-1107 8444-1108 8444-1109
  • Woodward MFR300-71M/K42 8444-1104
  • Woodward MFR300 75M/SU03, Transducer 8444-1093 8444-1094 8444-1095
  • Woodward MFR300-71M 8444-1091 8444-1092
  • Woodward MFR300-15M 8444-1090 8444-1089
  • Woodward MFR300-11M 8444-1071 8440-1089
  • Woodward MFR500-6M/WK0400 + DPC USB 8444-1070
  • Woodward MFR300-15M 8444-1064
  • Woodward SPM-D2-1040B/NYB 8440-2189
  • Woodward SPM-D2-1010B/NYB 8440-2177
  • Woodward SPM-D2-10B/PSY5-FU-D 8440-2170
  • Woodward SPM-D2-1040B/XN analog speed/voltage bias 8440-2190
  • Woodward MFR300-71M 8444-1063
  • SPM-D2-1010B/X analog speed/voltage bias 8440-2168
  • Woodward SPM-D2-1040B/X analog speed/voltage bias 8440-2171
  • Woodward SPM-D2-1010B/N wide range power supply 8440-2174
  • Woodward SPM-D2-1040B/N wide range power supply 8440-2175
  • Woodward SPM-D2-1010B /110VAC sensing 8440-2166
  • Woodward SPM-D2-1040B /400VAC sensing 8440-2164
  • Woodward DTSC-200A 8440-2297
  • Woodward DTSC-200-55B/K38 8440-2155
  • Woodward DTSC-200-51B 8440-1867 8440-1868
  • Woodward 8445-1049 8445-1048 Converter, 1x FO to CAN
  • Woodward easYlite-200 8446-1007 LED Lamp Expansion Module
  • Woodward IKD-OUT-16 16 DO Expansion Card 8440-2306
  • Woodward IKD-IN-16 16 DI Expansion Card 8440-2307
  • Woodward IKD1M 8 DI/8 DO Expansion Card 8440-2116
  • Woodward easYview-07-30 8446-1071
  • Woodward easYFLEX-3400XT-P2 (GAP) 8440-2217
  • Woodward easYFLEX-3400XT-P2 (GAP) 8440-2217
  • Woodward easY-I-3400XT-P1 8440-2293
  • Woodward easY-I-3500XT-P1 8440-2292
  • Woodward MSLC-2XT 8440-2298 Master Synchronizer and Load Control
  • Woodward DSLC-2XT 8440-2299 Digital Synchronizer and Load Control
  • Woodward: GC-3400XT-P1 8440-2267 Group Controller
  • Woodward: LS-612XT-P2 8440-2317
  • Woodward: CONTROL-LS-612XT-P1,8440-2222 Cabinet back mounting
  • Woodward: LS-522-1/P1 8440-2179
  • Woodward: LS-522-5/P1 8440-2151
  • Woodward: LS-512-1/P1 8440-2181
  • Woodward: LS-512-5/P1 8440-2153
  • Woodward: LS-521-1/P1 8440-2178
  • Woodward: CONTROL-LS-521-5/P1 8440-2150
  • Woodward: LS-511-1/P1 8440-2180 Circuit Breaker Control & Protection
  • Woodward: CONTROL-LS-511-5/P1 8440-2152 Circuit Breaker Control & Protection
  • Woodward easYgen-3500XT-P2-LT-RENTAL 8440-2291 Genset Control for
  • Woodward eeasYgen-3500XT-P2-RENTAL 8440-2290
  • Woodward easYgen-3200XT-RENTAL 8440-2285
  • easYgen-3500XT-P2-K58 8440-2318
  • easYgen-3500XT-P2-LT 8440-2089
  • Woodward easYgen-3500XT-P2 8440-2088 Genset Controller
  • Woodward: easYgen-3500XT-P1-LT 8440-2086
  • Woodward: easYgen-3500XT (P1) 8440-2085
  • Woodward: easYgen-3400XT (P2), Genset Controller 1A/5A 8440-2087
  • Woodward: easYgen-3400XT (P1) 8440-2084
  • Woodward 8440-2082 EasyGen 3200XT Genset Controller
  • Woodward: easYgen-3200XT (P1/LT) 8440-2083
  • Woodward: easYgen-3100XT 8440-2081
  • Woodward: easYgen-2500 (1A/P1) K33 8440-2096
  • Woodward easYgen-2500-5/P1-K33 Rental Version 8440-2029
  • Woodward easYgen-2500-1/P1 8440-1860
  • Woodward easYgen-2500-5/P1 8440-1884
  • Woodward easYgen-2300-1/P2 8440-2123 Controller
  • Woodward easYgen-2300-5/P2 8440-2058
  • Woodward 2300E – Ordinary Locations 8273-1017
  • Woodward Vertex Compressor Control 8200-1370
  • MicroNet Safety Module - Bulkhead Mount 8237-2492 Woodward
  • ProTech TPS - Bulkhead Mount Independent Relays 8237-2602
  • Woodward ProTech-GII - Bulkhead Mount Independent Relays 8237-2594
  • ABB AX410, AX411, AX413, AX416, AX418, AX450, AX455 and AX456 Single and dual input analyzers for low level conductivity
  • ABB AX411/511010/STD Single and dual input analyzers
  • Woodward ProTech-SX - Panel Mount, HV/LV 8237-1242 8237-1243
  • Woodward SPC Servo Position Controller 8200-226 8200-227
  • Woodward Peak200 – Bulkhead Mount, LV 8200-1500
  • Woodward 505HT for Pelton Turbines 8200-1400, 8200-1401
  • Woodward 2301E-HT Hydro (Francis Turbines) P/N 8237-2046
  • Woodward 8273-1013 8273-1014 Digital Electronic Load Sharing
  • Control Panel 9907-2024 Woodward
  • ABB REF630 UBFNAAABBBAZANBBXB Feeder Protection and Device
  • ABB PPD513 A2A-11165 High-performance controller
  • UniOP CP10G-04 CP10G-04-0045 Interface Module
  • UNIOP MKDR-04-0021 Monochrome LCD (with Contrast Control)
  • UNIOP eTOP03-0046 Monochrome LCD (STN)
  • UNIOP MKDR-16-TA-0045 HMI TOUCH SCREEN
  • UNIOP Operator Interface Display MD02R-04-0042
  • UniOP Display Screen eTOP20C-0050 eTOP20C
  • UniOp eTOP05-0045 eTOP05. eTOP05P Operator Interface Touch Panel
  • UNIOP ETOP11-0050 HMI 5.6Color Operator Interface Touch Panel
  • UniOp eTOP306 Panel
  • UniOP eTOP308 ETOP308U301 HMI Panel
  • UniOP ePALM10-0061 Handheld Robot Trainer
  • UniOP CP01R-04 CP05R-04 and CP01F-02
  • Uniop MD02R-04 - MD02R-04-0045 Industrial PLC Workstation
  • Uniop Cp02r-04-0021 Operating Interface
  • UniOP ECT-16-0045 High-Performance Color Touchscreen HMI
  • UniOP ERT-16 - Industrial PLC Workstation
  • UniOP ePAD04-0046 Compact Industrial Interface
  • UniOP BKDR-16 High-Reliability Monochrome Operator Interface
  • UniOP MKDR-04-004 Control Unit Panel
  • UniOP eTOP515 Series 500 HMI
  • Woodward 9907-1199 Advanced CPC-II Current-to-Pressure Converter
  • Woodward 8200-1300 High-Precision 505D Steam Turbine Controller
  • ABB PFSK130 3BSE002616R1 Core Signal Conditioning Unit
  • ABB PFSK165 3BSE027778R1 VP74201-933CW07 Signal Processing and Communication Unit
  • ABB PFSK164 3BSE021180R1 Tension sensor module and processing board
  • ABB 3BSE006505R1 PFSK142 Control board
  • ABB PFSK160A 3BSE009514R1 Regulated High-Capacity 24V DC
  • ABB PFSK162 3BSE015088R1 Signal Conditioning and Processing Board
  • ABB PFSK152 3BSE018877R1 Signal concentrator board
  • ABB PFSK151 3BSE018876R1 High-performance signal processing unit
  • ALSTOM PIB1201A 3BEC0067 Power Interface Board (PIB)
  • ALSTOM PIB310 3BHB0190 Adapter Module / Printed Circuit Board (PCB)
  • ALSTOM PIB102A 3BEB0180 Communication Card / PCB Module
  • ALSTOM BGTR8HE 24491276A1004 High-Frequency Power Controller / Rack Module
  • ALSTOM LC105A-1 Digital Discrete Output (Relay)
  • ALSTOM IR139-1 High-Efficiency Inverter / Control Board
  • ALSTOM AM164 Analog Output / Remote I/O
  • ALSTOM LE109A-1 Power System Control and Monitoring Module
  • ALSTOM UT150-1 PID temperature controller / process control board
  • ALSTOM AL132 AL132A STO0982E01 Control Motherboard / CPU Card
  • ALSTOM AS111-1 Analog Output (AO) Module
  • WATLOW AH116-2 Servo Drive / Control Module
  • WATLOW V4555724-0100 Electromechanical Contactor /Power Switch
  • Alstom KCEU142 Digital Protection Relay
  • ALSTOM MMLG01 Test block