Outputs
Three types of outputs (RELAY, SSR driver or DC linear) are selectable for three outputs, through the model selection guide or by adding a plug-in module for outputs 1, 2 and 3. Outputs Algorithm The UDC1200 and UDC1700 are available with the following output algorithms:
Time proportional: ON/OFF or time proportional with electromechanical relay SPDT 2 A or SSR driver (open collector).
Current proportional: Supply directly proportional current or voltage signal to the final control elements which require 0 20 mA, 4 20 mA, 0-10 V or 0-5 V.
Time proportional duplex: Three duplex modes can be selected, either ON/OFF duplex, time proportional duplex (heat/cool with two proportional bands, two cycle times and deadband) or TPSC.
Current proportional duplex: In addition to the first current/voltage output, a second similar output with its own proportional band is provided.
Current/Time or Time/Current duplex: Provides a variation of traditional time or current duplex mode by mixing current and time proportioning together.
Control Algorithms
Four control algorithms can be set up through the configuration menu: On/Off PD + MR PID TPSC The TPSC (Three Position Step Control) control algorithm is dedicated to control valve positioning without slidewire feedback from the motor shaft.
Configuration
There are two levels of configuration. The SET-UP mode allows modification of current parameters such as tuning parameters, alarm values, setpoint limit, ramp enable, auto-manual mode enable and auto pretune enable. The CONFIGURATION mode is more oriented to unit personality: input selection, output 2 and 3 usage, alarm type, communication address and lockout code. The operator mode screens are only selectable via the configuration software only. For instance, the alarm value screen can be moved from setup mode to normal operator mode if desired.
Control Mode
Manual or automatic mode with bumpless transfer is standard feature. In manual mode, the operator can directly control the output through the two front face keys (raise and lower keys). The output value is monitored on the lower display.
Alarms
Outputs 1, 2 and 3 can be used as alarms. Two electromechanical single pole double throw relays can activate external equipment when alarm setpoints are reached. An LED is also activated on the front-face. A direct or reverse acting alarm output can be configured. A logical combination of the two alarms: OR, AND or hysteresis (active when both alarms are active and inactive when both alarms are inactive) can be set which associates the two alarms status before energizing the relay. In order to detect a defective control loop, the controller can supply special loop alarm control by continually monitoring the PV response to output demand. A timer is automatically set up when any output is on saturation mode. When the timer reaches twice the reset time with no PV response, the loop alarm is activated. With this soft alarm there is no need for a heater circuit breaker, saving wiring time and costs.
Display
Dual, four-digit LED display with decimal point location configurable up to three places for linear ranges only.
Limit Controller
The UDC1200 1/16 DIN limit controller provides a latched relay output which is activated when the process parameters either exceed or fall bellow the desired value, providing a failsafe cut-off which has to be manually reset before the process can continue. The UDC1200 limit controller can be configured to be either a “high limit” unit where the delay will de-energize when the PV is above the limit setpoint, or a “low limit”, where the relay will drop out when the PV falls below the setpoint. A LED indicator shows when limits have been exceeded, and when the relay is latched out. The optional digital input allows a remote reset function.
Remote Setpoint Model
The UDC1700 1/8 DIN "R" model controller has a second input available that accepts either a linear or potentiometer input signal as a remote setpoint. The input signals accepted are field-configurable and are: 0-5 V, 1-5 V, 0-10 V, 2-10 V, 0-20 mA, 4-20 mA (factory set), 0-50 mV, 10-50 mV, 0 100 mV, or 0-2000 ohms. This allows the controller to act as a "slave" controller accepting a setpoint value from a 'master' device such as a PLC or setpoint-programming controller (such as the DCP50, DCP100, DCP300, or DCP550 series). The UDC1700R also includes a standard digital input allowing remote switching between the local setpoint and the remote setpoint value. Also standard in this model is "fuzzy" autotune software that minimizes process variable overshoot when responding to a setpoint change.
PC Software
The UDC1200 & 1700 are supported with PC software allowing you to quickly configure your device using configuration wizards, or to perform diagnostics.