Woodward: easYgen-3500XT (P1) 8440-2085
Product number: 8440-2085
Manufacturer product number: 8440-2085
Description: Woodward: easYgen-3500XT (P1), Genset Controller, 1A/5A,
Output Type/Preset Description
Relay output [R 01] Programmable
Fixed to "Ready for operation"
CAUTION! Only relay [R 01] has an
inverse logic. The relay opens (all other
relays close), if the logical output of the
LogicsManager becomes TRUE.
This discrete output is used to ensure that the internal functions
of the controller are operating properly.
It is possible to configure additional events, which cause the con
tacts of this discrete output to open, using the LogicsManager.
Relay output [R 02] Programmable
Preconfigured to "Centralized alarm (horn)"
When a centralized alarm is issued, this discrete output is ena
bled.
A horn or a buzzer maybe activated via this discrete output.
Pressing the button next to the "3" symbol will acknowledge the
centralized alarm and disable this discrete output.
The discrete output will re-enable if a new fault condition resulting
in a centralized alarm occurs. The centralized alarm is initiated by
class B alarms or higher.
Relay output [R 03] Programmable
Preconfigured to "Starter"
The generator starting circuit is engaged when this discrete
output is enabled.
This discrete output will enable depending on the start sequence
(refer to the start sequence description in Ä Chapter 4.5.9.1
“Engine Type” on page 219) to energize the starter for the config
ured starter time (parameter 3306 Ä p. 227).
Relay output [R 04] Programmable
Preconfigured to "Fuel solenoid / gas
valve"
Fuel solenoid
The fuel solenoid for the diesel engine is energized when this dis
crete output is enabled. If the engine is given a stop command or
engine speed drops below the configured firing speed, this dis
crete output is disabled immediately.
Gas valve
The gas valve for the engine is energized when this discrete
output is enabled. If the engine is given a stop command or
engine speed drops below the configured firing speed, this dis
crete output is disabled immediately.
Relay output [R 05] Fixed
Preconfigured to "Command: open MCB"
Only applicable for application mode .
The controller enables this discrete output when the MCB is to be
opened for switching operations.
If the discrete input "Reply MCB" is energized, the discrete output
"Command: open MCB" is disabled
Output Type/Preset Description
Relay output [R 06] Fixed
Preconfigured to "Command: close GCB"
Only applicable for application modes and .
The "Command: close GCB" output issues the signal for the GCB
to close. This relay may be configured as an impulse or constant
output signal depending on parameter 3414 Ä p. 194.
Impulse
If the output is configured as "Impulse", the discrete output will
enable for the time configured in parameter 3416 Ä p. 194). An
external holding coil and sealing contacts must be installed into
the GCB closing circuit if this discrete output is configured for an
impulse output signal.
Constant
If the relay is configured as "Constant", the relay will energize and
remain enabled as long as the discrete input "Reply GCB"
remains de-energized and the generator and busbar voltages are
identical. If a class C or higher alarm occurs, this discrete will dis
able and the GCB will open immediately.
Relay output [R 07] Fixed
Preconfigured to "Command: open GCB"
Not applicable for application mode
The parameter 3403 Ä p. 194 defines how this relay functions.
If this output is configured as "N.O.", the relay contacts close
resulting in the GCB opening circuit energizing.
If this output is configured as "N.C.", the relay contacts open
resulting in the GCB opening circuit de-energizing.
If the controller is configured for the breaker application "None",
this relay is freely configurable.
Application mode
The open GCB command remains enabled until the GCB is man
ually closed and the discrete input "Reply GCB" is energized. The
open GCB command will be issued when a fault condition or an
engine shut down occurs.
Application mode or
The controller enables the open GCB command when the GCB is
to be opened for switching operations. If the discrete input "Reply
GCB" is energized, the open GCB command will be disabled.
Relay output [R 08] Fixed
Preconfigured to "Command: close MCB"
Only applicable for application mode
The discrete output "Command: close MCB" is an impulse output
signal.
| ABB | TP854 |
| ABB | D2D146-AA28-28 |
| ABB | DSMB-02C |
| ABB | FS450R12KE3/AGDR-71C |
| ABB | PNI800 |
| ABB | CTB810,HN800 |
| ABB | PNI800 MB805 |
| ABB | DSAO120 |
| ABB | REA101-AAA |
| ABB | TB850 |
| ABB | DI810 |
| ABB | INSEM01 |
| ABB | PM645B |
| ABB | PFEA111-65 |
| ABB | DSQC355A |
| ABB | AI801 |
| ABB | AFC094AE02 |
| ABB | SPBRC400 |
| ABB | PPC380AE01 |
| ABB | 3HAC026271-001/DSQC646 |
This discrete output is enabled for the time configured in param
eter 3417 Ä p. 197.
An external holding coil and sealing contacts must be utilized with
the MCB closing circuit.
Relay output [R 09] Programmable
Preconfigured to "Stop solenoid"
Only applicable for application mode .
Inverted function of Fuel solenoid / gas valve (preconfigured [R4])
Relay output [R 10] Programmable
Preconfigured to "Auxiliary services"
The auxiliary services output (LogicsManager 03.01) will be ena
bled with the start command (prior to the engine start because of
the prerun time) and remains enabled as long as the engine is
running.
It w
Configure Monitoring
4.4.1 Generator
ID Parameter CL Setting range
[Default]
Description
1770 Generator
voltage moni
toring
2 The unit can either monitor the phase-neutral (wye) voltages or the phase
phase (delta) voltages.
If the controller is used in a compensated or isolated network, voltage protec
tion monitoring should be configured as phase-neutral to prevent earth-faults
resulting in tripping of the voltage protections.
[Phase
phase]
The phase-phase voltage will be monitored and all subsequent parameters
concerning voltage monitoring "generator" are referred to this value (VL-L).
Phase - neutral The phase-neutral voltage will be monitored and all subsequent parameters
concerning voltage monitoring "generator" are referred to this value (VL-N).
Notes
WARNING: This parameter defines how the protective functions operate