GE IS200VGENH1B Generator monitor and jump gate
Part number IS200VGENH1B manufacturer general electric company manufacturing country conforms to general electric company manufacturing policy series Mark VI function module off-the-shelf availability 200 vgx indi b is a generator monitor and jump gate manufactured and designed by general electric company as a part of Mark VI series used in gas turbine control system. The generator board VGEN and its terminal board TGEN track the voltage and current of three phases of the generator, and calculate its power and power factor.
VGEN uses a fast-acting solenoid located on the TRLY terminal board to perform power load imbalance (PLU) and early valve actuation (EVA) tasks for large steam turbine applications. IS200VGB before installing the VGEN board, please turn off the power of the VME I/O processor rack. To install the edge connection on the VGEN board, slide it in and push the top and bottom tie rods by hand.
Next, tighten the self-retaining screws at the top and bottom of the front panel. These screws improve the integrity of the front grounding of the circuit board and are used to firmly fix the circuit board in place. Screws should not be used to fix circuit boards. JBOY3 connector in the lower part of VME rack is used to connect cables to TGEN terminal board. In order to fix the cable in place, this connector will lock. J4 connector on the lower part of VME rack is used to connect cables to optional TRLY terminal board. In order to fix the cable in place, this connector will lock. Open the VME rack and check the diagnostic light at the top of the front panel. VGEN monitors the operation of three single-phase CT inputs and two three-phase PT inputs. There are four analog inputs on TGEN, which can be set to 4-20 mA or 5, 10 or 20 V dc. VGEN board converts signals and calculates frequency, power and power factor. VGEN provides early valve drive (EVA) and power load imbalance (PLU) functions for large steam turbines, and monitors the three-phase power of generators. All three line-to-line voltages are calculated using three-wire, open triangle voltage measurements from generator and bus PT inputs. They are not used for automatic synchronization, which requires the use of two different single-phase PT inputs. PT is magnetically isolated, and the nominal voltage of each PT input is 115 V RMS. All PT and CT inputs have test points to realize field verification of phase.
Three single-phase CT inputs are provided, and the standard continuous current range of each input is 0 to 5 A. On TGEN, CT is magnetically isolated. The terminal of CTs consists of a non-pluggable wiring board with tethered lugs, which can accommodate wires up to 10 AWG. These inputs are used to determine the following parameters: total Mwatts total Mvars total MVA power factor bus frequency (5 to 66 Hz) Four analog inputs can accept 4-20 mA or 5, 10 or 15 V DC inputs. All four circuits can be connected to the +24 V DC power supply, and each circuit has its own current limit.
The +24 V DC power supply of the turbine controller or self-powered power supply can be connected to the 4-20 mA sensor. On the terminal board, jumpers allow you to choose between the current and voltage inputs of each circuit. IS200VGB Diagnostic VGEN Three LEDs at the top of the front panel display status data. A steady red color indicates failure, while a flashing green color indicates normal operation. The third LED indicating status is usually off, but it will continue to blink orange if there is a diagnostic alarm problem on the motherboard. The following is a list of VGEN diagnostics: Perform high/low system (software) limit check and high/low input signal (hardware) limit check through diagnostics. In the field, you can modify the software restriction check. For voltage input, open circuit detection is provided, and relay driver and coil current are also tracked. I/O board inquires about connectors JR1, JS1 and JT1 on the terminal board, and each connector has its own ID device. The terminal board serial number, board type, revision number and plug position are all encoded on a read-only chip called ID device. VME generator
Related models
DS200SHVMG1AFE
IC660ELB912
IS230TVBAH2A
IS215VCMIH2BB IS200VCMIH2BCC
IS210MACCH1AGG
SR489-P5-LO-A20-E
MVR1600-4601
D20 EME 2400-21004
IC697MDL350
8101-HI-TX-02
IC698PSA100
IC698RMX016-ED
IC660BBD025
531X303MCPARG1
DS200FSAAG1ABA