ABB 3HAC5497-1
Important
All control parameters are determined in an optimum way for most actuators during Autoadjust.
Changes should only be made when Autoadjust cannot be executed or control stability cannot be achieved.
The KP value is the gain of the controller. The control speed and stability are influenced by the KP value. With higher KP values, the controlling speed increases.
Important
The control precision is not affected by the KP value.
To compensate for existing dissymmetries in the controlled system, the KP value should be set separately for both directions (up / down).
For most actuators, a satisfactory control response is achieved with a KP value in the 2.0 ... 10.0 range.
You can use parameter KP UP to adjust the KP value for the positioning direction up (towards 100 %).
3BSE089152R0059