Either module may be replaced without upsetting field input or output signals to the
good module. The module can be removed/replaced without removing field device
termination cabling, power, or communications cabling.
Light-emitting diodes (LEDs) incorporated into the front of the module provide visual
indications of the module’s operational status.
Standard Design
FBM208/208b has a rugged extruded aluminum exterior for physical protection of the
circuits. Enclosures specially designed for mounting the FBMs provide various levels
of environmental protection, up to harsh environments.
Fieldbus Communication
The Fieldbus Communications Module (FCM) or the Field Control Processor (FCP)
interfaces to the redundant 2 Mbps module Fieldbus used by the FBMs. The FBM208/
208b accepts communication from either path (A or B) of the 2 Mbps Fieldbus. If one
path is unsuccessful or is switched at the system level, the module continues
communication over the active path.
Modular Baseplate Mounting
The FBM208module mounts on aDIN rail mounted modular baseplate, which
accommodates up to four or eight FBMs. The FBM208b module also mounts on
conversion mounting structures. See 100 Series Conversion Mounting Structures
(PSS 41H-2W8).
Redundant modules must be located in adjacent positions on the baseplate, with the
first module located in an odd-numbered position (for example, the positions labelled
"3" and "4"). To achieve redundancy, a redundant adapter module is placed on the two
adjacent baseplate termination cable connectors to provide termination for a single
cable (see Figure 1. page 4). A single termination cable connects from the redundant
adapter to the associated termination assembly (TA).
Easy Removal/Replacement
Whenredundant, either module may be replaced without upsetting field input signals
to the good module. Each module can be removed/replaced without removing field
termination cabling, power, or communications cabling.
Redundant Modules in Foxboro DCS HMI
To system configurator applications and to other systems monitoring through SMON,
Foxboro DCS System Manager, and SMDH, redundant FBM208/208bs appear to be
separate, nonredundant modules. The functional redundancy for these modules is
provided by their associated control blocks.
Termination Assemblies
Field I/O signals for the FBM208 connect to the FBM subsystem via DIN rail mounted
termination assemblies (TAs). The TAs used with the FBM208 are described in
Termination Assemblies And Cables, page 13.
For field I/O signals for the FBM208b, see Use of Termination Assemblies in 100
Series Upgrade Subsystem, page 15.
Termination Assemblies And Cables
The FBM208field I/O signals connect to the FBM subsystem via DIN rail mounted
Termination Assemblies (TAs).
The redundant adapter connects the redundant FBMs baseplate input/output
connectors together. The redundant adapter provides a single termination connection
to a single TA (see Figure 1. page 4).
TAs are available in these materials:
• Polyamide (PA) material
The DIN rail mounted TAs connect to the redundant adapter by means of a removable
termination cable. The cable is available in a variety of lengths, up to 30 meters (98
feet), allowing the TA to be mounted in either the enclosure or in an adjacent
enclosure. Termination cables are available in these materials: