Honeywell CC-IP0101 DP Gateway Module DP-2 51410056-175
Instructions
Parameter Specification
Input / Output Model CC-PAIX02 - High-Level Analog Input
IOTA Models Non-Redundant Redundant
CC-TAIX01 CC-TAIX11
CC-GAIX21 CC-GAIX11
CC-TAID01 CC-TAID11
The Analog Input Module accepts high level current input from sensing devices.
Notable Features
• Extensive self-diagnostics
• Optional redundancy
• Supplies non-incendive field power
• Fast loop scan
Non-Incendive Power
Non-incendive power is provided with no external marshalling to support the 4-20mA loop and still provide for channel
power protection. This protection supports the Division 2 hazardous protection non-incendive power rating.
Detail Specifications –Analog Input
Parameter Specification
Input / Output Model CC-PAIN01 - High-Level Analog Input
IOTA Models CC-TAIN01 Non Redundant 6”
CC-TAIN11 Redundant 12”
Input Type Current (2-wire or self-powered transmitters)
Input Channels 16 Channels (16 Single Ended)Common Mode Rejection Ratio, dc to 60 Hz (500 source imbalance)70 dB A/D Converter Resolution 16 bits
Input Range 4-20 mA (through 200 Ω)
Normal Mode Rejection Ratio, at 60 Hz 20 dB
Normal Mode Filter Response Single-pole RC, -3 dB @ 6.0 Hz
Maximum Normal Mode Input ± 30 Volts
Crosstalk, dc to 60 Hz (channel-to-channel) -60 dB
Input Scan Rate 50 ms
Hardware Accuracy (@ CMV = 0 V) ± 0.075% of full-scale (23.5°± 2°C)
± 0.15% of full-scale (0 to 60°C)
Transmitter Field Power Conditioning Individually Protected Current Limiting Circuits for Class 1,
Div 2 non-incendive interfacing. No fusing required
Function The LLMUX IOP module supports up to 64 channels of temperature inputs. Low level inputs use the Honeywell PMIO LLMUX FTA. Each FTA supports 16 channels. Two types of LLMUX FTA are supported. One provides 16 RTD inputs. The other provides 16 TC or MV inputs. Any combination of FTAs may be used to provide the mix of TC, mV or RTD points required. Notable Features • TC and RTD operation • Remote cold junction capability • 1 Second PV scanning with OTD protection • Configurable OTD protection (See below) • Temperature points can be added in 16 point increments Temperature Support The Temperature Input LLMUX supports the existing solid state PMIO LLMUX FTA. The PMIO LLMUX FTA supports RTD and Thermocouple (TC) inputs. The Temperature variable is collected from all points at a 1 second rate. The 1 second update includes a configurable check for Open Thermocouple Detection (OTD) (see below) before propagation of the temperature variable. All TC inputs are compensated using a Cold Junction Compensation (CJT) device. Sampling and Open Sensor Detect The Temperature multiplexer supports RTD and Thermocouples with Open Sensor Detect before PV delivered if so configured. With the OTD configuration active, the PV is sampled and held while an OTD cycle is performed within the same measurement window. If the OTD is negative, the PV is propagated up through the system. If the OTD is positive, the PV is set to NAN and the input channel soft failure is set. In this way, no inappropriate control action occurs for PV values that are invalid due to an open thermocouple. PV sampling/reporting incurs no added delays from OTD processing.
Function
The Pulse Input Module (PIM) provides the Experion C300 controller with the ability to monitor various pulse input field
values. The PI module processes signals from pulse-generating devices and provides a calculated rate and an
accumulated total. The PI supports a “fast cutoff” capability to stop dosing operations when the threshold has been met.
High-accuracy and repeatable measurement capability make the PIM well suited for metering and custody transfer
applications.
This module is specifically engineered to support the MeterSuite Custody Transfer Application including support for dual
pulse per ISO6551. Implementation of ISO-6551/API 5.5 for dual pulse inputs, including Level A, pulse integrity.
Notable Features
• Extensive self-diagnostics
• Optional redundancy
• High Accuracy Frequency, Period and Pulse Width
Measurement
• Supports the MeterSuite Application
• ISO 6551 Fidelity
The Analog Output (AO) Module delivers high-level constant current to actuators and recording/indicating devices. Notable Features • Extensive self-diagnostics
• Optional redundancy
• HART-capable, multivariable instruments
• Multiple modems for fast collection of control variables
• Safe-state (FAILOPT) behaviors configurable on a per channel basis
• Output read-back and alarm on discrepancy
• Non-incendive output FAILOPT Series C AO module supports the FAILOPT parameter on a per channel basis. The user can configure each channel to either HOLD LAST VALUE, or SHED to a SAFE VALUE. The Output will always go to zero, the safe state, if the IOM device electronics fails. Open-wire Detection This Series C IO function will be able to detect and annunciate open field wire with a Channel Soft Failure indication.
About Xiamen kongjiang automation technology co., ltd:
Xiamen kongjiang automation technology co., ltd is a technology-based entity company established on may 11th, 2017, located in Xiamen, Fujian province. The company is mainly engaged in the sales of imported industrial control parts, electrical engineering design, installation, programming, debugging, construction and other businesses. The company has an experienced and well-trained technical team, which is committed to providing customers with services such as electrical automation system development, automatic upgrading and transformation of the original production line, energy-saving transformation and production of complete sets of electric control cabinets.
Add: Building F05, High-tech Software Park, Xiamen City, Fujian Province
Tel: 0592-5211302
Mobile: 17750019513 (WhatsApp)
Email: yy4291644@gmail.com
ivy@kongjiangauto.com
Website: https://www.abb-sis.com