UNITROL 1010 3BHE035301R1002 UNS 0121A-Z,V1 UN1010-0001 ABBcontrol unit
Obey these safety precautions before you do work on the system:
Clearly identify the work location and equipment.
2. Disconnect all possible voltage sources. Make sure that reconnection is not possible. Lock out and tag out.
• Open the main disconnecting device of the AVR.
• Disconnect any external power sources from the control circuits before you do work on the control cables.
• If you have a permanent magnet generator connected to the AVR, disconnect it from the AVR with a safety switch or by other means.
• After you disconnect the AVR, always wait for 5 minutes to let the intermediate circuit capacitors discharge before you continue.
• Do not do work on the AVR when the amber warning LED flashes. 3. Protect any other energized parts in the work location against contact. 4. Take special precautions when you are near bare conductors. 5. Measure that the installation is de-energized.
• Use a multimeter with an impedance of at least 1 Mohm.
• Make sure that the voltage between the AVR input power terminals (PWR L1, PWR L2 and PWR L3) and the grounding terminal (PE) is near 0 V.
• Make sure that the voltage between the AVR output terminals (IE+, IEand ExCap) and the grounding terminal (PE) is close to 0 V. 6. Install temporary grounding as required by the local regulations. 7. Ask for a permit to work from the person in control of the electrical installation work. Residual danger areas WARNING! Do not do work on the AVR when the amber warning LED flashes. When the AVR operates,
• The voltage in the power section can be up to 300 V AC and the short-circuit current is very high.
• The voltage in the control cabinet is more than 50 V. When the AVR is disconnected from power supplies, the large capacitors in the AVR hold a charge for some time. Wait for at least 5 minutes for the capacitors to discharge before you do work on the AVR. An amber warning LED flashes if the internal voltage is more than 30 V DC. Warning labels are attached to all of the cubicle doors to warn personnel against opening the doors during operation. If the device is built into a larger system, additional warning labels are attached to the inside of the cubicle doors and to the covers of the power converter modules. Consider the residual danger areas when you do work on the excitation system:
• Danger from live equipment inside the excitation system, if the protective covers are removed.
• Hazardous voltages from the rotor field winding and the secondary side of the excitation transformer.
• Danger from charged capacitors if a cabinet door is open immediately after the system stops.
• Danger from main and auxiliary voltages when cubicle doors are open. Introduction This document is a quick installation guide for the UNITROL 1010 and UNITROL 1020 automatic voltage regulator. Make sure that you read and understand this document before you install or use the product. This document is meant only as a brief guide to the product. For detailed information on the product, refer to the User Manual. Device description UNITROL 1010 and UNITROL 1020 are automatic voltage regulators (AVR) for synchronous machines of up to 80 MVA. The AVRs can be used for the excitation of indirectly excited synchronous machines and motors. The AVRs can also operate as a reactive power regulators, power factor regulators or field current regulators. Product package Contents of the product package:
• UNITROL 1000 series AVR
• Special red USB cable that is used to power and to connect with the AVR. Keep this USB cable in a safe place.
• Red jumper blocks (3 pcs.)
• Quick installation guide and test certificate Make sure that all of the listed items are in the product package and that there is no damage to the items. Hardware overview Primary parts of the AVR. Refer to the User Manual for more information. Warning and status indicators Mechanical installation For detailed information on mechanical installation, refer to the User Manual. Install the AVR in an indoor area that is dry and dust-free, and that does not contain volatile gases, acid fumes or similar hazards. Examine the installation area and refer to technical data to make sure that:
• The maximum ambient temperature is in the permitted range.
• The vibration is limited and within the permitted class.
• The ingress protection and pollution degree are suitable.
• The EMC environment is suitable. Installation requirements:
• Install the AVR vertically to make sure that cooling operates correctly.
• Free space requirements:
• 50 mm above the AVR
• 20 mm below the AVR
• 10 mm on the left and right sides of the AVR
• Make sure that there is sufficient cooling air flow around the AVR.
• Make sure that other devices do not blow hot air on to the AVR.
• The AVR is designed to be installed with suitable hardware to an installation plate.
• Make sure that the frame of the AVR is electrically grounded (PE) to the installation plate with a grounding wire (≥4 mm2) through a mounting hole. Use toothed washers to get a good electrical ground contact. Installation procedure: 1. Refer to Dimensions for the mounting hole dimensions. 2. Make the appropriate holes in the installation plate. 3. Attach the AVR to the installation plate with suitable hardware, for example, M6 screws to a torque of 10 Nm. The mounting holes have a diameter of 6.5 mm. 4. Make sure that there is a good electrical ground connection between the installation plate and the AVR.