Woodward-Service Bulletin 01671

From:Woodward | Author:kongjiang | Time :2026-03-03 | 302 Browse: | 🔊 Click to read aloud ❚❚ | Share:

Service Bulletin 01671

ProTech GII, TPS, and MSM

User Configuration Guidance

Issue

ProTech GII, TPS, and MSM controls support a variety of configuration options. When using

Active speed probe sensors, certain configurations could lead to a lapse in overspeed protection,

if multiple faults occur in the system comprised of the ProTech, field wiring and speed sensors.

Description

The ProTech GII, TPS and MSM are fault tolerant safety control devices that are fully configured

by customers for each unique site application.  These products have many functional options

available and the system is designed to continually provide its primary function, even when one

fault occurs anywhere in the ProTech system.

It has come to our attention that some user configurations of these products, may not react as

expected when a second fault occurs in the ProTech system.

These safety products are all configurable by the user, so it is important to emphasize the

following points:

• On any configurable device – it is possible to have a valid configuration that may not do all

that is expected, verification of customer and installers requirements and unit testing at site

commissioning is required to ensure the appropriate response to faults in the system.

• On any fault tolerant system, a single fault should be investigated and addressed.  Depending

on the configuration, running the system in a prolonged mode with an active alarm, leaves it

in a state where a second fault could cause a trip or prevent the unit from performing its

primary function.

If your configuration settings utilize one of the following features, this Service Bulletin can be

disregarded:

1. Probe Type: PASSIVE (such as MPU’s)

2. Speed Fail Trip: USED

If your configuration settings are using Active probes (not MPU’s) and your configuration has Speed Fail Trip

set to “NOT USED” follow the instructions in the Corrective Action section below.

All units shipped with the following part numbers:

GII

TPS

MSM

8237-1244 8237-1248 8237-1252

8237-1245 8237-1249 8237-1253

8237-1246 8237-1250 8237-1254

8237-1247 8237-1251 8237-1255

8237-1367 8237-1371 8237-1375

8237-1368 8237-1372 8237-1376

8237-1369 8237-1373 8237-1377

8237-1370 8237-1374 8237-1378

8237-1594 8237-1602 8237-1492

8237-1595 8237-1603 8237-1493

8237-1596 8237-1604 8237-1494

8237-1597 8237-1605 8237-1495

8237-1598 8237-1606 8237-1496

8237-1599 8237-1607 8237-1497

8237-1600 8237-1608 8237-1498

8237-1601 8237-1609 8237-1499

8237-1660 8237-2602 8237-2492

8237-2594 8237-2603 8237-2493

8237-2595 8237-2604 8237-2494

8237-2596 8237-2605 8237-2495

8237-2597 8237-2606 8237-2496

8237-2598 8237-2607 8237-2497

8237-2599 8237-2608 8237-2498

8237-2600 8237-2609 8237-2499

8237-2601 8237-2614

Potentially affected ProTech units may have also shipped as sub-components of other Woodward

cabinets, kits and systems. Specific customer sales order details are provided by the appropriate

Woodward Customer Service Representative.

If you are currently using configurations described above then at your earliest convenience, plan

to modify your unit configuration with the following recommendations.

It is recommended that on ProTech GII products, the option Speed Fail Trip always be set to

“USED” whenever the configuration of the speed input probe type is “Active”.

It is recommended that on ProTech TPS or MSM products, the option Speed Fail Trip always be

set to “Used” whenever the configuration of the speed input probe type is “Active”. If this is not

desired, due to a need to have other Safety Instrumented Functions (SIF) protected in all 3

kernels, then use the “Speed Redundancy Management” option and configure both “Base

Function” and “Fallback Function” to be HSS.

To review their ProTech configuration and compare it with the information in this bulletin to see if

any of these potential problem conditions are possible.

We suggest that customers with units that are currently in operation, to verify that they are not

running with active module alarm conditions that could lead to a potential issue.



  • ADLINK Multi-Function DAQ cPCI-9116
  • ADLINK 3U CompactPCI Blades CT-3620
  • ADLINK 3U CompactPCI Blades cPCI-3620
  • ADLINK 3U CompactPCI Blades cPCI-3620
  • ADLINK 3U CompactPCI Blades cPCI-3630
  • ADLINK 3U CompactPCI Blades cPCI-3640 Series
  • 3U CompactPCI Blades cPCI-3520 Series
  • ADLINK IMB-M42H ATX Motherboards
  • Adlink PCIe-GIE74 /PCIe-GIE74V Frame Grabbers / Video Capture Cards
  • ADLINK USB-1605 Removable screw terminal blocks or high-density D-Sub
  • Adlink ETX-NR667-L7400/LXE ETX Module
  • ADLINK NuPRO-842LV/P industrial control motherboard
  • ADLINK cPCI-8994 Serial Communication
  • ADLINK / PCI-7432 Digital I/O
  • ADLINK IEC-915GV Compact industrial-grade fanless embedded system
  • ADLINK ADLINK, PLX / PCI-7296 Digital I/O
  • ADLINK HPCI-14S12U 0040 Backplane Selection Guide
  • ADLINK MXE-5500 /MXE-5501/M16G (G) Fanless Embedded Computer
  • Adlink Multi-Function DAQ PCI-9112
  • ADLINK NuPRO-852LV Control Board
  • ADLINK CompactPCI cPCI-7432R Digital I/O Module
  • ADLINK NUPRO-E320LV PICMG Single Board Computers
  • ADLINK PICMG Single Board Computers NuPRO-E72
  • ADLINK PICMG Single Board Computers NuPRO-865
  • Vibro-Meter Rack VM600SYSMK2-ABE04x 6U 19-inch rack Mk2 system
  • Vibro-Meter Relay expansion RLC16 Mk2 SIL2 (single card) 600-044L
  • Vibro-Meter Relay expansion RLC16 Mk2 SIL2 600-04
  • Vibro-Meter Relay expansion RLC16 Mk2 600-045L
  • Vibro-Meter Relay expansion RLC16 Mk2 600-045
  • Vibro-Meter I/O interface card  IOCN Mk2    600-051
  • Vibro-Meter CPU controller   CPUM Mk2  600-050
  • Vibro-Meter I/O interface card    IOC10 Mk2 (rear card)    600-046
  • Vibro-Meter Temperature / Analog Acquisition  AMC10 Mk2  600-042
  • Vibro-Meter I/O interface card IOC4 Mk2 600-043
  • Vibro-Meter Protective measuring card MPC4 Mk2 SIL2 601-041-A10
  • Vibro-Meter Protective measuring card MPC4 Mk2 601-041-A0
  • Vibro-Meter PSU-VM600 VM600 Rack Power Module
  • Vibro-Meter ABE056 - 1U ultra-thin single-rack
  • Vibro-Meter ABE046 - 6U 19-inch rack
  • Vibro-Meter ABE045 - 6U 19-inch rack
  • Vibro-Meter ABE044 - 6U 19-inch rack (with expansion slots)
  • Vibro-Meter ABE042 6U 19-inch rack (4 slots)
  • Vibro-Meter I/O interface card XIO16T
  • Vibro-Meter XMC16 16-channel combustion monitoring card
  • Vibro-Meter XMV16 - 16-channel vibration condition monitoring card
  • Vibro-Meter RLC16 Relay Card
  • Vibro-Meter IRC4 Intelligent Relay Card
  • Vibro-Meter IOCR2 input/output rear interface card
  • Vibro-Meter CPUR2 Central Processing and Controller Card
  • Vibro-Meter I/O interface card  -  IOCR
  • VIBRO-METER CPU controller CPUR
  • VIBRO-METER IOCN 200-585-000-322 I/O interface card
  • VIBRO-METER IOCN 200-585-000-321 I/O Interface Card
  • VIBRO-METER 200-595-074-323 VM600 system CPU management card, non-redundant
  • VIBRO-METER CPUM 200-595-074-322 CPU Controller
  • VIBRO-METER CPU controller CPUM 200-595-070-321
  • Vibro-Meter IOC8T VM600 Mk1 I/O Interface Card
  • Vibro-Meter AMC8 Analog Monitoring Card
  • VIBRO-METER IOC4G2 I/O interface card
  • VIBRO-METER MPC4G2 Protective measuring card
  • VIBRO-METER IOC4T 200-560-101-017 VM600 Mk1 Isolated I/O Interface Card, equipped with MPC4
  • VIBRO-METER IOC4T 200-560-101-015 VM600 Mk1 interface card
  • VIBRO-METER IOC4T 200-560-000-114 I/O interface card
  • VIBRO-METER IOC4T 200-560-000-113 I/O interface card
  • VIBRO-METER IOC4T 200-560-000-111 Sensor wiring
  • VIBRO-METER MPC4 200-510-072-212 Protection Measurement Card
  • VIBRO-METER MPC4 200-510-071-114 Protective Measurement Card
  • VIBRO-METER 200-510-071-111 4-channel vibration protection + 2-speed channels
  • VIBRO-METER 200-510-070-111 4-channel vibration protection + 2-speed channels
  • ADLINK PICMG Single Board Computers NuPRO-E315
  • ADLINK High Speed Link (HSL) PCI-7853
  • ADLINK Digital I/O PCIe-7432
  • ADLINK Mini-ITX Embedded Boards AmITX-AL-I
  • ADLINK 6U CompactPCI 2.0 Blades cPCI-6860A
  • ADLINK NuPRO-900A PICMG Single Board Computers
  • ADLINK Analog Output PCI-6308 Series
  • ADLINK USB DAQ USB-2405
  • ADLINK CRR-LX800-E-500 Compact Industrial Computer Module (COM)
  • ADLINK 15-slot 6U PXI/CompactPCI Chassis with AC PXIS-3320
  • ADLINK NUPRO-842 PICMG Single Board Computers
  • ADLINK PCI-8124-C Advanced 4-CH Encoder Card
  • ADLINK PCI-8102 Centralized Motion Controllers PCI-8102
  • ADLINK PCIe-7200 High-Speed DIO
  • SEL SEL-7201 Feeder Protection Panel
  • SEL SEL-7206 Distribution Bus Differential Protection Panel
  • SEL SEL-4388 Mirrored Bits Tester
  • SEL SEL-T4287 Traveling-Wave Test System
  • SEL SEL-4000 Relay Test System
  • SEL SEL-9510 Control Switch Module
  • SEL SEL-9502 Contact Arc Suppressor
  • SEL SEL-9501 Contact Arc Suppressor
  • SEL SEL-2652 Trip Coil Monitor
  • SEL SEL-2894 Interface Converter
  • SEL SEL-2890 Ethernet Transceiver
  • SEL SEL-2886 EIA-232 to EIA-485 Interface Converter
  • SEL SEL-9220 Fiber-Optic Adapter for SEL-300 Series Relays
  • SEL SEL-2824 Multimode Fiber-Optic EIA-485 Transceivers
  • SEL SEL-2820 Multimode Fiber-Optic EIA-485 Transceivers
  • SEL SEL-2815 Fiber-Optic Transceiver/Modem
  • SEL SEL-2814 Fiber-Optic Transceivers With Hardware Flow Control
  • SEL SEL-2812 Fiber-Optic Transceivers With IRIG-B
  • SEL SEL-2810 Fiber-Optic Transceivers With IRIG-B
  • SEL SEL-2831 Single-Mode Fiber-Optic Transceiver/Modem
  • SEL SEL-2830 Single-Mode Fiber-Optic Transceiver/Modem
  • SEL SEL-2829 Single-Mode Fiber-Optic Transceiver/Modem
  • SEL SEL-C805 200 µm Multimode Fiber-Optic Cable
  • SEL SEL-C804 Multimode Arc-Flash Detection Fiber-Optic Cables
  • SEL SEL-9331 Power Supply
  • SEL SEL-9322 15 VDC Power Supply
  • SEL SEL-9321 Low-Voltage DC Power Supply
  • SEL SEL-LPS Linear Power Supply
  • SEL SEL-RPM Redundant Power Module
  • SEL SEL-7250 Digital Direct-Replacement Assemblies
  • SEL SEL-2533 Annunciator
  • SEL SEL-2523 Annunciator Panel
  • SEL SEL-2522 Alarm Panel
  • SEL SEL-2516 Rack-Mount Remote I/O Module
  • SEL SEL-2515 Remote I/O Module
  • SEL SEL-2507 High-Speed Remote I/O Module
  • SEL SEL-2506 Rack-Mount Remote I/O Module
  • SEL SEL-2505 Remote I/O Module
  • SEL SEL-3401 Digital Clock
  • SEL SEL-9929 Satellite-Synchronized Clock Display Kit
  • SEL SEL-3405 High-Accuracy IRIG-B Fiber-Optic Transceiver
  • SEL SEL-3400 IRIG-B Distribution Module
  • SEL SEL-2401 Satellite-Synchronized Cloc
  • SEL SEL-2407 Satellite-Synchronized Clock
  • SEL SEL-2488 Satellite-Synchronized Network Clock