Woodward ESDR 4 Current Differential Protection Relay

From:Woodward | Author:kongjiang | Time :2026-01-20 | 176 Browse: | Share:

ESDR 4

Current Differential Protection Relay

The ESDR 4 is a three-phase current differential protection relay for generators and motors (protected object).

The currents flowing in the individual lines are each measured using a current transformer on both sides of the

protected object. They form the protection area boundary or zone. All two or three-phase short circuits and line

to-earth faults within this protection area are detected by the ESDR 4 as fault currents which initiate tripping.The

unit does not trip if fault currents occur outside the protection zone. In this way, a selective protection is guaran

teed.

The unit monitors six (6) measured currents via isolated inputs. The unit calculates internally the restraint current

(Is) and the differential current (Id) separately for each phase. The actual values of the calculated parameters (Dif

ferential current Id und Restraint current IS) are shown on the display either as absolute values or as a percentage

of the generator rated current (selectable in locked input mode).

Theoretically the currents Ia and Ib are equal, both in fault-free operation and outside the protection zone (Figure

4-1-a).The difference is zero and the differential protection does not initiate. However, in practice current differ

entials do occur (= spurious currents), even in fault-free operation. They result, for example, from summation or

phase angle errors in the CTs, which are influenced by deviating burden values. These spurious currents remain

small inside the operating range, but increase with increasing load and are especially high when one or more CTs

become saturated (e.g. in the case of an external short circuit). In order to prevent a tripping of the relay due to

spurious currents, the trigger threshold is not held statically constant but increases in relation to the restraint cur

rent Is.  Spurious currents need to be taken into account when adjusting the trip characteristic.

When a fault occurs inside the protection area (Figure 4-1-b), unequal currents flow in the CTs, which result in a

current differential. If this exceeds the differential protection threshold, the relay will trip.

Monitoring of the Differential Current

The monitoring of the differential current is carried out in two stages..

The first monitoring level serves as a warning and can be enabled or disabled. Should the adjustable warning

characteristic be exceeded, a text appears in the display and a relay contact is enabled. The pick-up time and the

dropout delay of the relay output are adjustable. The warning stage of the monitoring is auto-resetting.

The second stage of monitoring (main stage) serves to initiate tripping. In contrast to the first stage, it offers the

possibility to monitor the overstepping of an adjustable tripping characteristic (Id < In) and additionally, a fixed

tripping-threshold of 100%, relative to the generator rated current (Id > In). The trigger-delay for each limit value

may be independently adjusted, thus allowing a shorter triggering time at higher differential currents. When one

or both tripping characteristics are exceeded, a text display is initiated and two relay contacts are energized. The

tripping characteristics possess a 2% hysterisis relative to the generator rated current. .

The signal relay is only automatically reset if the function "automatic reset relay" in the Entry field on the screen

is configured to "on". Otherwise, the resetting is carried out by pressing the "Clear" button on the front of the

unit or via the discrete input terminal 18 "reset".

The two monitoring levels can also be used to change the characteristics of the control function (stage 1: small

value and a long time; stage 2: high value and a short time)

Tripping Characteristic

The following figure shows the tripping and warning characteristics (with sample values for X12. Y1.and Y2). It

represents the tripping and warning thresholds (Y) relative to the restraint current (X) The positions of the corner

points are determined by the coordinates P (X12/Y2) and P (X12/Y1). The selection of these positions is depend

ent on the generator being protected. The following gives the ranges of tripping and warning thresholds:

IS / IN

IS / IN

IS / IN

0 to X12

X12 to 5 × IN

> 5 × IN

The threshold Id is independent of the restraint current..

The threshold Id is dependent on the restraint current. A change of 100% in the

restraint current causes an increase of 10% in the tripping threshold.

The threshold Id stays constant at 85%.

Different characteristics can be chosen for the first and second monitoring levels, whereby the horizontal position

(X-coordinate) is valid for both stages. The vertical position (Y-coordinate) can be chosen separately for each

monitoring level. This results in a fixed difference in thresholds of the first and second monitioring levels for

each restraint current Is.

Control Inputs

Configuration

Terminal 17

Acknowledgement

Terminal 18

Blocking

Terminal19

Relays

Tripping (relay 1)

Terminals 1/2/3

Tripping (relay 2)

Terminals 4/5/6

Warning (relay 4)

Terminals 11/12/13

Ready for operation

(relay 3)

Terminals 7/8

When this input is energized, the unit locks into Configuration mode and stays in this

mode until the terminal is de-energized.

If this input remains energized for at least 1 s, the faults detected in monitoring

level 2 are reset. This means that the relays will be de-energized and the text display

will be deleted from the screen as long as the monitored currents are not exceeding

the configured threshold level.

When this input is energized, the differential protection is disabled.This means that

the differential current is not monitored, no relay can be enabled and no text is dis

played.

This relay becomes enabled when the unit detects threshold limit 2 (main stage) has

been exceeded. The configured differential current characteristics and delay time will

determine how relay 1 functions.

This relay becomes enabled when the unit detects threshold limit 2 (main stage) has

been exceeded. The configured differential current characteristics and delay time will

determine how relay 2 functions.

This relay becomes enabled when the unit detects threshold limit 1 has been ex

ceeded. The configured differential current characteristics and delay time will deter

mine how relay 4 functions.

This relay is enabled when the unit is operational and the differential current is being

monitored. The relay becomes disabled if the monitoring is deactivated through any

of the following reasons:

• the internal self-monitoring has detected a malfunction of the unit. A correct func

tioning of the unit cannot be guaranteed and corrective action may be necessary.

• the set values for parameter "CT-ratio" or parameter "Generator Current" are out

side the permissible limits (see page 19).

• the digital input "Blocking" is energized.

• the parameter "Monitoring" is configured to "Off".

When in configuration mode (simultaneous pressing of "Digit↑" and "Cursor→"), the configuration screen can

be advanced by pressing the "Select" button. Should there be no entry, parameter change or other action for 60

seconds, the unit will automatically revert into Automatic mode.

During the configuration mode, the monitoring function is still active. This means inevitably, that while adjusting

parameters during operation, it is possible to cause a tripping of the relay.

adjust settings

[press "SELECT"]

Configuration mode "Select" button

Pressing the "Select" key activates the configuration mode, and the following pa

rameters can be enabled or changed within the given limits. Please you note that as

you advance through the configuration screens, by configuring some parameters as

"ON", additional screens must be configured relating to that parameter. If the pa

rameter is configured as "OFF", the additional screens will be disabled and not dis

played.

Software version

Software version

Displays the software version.

SPRACHE/LANGUAGE ----------------

Language selection english/german

The screens can be displayed in German or English.

curr. transform.

ratio     0000/x

CT-Ratio Selection 10 to 6.000/{x} A

The Ratio of the CTs being used is entered here. The CTs should be selected so that

in fault-free operation at generator rated current, at least 60 % of nominal current

flows in the CT-secondary. Failure to use properly a sized CT-Ratio leads to loss of

resolution and inaccuracies in the monitoring functions.

generator nomin.

current    0000A

Generator rated current 5 to 6.000 A

This value is used as reference value for the calculation and display of restraint cur

rent and differential current. The entered value of generator current must be at least

60% of the nominal current of the CT and must not exceed the entered value of  CT

nominal current.

Example CT-Ratio 500/5 A

Range of Generator rated current 300 A to 500 A.

If the nominal value is less than 50% of the transformer ratio, the message "Wrong

Entry" will be displayed on the screen in Automatic mode and the unit will de

activate monitoring functions (the Monitoring LED goes out).

automatic reset

relay       ON

Automatic reset of the relay ON/OFF

Applies only to monitoring level 2 (tripping).

Monitoring level 1 (warning) always Auto-resets.

ON................The relays de-energize automatically when the fault is no longer pre

sent. The screen input "Automatic reset of error text" determines

what happens to the Alarm-text in the display.

OFF..............The relays remain energized until they are reset.

monitoring

ON

Monitoring ON/OFF

ON................Monitoring of the differential current is active and the follow

ingscreens of this option are displayed.

OFF..............The monitoring is de-activated and the following screens are not dis

played.

release limit

Is/In     X=000%

Trigger Value IS/IN (X12) 50 to 300 %

Definition of the threshold characteristic for the monitoring of levels 1 and 2.

This value determines the horizontal position (X12-coordinates of points

P [X12/Y1] and P [X2/Y2]) of the corner points of the Warning and Tripping char

acteristics.

release limit

Id/In     Y=000%

Limit valueId

This value determines the vertical position (Y2-coordinate) of the corner point

P [X12/Y2] of the tripping characteristic (monitoring level2).

pick-up t. Id>IN

release    0.00s

Relay enable delay time for Id>IN (monitoring level 2) 0.04 to 3.00 s

If the differential current surpasses the generator rated current without interruption

over this time period, a fault condition for exceeding the threshold limit will be ini

tiated.

pick-up t. Id

release    0.00s

Relay enable delay time for Id

If the differential current surpasses the adjusted trigger threshold without interrup

tion over this tme period, a fault condition for exceeding the threshold limit will be

initiated.

release time

release    0.00s

Relay disable delay time (monitoring level 2) 0.10 to 3.00 s

Only visible when the screen "Automatic reset of the relay" is configured to

ON .

If the differential current value which initiated the fault condition should fall 2% or

more below the trigger threshold limit and remain uninterrupted for the period of

time configured here, the fault condition will be terminated and the relay output

and the fault text will be reset.

automatic reset

error text   ON

Automatic reset of error text ON/OFF

Only visible when the screen "Automatic reset of the relay" is configured to

ON

ON................The displayed fault text will be automatically deleted, when the fault

conditions are no longer detected.

OFF..............The displayed fault text must be deleted manually, and can only be

done when fault conditions are no longer detected.

automatic reset

error text   00s

Delay for automatic reset of error text 1 to 60 s

Only visible when the screens "Automatic reset of the relay" and "Automatic

reset of error text" are configured to ON

The fault text will automatically delete, when the fault conditions are no longer de

tected for the time period set here.

warning

ON

Warning (monitoring level 1) ON/OFF

ON................The adjustable warning characteristic is being monitored and the fol

lowing screens of this option are displayed.

OFF..............The adjustable warning characteristic is not being monitored and the

following screens of this option are not displayed.

warning limit

Id/IN    Y=00.0%

Trigger value Id/IN (monitoring level1. Y1) 3.0 to 40.0 %

Only visible when the screen "Warning" is configured to ON.

This value determines the vertical position of the corner point of the warning char

acteristic. The horizontal position (X12) is identical with that of the trip character

istic. Usually the warning limit is lower than the trip limit value.

pick-up time

warning    0.00s

Enable delay time of the "warning" relay (monitoring level1) 0.04 to 3.00 s

Only visible when the screen "Warning" is configured to ON.

If the differential current exceeds the warning threshold curve without interruption

over this time period, the control recognizes that the warning limit has been ex

ceeded.

release time

warning    0.00s

Relay disable delay time (monitoring level 1) 0.10 to 3.00 s

Only visible when the screen "Warning" is configured to ON

If the differential current value which initiated the warning should fall 2% or more

below the trigger threshold limit and remain uninterrupted for the period of time

configured here, the fault condition will be terminated and the relay output and

fault text will be reset.

display value

Id           [-]

Display – measured value Id in [%] / [A]

[%]...............The percentage of the rated generator current that is measured is dis

played on the screen.

[A]:...............The measured absolute values are displayed on the screen.

display value

IS           [-]

Display – measured value IS in [%] / [A]

[%]...............The percentage of the rated generator current that is measured is dis

played on the screen.

[A]:...............The absolute measured values are displayed on the screen.



  • WOODWARD 5448-890 SPM-D10 Series One Breaker Synchronizer
  • FOXBORO 43AP-FA42D/PB-AA 43AP Pneumatic Indicating Controllers
  • Stucke Elektronik SYMAP®G generator protection
  • Stucke Elektronik SYMAP®F feeder protection
  • Stucke Elektronik SYMAP®ECG engine control and generator protection
  • Stucke Elektronik SYMAP®EC Engine Control
  • Stucke Elektronik SYMAP®ARC Arc protection system
  • Stucke Elektronik SYMAP®R Digital protection system
  • Stucke Elektronik SYMAP® Compact Digital protection and control equipment
  • LEYBELOD SV40 BI Single-stage, oil-sealed rotary vane pump
  • LEYBELOD TURBOVAC 361 (C) Suspension turbomolecular pump
  • LAND M2300/1100C-V Industrial Control Module
  • LAMBDA LZS-1500-3 Single Output Industrial Power Supplies
  • LAMBDA LZS-A1500-3-001 POWER SUPPLY
  • LAMBDA HWS1500-24 Power supply
  • Kongsberg K-Chief Control Room Panel (CRP) 603525
  • Kongsberg MSI-12 Input/Output Module 339368
  • Kongsberg dPSC Dual Process Segment Controller Module 8100183
  • HHirschmann Modular OpenRail Fast Ethernet switch 8-24 ports MS20-1600SAAEHH08.0
  • Hirschmann MM20-Z6Z6Z6Z6SAHH ETHERNET / Fast-ETHERNET Media Modules
  • Hirschmann MM2-2FXM3/2TX1 ETHERNET / Fast-ETHERNET Media Modules
  • Hirschmann Industrial ETHERNET Switch MICE MS20/MS30
  • Hirschmann MACH102-24TP-FR Gigabit Ethernet industrial workgroup switch
  • Hirschmann MM2-4TX1 MICE switch medium module
  • Hirschmann MICE switch medium module MM2-2FXS2
  • ABB AFS670 19" Ruggedized Switch AFS670-EREEDDDSSEEEEEEEPZYX05.1.0
  • NI Controller for VXI VXIPC-871B
  • GE VMIVME-1150 Serial Communications Controller
  • GE Hydran M2-X Enhanced Monitoring with Extended Sensor Life
  • GE IC660BBD022 I/O module
  • GE Digital Energy D20 Analog Input Module
  • Foxboro FBM I/O cards PBCO-D8-009
  • GE SR750-P5-G5-S5-HI-A20-R-E Multilin Relay
  • ABB 3BSE019050R1000 PFTL 301E 1,0kN, Load cell
  • Foxboro DNBT P0971WV Dual-node bus module of I/A series
  • EPRO MMS6210 Dual-channel axial displacement measurement module
  • EMERSON PMCspan PMC Expansion Mezzanine
  • EMERSON KJ3242X1-BK1 12P4711X042 S-Series H1 Card
  • EMERSON KJ4006X1-BD1 Interface Terminal Block
  • EMERSON KJ4001X1-CK1 40-Pin Mass Termination Block
  • ABB UCD224A103 Industrial controller module
  • ABB ARCOL 0339 Solid-state motor controller
  • ABB UFC718AE01 HIEE300936R0101 Main Circuit Interface Board
  • Abaco VME-REPEATL-485 VMEBus Repeaters
  • Abaco VME-4900 Digital-to Synchro/Resolver Board
  • Abaco VME-4911 digital converter board
  • Abaco XM-664-80 Transition module with rear I/O access to VIPC664
  • Abaco TPMCC 6U VME triple PMC carrier for use with the V5C SBC
  • Abaco VIPC8243 is an intelligent 6U VME carrier board
  • Abaco DCPMC Conduction-cooled or Rugged PMC Carrier
  • Abaco CP237 is a 6U CompactPCI Card
  • Abaco VME-3413 32-Channel Signal Conditioning Board
  • Abaco VME-3125 VME Analog I/O Input Boards
  • Alstom GE SPU232.2. 029.366.817 Single Processor Unit SPU2322
  • ALSTOM COP232.2 VME A32/D32, 029.232 446 controller unit
  • ICS TRIPLEX T8111C​ Trusted TMR Processor
  • VMIC VMIVME-7740 VME Single Board Compute 750
  • foxboro FBM232 Field Device System Integrator Module P0926GW
  • GE 04220HL21204A IPC Control Module
  • ABB 3BSE000860R1 SB510 Backup Power
  • ABB 0504994880 Controller unit
  • ABB PFSA140 3BSE006503R1 Industrial robot Supply Unit
  • ABB 5SHX1445H0002 3BHL000387P0101 POWER IGCT unit
  • ABB 128877-103 CABLE, SP1200 IR DET.
  • ABB CI853K01 and TP853 RS-232C Interface
  • ABB REM610 MOTOR PROTECTION RELAY REM610C11HCNR
  • ABB IGBT 5SDF0860H0003 5SDF1045H0002 unit
  • ABB TC512V1 3BSE018059R1 RS485 Twisted pair Modem
  • ABB DO880 S800HI 3BSE028602R1 Digital Output
  • ABB GDD360C 3BHE047217R0101 Advanced Automation Solution
  • ABB UCD240A101 3BHE022287R0101 controller unit
  • ABB AC800F Ethernet Module AM811F 3BDH000050R1​
  • ABB AC800F Module AM801F 3BDH000040R1
  • ABB SD802F 3BDH000012R1 POWER UNIT
  • ABB operation panel PM820-2 3BSE010798R1 system module
  • ABB operation panel PM820-1 3BSE010797R1 system module
  • ABB CI857K01 3BSE018144R1 INSUM Ethernet Interface
  • ABB PM861/PM861AK01 and TP830 Processor Unit
  • ABB SA811F 3BDH000013R1 Power Supply 115/230 VAC
  • ABB 751010R0815 1VC1T0374A00R unit
  • 5SGY35L4510 Robot high voltage board Brand ABB
  • ABB HVC-02B 3HNA024966-00103 Robot high voltage board Brand HVC02B
  • ABB SLMG99 UNIT
  • ABB 086406-002 PWA.SIOC. SMART I/O CALIP 086407-502
  • ABB UCD208A101 3BHE020018R0101 UNIT
  • ABB UAD154A 3BHE026866R0101 UNIT
  • ABB GCD207B101 3BHE024642R0101 controller card
  • ABB TB820V2 S800 Modulebus module 3BSE013208R1
  • ABB UDD406A 3BHE041465P201 Control unit
  • ABB PPD113B01-10-150000 3BHE023784R1023 unit CPU module
  • ABB 5SHY35L4512 3BHE014105R0001 5SXE08-0166 IGCT unit
  • ABB Backplane Uni Type3+housing FETD685A1156U01
  • ABB 07DC91C GJR5251400R0202 Digital input and output Unit
  • ABB UNS2881b-P,V1 3BHE009319R0001 UNS2881BPV1 Inspirational system
  • ABB UNS2880B-P,V2 3BHE014967R0002 UNS2880B-PV1 Inspirational system
  • ABB CI810B 3BSE020520R1 AF 100 Fieldbus Comm. Interface
  • ABB FM9925a-E HIEE451116R0001 Interface Module Card
  • Bently 2300/25 0002 Vibration Monitors
  • Bently 2300/20 0002 Vibration Monitors
  • ALSTOM VP327 020-23EU 75X-6025-29 Control mainboard VP32702
  • ABB NE802 3BSE080237R1 Industrial switch
  • ABB 3BSE080207R1 NE810 Industrial switch
  • MOTOROLA MVME2400 VME Processor Modules
  • ABB 3BHE021481R0001 intelligent current distr UNIT
  • MOTOROLA MVME2434 VME Processor Modules
  • METSO PDP606 CONTROLLER unit
  • WOODWARD PG-PL-29 Governor 8577-613
  • GE IS230TNRLH1B Combination module kit Mark VI
  • GE IS230TNAIH2C Combination module kit Mark VI
  • ABB 3ASC25H204 DAPU 100 Control board I/O
  • ABB 3BHE014070R0101 V PPC905AE101 CCB-2 COMPLETE
  • ABB PRC3BSE050198R1 PM866K01 Processor Unit
  • Kongsberg RAIV400 600370 Remote Analogue Input
  • ABB SPSED01 event sequence module
  • ABB HIEE300900R0001 PP C322 BE01 PSR-2 processor + fieldbus
  • ABB 3BHE003604R0102 UFC765AE102 circuit board
  • ABB ACU-01B 3HNA024871-001 Robot controller
  • ABB XVC770BE101 3BHE021083R0101 circuit board
  • ABB UAC383AE01 HIEE300890R0001 Module
  • ABB REF610C11LCNP FEEDER PROTECTION RELAY
  • ABB MT91 Operator Panel MT-91-ARC FP A
  • ABB XUD194 XUD194A 3BHC018137R0001 module base
  • ABB 5SHY4045L0001 3BHB018162 3BHE009681R0101 GVC750BE101
  • ABB G2000A5.7ST graphical operation panel (HMI)
  • ABB 3BHE017628R0002 PPD115A02 SG579989013
  • ABB Motor Protection and Control REM615 Product Guide
  • ABB PFTL101B 3BSE004185R1 2.0KN sensor
  • ABB PFCL201CE 50KN 3BSX802939-108 sensor