Блок питания VM600Mk2/VM600 RPS6U
Виброметр питания VM600Mk2 / VM600 RPS6U
KEY FEATURES AND BENEFITS
• From the vibro-meter ® product line
• Power supply for VM600Mk2/ VM600 ABE04x 19 ″ system racks with a height of 6U
• Input: AC-input and DC-input versions
• Outputs: +5 VDC and ±12 VDC • Output over-voltage, short-circuit and overload protection
• Status indicators
• High-power, high-performance, high efficiency
• Minimal derating within the operating  temperature range
APPLICATIONS
• VM600Mk2/ VM600 machinery protection and/ or condition monitoring systems
• One RPS6U rack power supply powers a full rack of modules (cards)
• Two RPS6U rack power supplies enable rack  power supply redundancy
DESCRIPTION
The VM600Mk2/ VM600 RPS6U rack power supplies  are designed for use in the VM600Mk2/ VM600  series of machinery protection systems and  condition and performance monitoring systems,  from Meggitt’s vibro-meter ® product line.  A VM600Mk2/ VM600 RPS6U rack power supply is  installed in the front of a VM600Mk2/ VM600 ABE04x  system rack (19 ″ system racks with a standard  height of 6U) and connects via two high-current  connectors to the VME bus of the rack’s  backplane. The RPS6U power supply provides  +5 VDC and ±12 VDC to the rack itself and all  installed modules (cards) in the rack via the rack’s  backplane.
DESCRIPTION (continued)
Either one or two VM600Mk2/ VM600 RPS6U rack  power supplies can be installed in a VM600Mk2/  VM600 ABE04x system rack. A rack with one  RPS6U power supply (330 W version) supports the  power requirements for a full rack of modules  (cards) in applications with operating  temperatures up to 50 °C (122 °F).  Alternatively, a rack can have two RPS6U power  supplies installed in order to either support rack  power supply redundancy or in order to supply  power to the modules (cards) non-redundantly  over a wider range of environmental conditions.  A VM600Mk2/ VM600 ABE04x system rack with two  RPS6U power supplies installed can operate  redundantly (that is, with rack power supply  redundancy) for a full rack of modules (cards).  This means that if one RPS6U fails, the other will  provide 100 % of the rack’s power requirement so  that the rack will continue to operate, thereby  increasing the availability of the machinery  monitoring system.  Note: This is known as a redundant RPS6U rack  power supply configuration.  A VM600Mk2/ VM600 ABE04x system rack with two  RPS6U power supplies installed can also operate  non-redundantly (that is, without rack power  supply redundancy). Typically, this is only  necessary for a full rack of modules (cards) in  applications with operating temperatures above  50 °C (122 °F), where RPS6U output power derating  is required.  Note: Even though two RPS6U rack power supplies  are installed in the rack, this is not a redundant  RPS6U rack power supply configuration.  The number and type of RPS6U power supplies  installed in a VM600Mk2/ VM600 ABE04x system  rack, together with the number of modules  (cards) installed and the environmental  conditions, helps determine the mode of  operation of the RPS6U power supplies as either  redundant or non-redundant. See also Ordering  information on page 16.  Different versions of the RPS6U rack power supply  enable a VM600Mk2/ VM600 ABE04x system rack  to be powered using external AC and/or DC  mains supplies. All RPS6U power supplies support a  wide input voltage range.  A power supply check relay, available on the  associated rear panel at the rear of a VM600Mk2/  VM600 ABE04x system rack, is used to indicate  that the RPS6U power supplies are operating  normally. Refer to the VM600Mk2/ VM600 ABE04x  system rack data sheet for further information.  In applications where the VM600Mk2/ VM600  ABE04x system rack is powered by an AC mains  supply, a VM600Mk2/ VM600 ASPS auxiliary sensor  power supply can also be included in the rack.  The ASPS provides +24 VDC outputs which can be  used by external sensor/measurement chain  hardware such as front-end sensors, signal  conditioners and galvanic separation units.  For further information, contact your local  Meggitt representative.
Notes
1. In 2016, the RPS6U rack power supply was improved to provide a higher output power of 330 W with higher-performance and higher-efficiency, which required a redesign of the underlying power supply circuitry. Accordingly, the different versions of the RPS6U rack power supply in use are:
• Later versions of the RPS6U (PNR 200-582-x00-02h or later) that define the power as a total maximum output power of 330 W, with nominal output (supply) voltages of +5 VDC up to 50 A, +12 VDC up to 8 A and −12 VDC up to 4 A. Note: The total maximum output power of 330 W is a combination load for all outputs as the +5 VDC and ±12 VDC outputs are usually not simultaneously loaded to the maximum in practice. For example, if the +5 VDC output is at its maximum rated load (5.35 V × 50 A = 267.5 W), then the combined loads on the +12 VDC and −12 VDC outputs must not exceed 62.5 W.