KONG -Y
NameDescriptionContent
Location:

Woodward ESDR 4 Current Differential Protection Relay

From:Woodward | Author:kongjiang | Time :2026-01-20 | 1389 Browse: | 🔊 Click to read aloud ❚❚ ▶ | Share:

mode until the terminal is de-energized.

If this input remains energized for at least 1 s, the faults detected in monitoring

level 2 are reset. This means that the relays will be de-energized and the text display

will be deleted from the screen as long as the monitored currents are not exceeding

the configured threshold level.

When this input is energized, the differential protection is disabled.This means that

the differential current is not monitored, no relay can be enabled and no text is dis

played.

This relay becomes enabled when the unit detects threshold limit 2 (main stage) has

been exceeded. The configured differential current characteristics and delay time will

determine how relay 1 functions.

This relay becomes enabled when the unit detects threshold limit 2 (main stage) has

been exceeded. The configured differential current characteristics and delay time will

determine how relay 2 functions.

This relay becomes enabled when the unit detects threshold limit 1 has been ex

ceeded. The configured differential current characteristics and delay time will deter

mine how relay 4 functions.

This relay is enabled when the unit is operational and the differential current is being

monitored. The relay becomes disabled if the monitoring is deactivated through any

of the following reasons:

• the internal self-monitoring has detected a malfunction of the unit. A correct func

tioning of the unit cannot be guaranteed and corrective action may be necessary.

• the set values for parameter "CT-ratio" or parameter "Generator Current" are out

side the permissible limits (see page 19).

• the digital input "Blocking" is energized.

• the parameter "Monitoring" is configured to "Off".

When in configuration mode (simultaneous pressing of "Digit↑" and "Cursor→"), the configuration screen can

be advanced by pressing the "Select" button. Should there be no entry, parameter change or other action for 60

seconds, the unit will automatically revert into Automatic mode.

During the configuration mode, the monitoring function is still active. This means inevitably, that while adjusting

parameters during operation, it is possible to cause a tripping of the relay.

adjust settings

[press "SELECT"]

Configuration mode "Select" button

Pressing the "Select" key activates the configuration mode, and the following pa

rameters can be enabled or changed within the given limits. Please you note that as

you advance through the configuration screens, by configuring some parameters as

"ON", additional screens must be configured relating to that parameter. If the pa

rameter is configured as "OFF", the additional screens will be disabled and not dis

played.

Software version

Software version

Displays the software version.

SPRACHE/LANGUAGE ----------------

Language selection english/german

The screens can be displayed in German or English.

curr. transform.

ratio     0000/x

CT-Ratio Selection 10 to 6.000/{x} A

The Ratio of the CTs being used is entered here. The CTs should be selected so that

in fault-free operation at generator rated current, at least 60 % of nominal current

flows in the CT-secondary. Failure to use properly a sized CT-Ratio leads to loss of

resolution and inaccuracies in the monitoring functions.

generator nomin.

current    0000A

Generator rated current 5 to 6.000 A

This value is used as reference value for the calculation and display of restraint cur

rent and differential current. The entered value of generator current must be at least

60% of the nominal current of the CT and must not exceed the entered value of  CT

nominal current.

Example CT-Ratio 500/5 A

Range of Generator rated current 300 A to 500 A.

If the nominal value is less than 50% of the transformer ratio, the message "Wrong

Entry" will be displayed on the screen in Automatic mode and the unit will de

activate monitoring functions (the Monitoring LED goes out).

automatic reset

relay       ON

Automatic reset of the relay ON/OFF

Applies only to monitoring level 2 (tripping).

Monitoring level 1 (warning) always Auto-resets.

ON................The relays de-energize automatically when the fault is no longer pre

sent. The screen input "Automatic reset of error text" determines

what happens to the Alarm-text in the display.

OFF..............The relays remain energized until they are reset.

monitoring

ON

Monitoring ON/OFF

ON................Monitoring of the differential current is active and the follow

ingscreens of this option are displayed.

OFF..............The monitoring is de-activated and the following screens are not dis

played.

release limit

Is/In     X=000%

Trigger Value IS/IN (X12) 50 to 300 %

Definition of the threshold characteristic for the monitoring of levels 1 and 2.

This value determines the horizontal position (X12-coordinates of points

P [X12/Y1] and P [X2/Y2]) of the corner points of the Warning and Tripping char

acteristics.

release limit

Id/In     Y=000%

Limit valueId

This value determines the vertical position (Y2-coordinate) of the corner point

P [X12/Y2] of the tripping characteristic (monitoring level2).

  • Eaton SPN6084LEAXX2F Power Defense SB
  • Eaton MPNC4N3LEAXXSW Magnum low voltage power circuit breaker
  • EatonSP N8403YEAXX2H Power Defense SB
  • Eaton MPS8604WEAXX2C Magnum low voltage power circuit breaker
  • Eaton MPS8404WEAXXSW Magnum low voltage power circuit breaker
  • Eaton MPN6504LEAXX3A
  • Eaton MPSC323VEAXX2A Magnum low voltage power circuit breaker
  • Eaton SPS6304WEAXX2F Power Defense SB
  • Eaton MPN6504LEAXX2H Magnum low voltage power circuit breaker
  • Eaton MPSC504HEAXX2H Magnum low voltage power circuit breake
  • Eaton SPN85N3LEAXX2F Power Defense SB
  • Eaton SPN6403CEAXX2F Power Defense SB
  • Eaton MPSC5N4MEAXX3A Power Defense SB
  • Eaton SPSC124WEAXX2A Power Defense SB
  • Eaton SPS85A4WEAXX2H Power Defense SB
  • Eaton SPSC5N4MEAXX2A Power Defense SB
  • Eaton MPN8403VEAXX2H Magnum low voltage power circuit breaker
  • NZMB2-4-A200 MCCB NZM, NZM2 TM and Elec
  • Eaton NZMN1-A63 Series NZM complete molded case circuit breaker
  • Eaton NZMB1-S26-CNA Series NZM complete molded case circuit breaker
  • Eaton NZMH2-A25-NA Series NZM complete molded case circuit breaker
  • NZMH2-A200-BT-NA Eaton Series NZM complete molded case circuit breaker
  • NZMN4-VEF1200-NA Eaton Series NZM complete molded case circuit breaker
  • NZMH2-AF250-NA MCCB NZM, NZM2 TM and Elec
  • NZMB1-AF60-NA Eaton Series NZM complete molded case circuit breaker
  • NZMN1-A50 Eaton Series NZM complete molded case circuit breaker
  • NZMH2-A80-NA Eaton Series NZM complete molded case circuit breaker
  • Eaton Cutler-Hammer HFD3030 6639C86G87 3 Pole 30A 600V Circuit Breaker
  • Moeller XV-230-57CNN-1-13-1 HMI PLC Panel Touchscreen 5.7"
  • EATON CEAG CU CG-S , 40071360300 Control Unit
  • EATON SDN90186 MOTOR CONTROL CENTER
  • EATON HMCP150U4 CIRCUIT BREAKER
  • Eaton 7801C57 Digitrip Optimizer Hand Held Programmer
  • Eaton HMCP400R5 Circuit Breaker
  • EATON MP-3000 SAFETY RELAY 66D2032GX1
  • EATON PGGLOBL1701DPRO 1785T Touch Panel
  • Eaton, Moeller, Easy MFD-CP8-NT
  • Eaton WL-35717F Vacuum Interrupter
  • EATON VICKERS EEA-PAM-535-A-32 AMPLIFIER CARD
  • EATON FP5000-00 / FP5200-00 66D2041G11 FEEDER PROTECTION RELAY
  • Eaton IQ-504 120VAC Modular Overload Relay
  • Beckhoff CX5620-0225    CPU module
  • Beckhoff CX5620-0220    CPU module
  • Beckhoff CX5620-0215    CPU module, Beckhoff RT Linux®
  • Beckhoff CX5620-0210 CPU module, Beckhoff RT Linux®
  • Beckhoff CX5620-0195    CPU module
  • Beckhoff CX5620-0190    CPU module
  • Beckhoff CX5620-0185    CPU module
  • Beckhoff CX5620-0175    CPU module
  • Beckhoff CX5620-0170  CPU module
  • Beckhoff CX5620-0163    CPU module
  • Beckhoff CX5620-0162 CPU module
  • Beckhoff CX5620-0161 CPU module
  • Beckhoff CX5620-0160 CPU module
  • Beckhoff CX5620-0100 CPU module
  • Beckhoff CX5120-0195    CPU module
  • Beckhoff CX5120-0190 CPU module
  • Beckhoff CX5120-0185 CPU module
  • Beckhoff CX5120-0175 CPU module
  • Beckhoff CX5120-0170    CPU module
  • Beckhoff CX5120-0163    CPU module
  • Beckhoff CX5120-0162    CPU module,
  • Beckhoff CX5120-0161    CPU module
  • Beckhoff CX5120-0160 CPU module,
  • Beckhoff CX5120-0150 CPU module
  • Beckhoff CX5120-0143 CPU module
  • Beckhoff CX5120-0142 CPU module
  • Beckhoff CX5120-0141 CPU module, Microsoft Windows 10 IoT Enterprise 2016 LTSB
  • Beckhoff CX5120-0140 CPU module
  • Beckhoff CX5120-0130 CPU module
  • Beckhoff CX5120-0123 CPU module
  • Beckhoff CX5120-0122 CPU module
  • Beckhoff CX5120-0120 CPU module
  • Beckhoff CX5120-0113 CPU module
  • Beckhoff CX5120-0112 CPU module
  • Beckhoff CX5120-0111 CPU module
  • Beckhoff CX5120-0110 CPU module
  • Beckhoff CX5120-0100 CPU module, no operating system
  • Beckhoff C6017-0040 | Fanless ultra-compact Industrial PC
  • Beckhoff C6017 | Fanless ultra-compact Industrial PC
  • Beckhoff C6015-0030  | Fanless ultra-compact Industrial PC
  • Beckhoff C6015-0040 | Fanless ultra-compact Industrial PC
  • Beckhoff C6015 | Fanless ultra-compact Industrial PC
  • Beckhoff CX2500-M510 | Fieldbus master module
  • Beckhoff CX2500-M310 | Fieldbus master module
  • Beckhoff CX2500-B510 | Fieldbus slave module
  • Beckhoff CX2500-B310 | Fieldbus slave module PROFIBUS for CX20xx, CX52x0. CX53x0. CX56x0
  • Beckhoff CX2500-0070 | USB 3.0 module for CX20xx, CX52xx, CX53x0. CX56x0
  • Beckhoff CX2500-0062 | 2.5 Gbit Ethernet module for CX20xx, CX52x0. CX53x0. CX56x0
  • Beckhoff CX2500-1061 | Power over Ethernet module for CX20xx, CX52x0. CX53x0. CX56x0
  • Beckhoff CX2500-1060 | Ethernet module for CX20xx, CX52x0. CX53x0. CX56x0
  • Beckhoff CX2500-0031 | Serial Interface RS485/RS422
  • Beckhoff CX2500-0030 | Serial Interface RS232 for CX20xx, CX52x0. CX53x0. CX56x0
  • Beckhoff CX5230-0195 CPU module
  • Beckhoff CX5230-0190    CPU module
  • Beckhoff CX5230-0175    CPU module,
  • Beckhoff CX5230-0170  CPU module
  • Beckhoff CX5230-0100    CPU module, no operating system, no TwinCAT
  • Beckhoff CU8130-0240 | UPS modul, battery-backed
  • Beckhoff CU8130-0120 | UPS module, battery-backed
  • Beckhoff CU8110-0120 | UPS module, capacitive
  • Beckhoff CU8110-0060 | UPS module, capacitive
  • Beckhoff CX5130-0195    CPU module
  • Beckhoff CX5130-0190    CPU module
  • Beckhoff CX5130-0185 CPU module
  • Beckhoff CX5130-0170    CPU module
  • Beckhoff  CX5130-0163 CPU module, Microsoft Windows 10 IoT Enterprise 2019 LTSC, 32 bit
  • Beckhoff  CX5130-0162    CPU module
  • Beckhoff CX5130-0161  CPU module
  • Beckhoff CX5130-0160    CPU module
  • Beckhoff CX5130-0155  CPU module
  • Beckhoff CX5130-0150    CPU module
  • Beckhoff CX5130-0143 CPU module
  • Beckhoff CX5130-0142 CPU module
  • Beckhoff CX5130-0140    CPU module
  • Beckhoff CX5130-0135 CPU module
  • Beckhoff CX5130-0130 CPU module
  • Beckhoff CX5130-0125    CPU module
  • Beckhoff CX5130-0123    CPU module
  • Beckhoff CX5130-0122    CPU module
  • Beckhoff CX5130-0121 CPU module
  • Beckhoff CX5130-0115    CPU module,
  • Beckhoff CX5130-0113    CPU module
  • Beckhoff CX5130-0112   CPU module
  • Beckhoff CX5130-0111   CPU module
  • Beckhoff CX5130-0110 CPU module, Microsoft Windows Embedded Compact 7. no TwinCAT
  • Beckhoff CX5130-0100  CPU module, no operating system, no TwinCAT
  • DEIF FAS-113DG Synchronisation & circuit breaker closing